RenewAire TC7D Series Owner's manual

TC7D-W Wall mount
TC7D-E Enclosure
TC7D-W (Wall Mount)
TC7D-E (Enclosure)
TC7D SERIES DIGITAL TIME CLOCK
Supplemental Installation Manual for Accessories

1.800.627.44992
TC7D Series Digital Time Clock
ACCESSORY
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO
PERSONS, OBSERVE THE FOLLOWING RULES:
Use the unit only in the manner intended by the manufacturer. If
you have questions, contact the manufacturer.
Before installing, servicing or troubleshooting the transformer/re-
lay package, switch power off at service panel and lock service
panel to prevent power from being switched on accidentally.
More than one disconnect switch may be required to de-energize
the equipment for servicing.
Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards,
including fire-rated construction codes and standards.
When cutting or drilling into wall or ceiling, do not damage elec-
trical wiring and other hidden utilities.
NEVER place a switch where it can be reached from a tub or
shower.
Intended for use with 24 VAC Class 2 power supplies only.
Do not connect loads that exceed the timer’s switch rating.
Confirm sufficient 24 VAC power is available to operate the timer
and the connected loads.
CAUTION

31.800.627.4499
TC7D Series Digital Time Clock ACCESSORY
1.0 OVERVIEW 4
1.1 SPECIFICATIONS..................................................................................................4
1.2 DIMENSION DRAWINGS .......................................................................................4
2.0 SETTINGS 5
2.1 SETTING INSTRUCTIONS......................................................................................5
3.0 ELECTRICAL 6
3.1 ELECTRICAL SCHEMATICS ...................................................................................6
TABLE OF ILLUSTRATIONS
Figure 1.2.0 TC7D-W Dimensions........................................................................................................4
Figure 1.2.1 TC7D-E Dimensions.........................................................................................................5
Figure 2.1.0 Setting Instructions .........................................................................................................5
TABLE OF SCHEMATICS
Figure 3.1.0 EV90, EV90P, EV130, EV200 and EV300 Schematic .........................................................6
Figure 3.1.1 SL70 Schematic ..............................................................................................................6
Figure 3.1.2 EV450, HE1XIN and HE1.5IN Standard Wiring Schematic ..................................................6
Figure 3.1.3 EV450 ECM Schematic ....................................................................................................7
Figure 3.1.4 HE1X and HE1.5 ECM Schematic......................................................................................7
Figure 3.1.5 HE1XRT, HE1.5RT with Independent Blower Control and HE2X through LE10X Schematic ..7
Figure 3.1.6 RH-W Electric Heater Schematic ......................................................................................7
TABLE OF CONTENTS

1.800.627.44994
TC7D Series Digital Time Clock
ACCESSORY
Operating Voltage: 24VAC 50/60Hz
Switching: Single Pole, Single Throw [SPST]
(can be field-modified to Single Pole, Double Throw [SPDT])
Power consumption: 3.5VA
Switch rating: 10 Amps at 131°F
Operating Temperature Range: 14°F – 131°F
Connections (TC7D-W): (3) 16 GA pigtails (wire nuts not provided)
Connections (TC7D-E): (3) copper screw terminals
Setting Options:
u8 pairs of on-off time of day cycles can be programmed.
uEach on-off cycle can be assigned to any one day of the week, or to the following groups of days:
Monday – Friday; Monday – Saturday; Monday – Sunday; Saturday and Sunday.
uManual Over-ride provided by “On/Auto/Off” switch.
uProgram Reset button clears all settings.
Enclosure (TC7D-W): Requires a 4" x 4" electrical box by others.
uBox must accommodate (4) mounting screws (see drawing).
uMinimum box depth 1.5". White wall plate and mounting screws provided.
Enclosure (TC7D-E): NEMA 3R. (see drawing page 4)
OVERVIEW
1.0 OVERVIEW
1.1 SPECIFICATIONS
4 1/2"
4 1/2"
1 13/16"
3 5/16"
1.2 DIMENSION DRAWINGS
FIGURE 1.2.0 TC7D-W WALL MOUNT DIMENSIONS

