Reliable RFC30 User manual

The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Bulletin 006 Rev. G
Bulletin 006 Rev. G
Model RFC30 (SIN RA0611)
Model RFC43 (SIN RA0612)
Model RFC49 (SIN RA0616)
Residential Flat Concealed
Sprinklers
A Residential Flat Concealed
Sprinkler engineered for a minimum
design density of 0.05 gpm/ft2with
low GPM requirements.
Features
1. Very low water flow requirements.
2. Cover plate attachment (Plain or Perforated)
with ½” (13mm) Total adjustment.
3. Thread-On/Thread-Off or Push-On/Thread
Off cover attachment option.
4. Smooth aesthetic ceiling profile.
5. Available in brass, chrome and black plated
or painted finishes.
Listings & Approval
1. Listed by Underwriters Laboratories, and
certified by UL for Canada (cULus)
2. NYC MEA 258-93-E
UL Listing Categories
Residential Automatic Sprinklers
UL Guide Number
VKKW
Product Description
Model RFC30, RFC43 and RFC49 Concealed Residen-
tial Sprinklers are fast response residential fusible solder
link automatic sprinklers. Residential sprinklers differ from
standard sprinklers primarily in their response time and
water distribution patterns.
Model RFC30, RFC43 and RFC49 sprinklers discharge
water in a hemispherical pattern below the sprinkler de-
flector. Residential distribution patterns are higher and
generally contain a finer droplet size than standard sprin-
kler patterns.
The combination of speed of operation and high dis-
charge pattern required for residential sprinklers has dem-
onstrated, in fire testing, an ability for controlling residen-
tial fires, and thereby providing significant evacuation time
for occupants.
The RFC30, RFC43 and RFC49 Sprinklers provide the
best form of fire protection by combining an attractive ap-
pearance and ½” (13mm) of cover adjustment for ease of
installation. The small diameter cover plate is easily and
positively attached and blends into the ceiling, concealing
the most dependable fire protection available, an automat-
ic sprinkler system.
The RFC30, RFC43 and RFC49 are UL Listed Residential
Sprinklers to be installed in the residential portions of any
occupancy in accordance with NFPA 13, 13R, & 13D.
The RFC30, RFC43 and RFC49 can reduce the need for
precise cutting of drop nipples. The threaded cover plate
assembly can be adjusted without tools to fit accurately
against the ceiling. The fire protection system need not be
shut down to adjust or remove the cover plate assembly.
Application and Installation
The RFC30, RFC43 and RFC49, for residential installa-
tions, use a 165°F (74°C) fusible solder link in a tuning fork
style sprinkler frame with a drop-down deflector. This as-
sembly is recessed into the ceiling and concealed by a flat
cover plate. The cover plate is attached to the skirt, using
135°F (57°C) ordinary temperature classification solder.
When the ceiling temperature rises, the solder holding
the cover plate releases the cover allowing the deflector
to drop into position and exposing the sprinkler inside to
2.
ceiling temperature. The subsequent operation of the sol-
der link opens the waterway and causes the deflector to
drop into position to distribute the discharging water in a
hemispherical pattern below the sprinkler deflector. Any
adjustment of thread engagement between the cover
plate and cup will assure that the drop-down deflector is
properly located below the ceiling. The residential distri-
bution pattern contains a finer droplet size than a standard
sprinkler, and the pattern produces significantly higher
wall wetting.
After a 25/8inch diameter hole is cut in the ceiling, the
sprinkler is to be installed with the Model FC Wrench.
When installing a sprinkler, the wrench is first positioned
into the sprinkler/cup assembly and around the hexagonal
body of the sprinkler frame. The Wrench must bottom out
against the cup in order to ensure proper, safe installation.
The sprinkler is then tightened into the pipe fitting. When
inserting or removing the wrench from the sprinkler/cup
assembly, care should be taken to prevent damage to
the sprinkler. DO NOT WRENCH ON ANY OTHER PART
OF THE SPRINKLER/CUP ASSEMBLY. MODEL RFC30,
RFC43 AND RFC49 CONCEALED SPRINKLERS MUST
BE INSTALLED ONLY WITH 135°F RATED COVERS.
Note: A leak tight ½” NPT (R1/2) sprinkler joint can be ob-
tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not
tighten sprinklers over maximum recommended torque. It
may cause leakage or impairment of the sprinklers.
Cover assemblies provide up to 1/2” (13mm) of adjust-
ment. Turn the cover clockwise until the flange is in con-
tact with the ceiling. For the push-on/thread-off option, the
cover assembly is pushed onto the cup and final adjust-
ment is made by turning the cover clockwise until the skirt
flange makes full contact with the ceiling. Cover removal
requires turning in the counter-clockwise direction.
In ceilings that have a plenum space above the sprinkler,
the plenum space may have neutral or negative pressur-
ization but must not be positively pressurized. Inspect all
sprinklers after installation to ensure that the gap between
the cover plate and ceiling and the 4 slots in the cup are
all open and free from any air flow impediment.
Temperature Rating
Sprinkler Cover Plate Max. Ambient Temp.
165°F/74°C 135°F/57°C 100°F/38°C
Installation Data: RFC30 (SIN RA0611)
Thread
Size
inch (mm)
K Factor
Sprinkler
Spacing
ft. (m)
Maximum
Distance to
Wall
ft. (m)
Minimum
Distance between
sprinklers
ft. (m)
Minimum Required
Sprinkler Discharge
Flow
gpm (Lpm)
Press.
psi (bar)
½” (15mm)
½” (15mm)
3.0
3.0
12 x 12 (3.6x3.6)
14 x 14 (4.3x4.3)
6 (1.83)
7 (2.13)
8 (2.43)
8 (2.43)
9 (34.1)
10 (37.8)
9.0 (0.62)
11 (0.76)
Note: 1 bar = 100 Kpa
Installation Data: RFC43 (SIN RA0612)
Thread
Size
inch (mm)
K Factor
Sprinkler
Spacing
ft. (m)
Maximum
Distance to
Wall
ft. (m)
Minimum
Distance between
sprinklers
ft. (m)
Minimum Required
Sprinkler Discharge
Flow
gpm (Lpm)
Press.
psi (bar)
½” (15mm)
½” (15mm)
½” (15mm)
½” (15mm)
½” (15mm)
4.3
4.3
4.3
4.3
4.3
12 x 12 (3.6x3.6)
14 x 14 (4.3x4.3)
16 x 16 (4.9x4.9)
18 x 18 (5.5x5.5)
20 x 20 (6.0x6.0)
6 (1.83)
7 (2.13)
8 (2.43)
9 (2.74)
10 (3.05)
8 (2.43)
8 (2.43)
8 (2.43)
8 (2.43)
8 (2.43)
12 (45)
13 (49)
13 (49)
18 (68)
21 (79)
7.8 (0.54)
9.1 (0.63)
9.1 (0.63)
17.5 (1.21)
23.8 (1.64)
Note: 1 bar = 100 Kpa
Installation Data: RFC49 (RA0616)
Thread
Size
inch (mm)
K Factor
Sprinkler
Spacing
ft. (m)
Maximum
Distance to
Wall
ft. (m)
Minimum
Distance between
sprinklers
ft. (m)
Minimum Required
Sprinkler Discharge
Flow
gpm (Lpm)
Press.
psi (bar)
½” (15mm)
½” (15mm)
½” (15mm)
½” (15mm)
½” (15mm)
4.9
4.9
4.9
4.9
4.9
12 x 12 (3.6x3.6)
14 x 14 (4.3x4.3)
16 x 16 (4.9x4.9)
18 x 18 (5.5x5.5)
20 x 20 (6.0x6.0)
6 (1.83)
7 (2.13)
8 (2.43)
9 (2.74)
10 (3.05)
8 (2.43)
8 (2.43)
8 (2.43)
8 (2.43)
8 (2.43)
13 (49)
13 (49)
13 (49)
17 (64.3)
20 (75.7)
7.0 (0.48)
7.0 (0.48)
7.0 (0.48)
12.0 (0.83)
16.7 (1.14)
Note: 1 bar = 100 Kpa
FOR SLOPED CEILING APPLICATIONS SEE RASCO BULLETIN 035.
3.
Maintenance
Model RFC30, RFC43 and RFC49 Concealed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
tle vacuuming. Remove any sprinkler cover plate assem-
bly which has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated sprinklers. Prior to installation, sprinklers should
be maintained in the original cartons and packaging until
used to minimize the potential for damage to sprinklers
that would cause improper operation or non-operation.
Model RFC30, RFC43 and RFC49 Residential
Concealed Sprinkler Specification
Sprinklers shall be cULus Listed low flow residential con-
cealed sprinklers with drop-down deflector and adjust-
able flat cover plate engineered for a minimum design
density of 0.05 gpm/ft2. Sprinkler frame and deflector
shall be of bronze frame construction having a ½” NPT
thread. Thermal element shall consist of an approved
black-painted beryllium-nickel fusible solder link with
symmetric lever mechanism, maintaining a Teflon-coated
Belleville spring washer and machined brass cap water
seal assembly containing no plastic parts. Sprinkler
K-factor shall be nominal 3.0 (44), 4.3 (62.4), and 4.91
(70) having a 5
/
16”, 3
/
8” and 7
/
16” orifice. Temperature rating
shall be Ordinary 165°F (74°C); cover plate temperature
rating to be 135°F (57°C). Cover plate assembly shall
consist of a brass cover plate and copper alloy retainer
flange allowing a ½” cover plate adjustment. Any secure
engagement between the cover plate and the cup will
assure that the drop-down deflector is properly located
below the ceiling. A plastic protective cap shall be
provided and factory installed inside the sprinkler cup
to protect the drop-down sprinkler deflector from dam-
age, which could occur during construction before the
cover plate is installed. Standard cover finish: [Chrome]
[White] [Specialty – specify]. Residential concealed
sprinklers shall be Reliable Model RFC30, SIN RA0611
(Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006)
or Model RFC49, SIN RA0616 (Bulletin 006).
Ordering Information
Specify:
1. Sprinkler Model
2. Cover Plate Finish
3. Thread-On or
Push-On Feature
Cover Plate Finishes(1)
Standard Finishes
Chrome
White Paint
Special Application
Finishes(2)
Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome
(1) Other finishes and colors are
available on special order.
Consult factory for details.
Coverplate custom paint is
semi-gloss, unless specified
otherwise.
(2) For the perforated style cover-
plate, consult factory for avail-
ability on these and other cus-
tom finishes.
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 05/12 P/N 9999970261
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
• Automatic sprinklers
• Flush automatic sprinklers
• Recessed automatic sprinklers
• Concealed automatic sprinklers
• Adjustable automatic sprinklers
• Dry automatic sprinklers
• Intermediate level sprinklers
• Open sprinklers
• Spray nozzles
• Alarm valves
• Retarding chambers
• Dry pipe valves
• Accelerators for dry pipe valves
• Mechanical sprinkler alarms
• Electrical sprinkler alarm switches
• Water flow detectors
• Deluge valves
• Detector check valves
• Check valves
• Electrical system
• Sprinkler emergency cabinets
• Sprinkler wrenches
• Sprinkler escutcheons and guards
• Inspectors test connections
• Sight drains
• Ball drips and drum drips
• Control valve seals
• Air maintenance devices
• Air compressors
• Pressure gauges
• Identification signs
• Fire department connection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Reliable...For Complete Protection

This manual suits for next models

2

Other Reliable Irrigation System manuals

Reliable J112 Pendent Manual

Reliable

Reliable J112 Pendent Manual

Reliable F1FR80 Series User manual

Reliable

Reliable F1FR80 Series User manual

Reliable J112SS Series Manual

Reliable

Reliable J112SS Series Manual

Reliable Non-Ferrous Concealer User manual

Reliable

Reliable Non-Ferrous Concealer User manual

Reliable DD56-6 Manual

Reliable

Reliable DD56-6 Manual

Reliable F156 Series User manual

Reliable

Reliable F156 Series User manual

Reliable G VELO Pendent Manual

Reliable

Reliable G VELO Pendent Manual

Reliable F156 Series User manual

Reliable

Reliable F156 Series User manual

Reliable RFC43 User manual

Reliable

Reliable RFC43 User manual

Reliable Pantman F1 User manual

Reliable

Reliable Pantman F1 User manual

Reliable GFR VELO–ECOH Manual

Reliable

Reliable GFR VELO–ECOH Manual

Reliable F3-80 Series Manual

Reliable

Reliable F3-80 Series Manual

Reliable RFC Series Manual

Reliable

Reliable RFC Series Manual

Reliable F1 LO User manual

Reliable

Reliable F1 LO User manual

Reliable F1FR-FS56 Manual

Reliable

Reliable F1FR-FS56 Manual

Reliable F1FR56-300 Series Manual

Reliable

Reliable F1FR56-300 Series Manual

Reliable F1FR40 Manual

Reliable

Reliable F1FR40 Manual

Reliable RFC56 User manual

Reliable

Reliable RFC56 User manual

Reliable G5 Series User manual

Reliable

Reliable G5 Series User manual

Reliable F3-80 Series User manual

Reliable

Reliable F3-80 Series User manual

Reliable F1FR User manual

Reliable

Reliable F1FR User manual

Reliable G5-56 Manual

Reliable

Reliable G5-56 Manual

Reliable F1FR User manual

Reliable

Reliable F1FR User manual

Reliable MBEC-14 Manual

Reliable

Reliable MBEC-14 Manual

Popular Irrigation System manuals by other brands

Hunter Hydrawise Ready manual

Hunter

Hunter Hydrawise Ready manual

Kärcher HKF 50 E manual

Kärcher

Kärcher HKF 50 E manual

Tyco F950 quick start guide

Tyco

Tyco F950 quick start guide

Tyco G2 manual

Tyco

Tyco G2 manual

Western CP600 Operation manual

Western

Western CP600 Operation manual

Viking VK512 K25.2 Technical data

Viking

Viking VK512 K25.2 Technical data

IrriGreen Irrigreen2 Guide

IrriGreen

IrriGreen Irrigreen2 Guide

Tyco 3002B quick start guide

Tyco

Tyco 3002B quick start guide

Westfalia Garten Meister 95 88 11 Original instructions

Westfalia

Westfalia Garten Meister 95 88 11 Original instructions

Viking M Technical data

Viking

Viking M Technical data

Munters Green Field user manual

Munters

Munters Green Field user manual

Tyco RFII Series quick start guide

Tyco

Tyco RFII Series quick start guide

Viking VK3001 Technical data

Viking

Viking VK3001 Technical data

Nelson F75 Big Gun Operation & maintenance instructions

Nelson

Nelson F75 Big Gun Operation & maintenance instructions

Autopot 48Pot XL Set-up guidelines

Autopot

Autopot 48Pot XL Set-up guidelines

Tyco DS-1 Series manual

Tyco

Tyco DS-1 Series manual

Victaulic VicFlex I-VICFLEX.AQC-U installation instructions

Victaulic

Victaulic VicFlex I-VICFLEX.AQC-U installation instructions

Philips sonicare AirFloss Ultra user manual

Philips

Philips sonicare AirFloss Ultra user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.