51.800.627.4499
TC7D Series Digital Time Clock ACCESSORY
DIMENSIONS ARE APPROXIMATE.
.8750
1.250
7.0 ACCESS
2.750
.940
1.250
6.150
2.060
4.120
1.250
2.500
8.040
ISOMETRIC VIEW
FRONT VIEW
.955
.938
1.875
ø0.8750
Knockout
ø1.1250
Knockout (5)
ø0.2580
Thru
SETTINGS
FIGURE 1.2.1 TC7D-E ENCLOSURE DIMENSIONS
Set Time and Day Slide Set switch to press 1…7 button until arrow points to the correct day
(1=Monday). Press h then m buttons to set correct time. PM indicator shows
noon to 11:59 PM. Slide Set switch to Run. Clock colon will blink.
Set Switch “On” Cycle Slide Set switch to . A “1” indicates the first switch cycle and a “Bulb”
indicates a switch-on (circuit closes). Press 1…7 button until arrows point to
selected day(s) for this cycle. Press h and m buttons to show switch-on time,
noting PM indicator.
Set Switch “Off” Cycle With Set switch at , press button, note switch cycle number changes to
“2” and bulb blanks, indicating switch-off (circuit opens). Press 1…7 button
to match day(s) set for switch cycle “1.” Press h and m buttons to select
switch-off time.
A
utorun Slide Set switch to Run and Mode switch to Auto, switching begins with next
switch-on set time.
Override “On” Slide Mode switch to I. Switch remains on indefinitely (circuit closed).
Override “Off” Slide Mode switch to O. Switch remains on indefinitely (circuit open).
Skip Cycle In automatic run mode, press
x
→button. The next calendar day is skipped.
Setting ERROR If EEE appears, a setting error exists. The switch cycle number in error is
shown. Slide set switch to , press button until cycle is shown, review
this and the following setting to correct error, slide set switch to Run.
Clear any setting Setting slide set switch to , press button to show switch cycle to clear.
Press the button and the skip (x) button simultaneously, hold for several
seconds.
Clear All To erase all settings, Press R.
2.0 SETTINGS
2.1 SETTING INSTRUCTIONS
FIGURE 2.1.0 SETTING INSTRUCTIONS

1.800.627.44996
TC7D Series Digital Time Clock
ACCESSORY
FIGURE 3.1.0 EV90, EV90P, EV130, EV200, EV240, EV300 SCHEMATIC
1
2
3
4
5
TC7D-WTC7D-E
5
4
3
2
11
2
3
BLACK
RED
YEL
24 VAC
ERV INTERNAL CONTROL
WIRING (SIMPLIFIED)
COMM
HIGH OR LOW
SPEED INPUT
SL70
SL70
ELECTRICAL
3.0 ELECTRICAL
3.1 ELECTRICAL SCHEMATICS
FIGURE 3.1.1 SL70 SCHEMATIC
Control Terminals
Unit Internal
Wiring
Not Shown
EV90
EV90P
EV130
EV200
EV240
EV300
24VAC Class II Power Supply
provided by other
1
2
3
4
5
TC7D-WTC7D-E
5
4
3
2
1
EV Residential
1
2
3
4
5
TC7D-WTC7D-E
5
4
3
2
11
2
3
BLACK
RED
YEL
BLUE
RED
YELLOW
The Normally Closed (N.C.) contacts of
one or more additional Low Voltage
Controls may be connected to ERV unit in
parallel with the TC7D-E/W.
Unit's 24VAC
Power Supply
ERV INTERNAL CONTROL
CIsolation
Relay Coil
WIRING (SIMPLIFIED)
BLUE
YEL
YEL
RED
EV450 , 1X,
1.5IN
FIGURE 3.1.2 EV450, HE1XIN AND HE1.5IN STANDARD WIRING SCHEMATIC
NOTE: For EV450
and HE1XIN mod-
els built prior to
1/22/2011, please
call RenewAire Customer
Service at 800-627-4499
or email RenewAireSup-
port@RenewAire.com.
NOTE: There is a
wire on the TC7D
that connects
terminal 1 to terminal 5.
You must cut this wire
to eliminate voltage to
terminal 5.

71.800.627.4499
TC7D Series Digital Time Clock ACCESSORY
ELECTRICAL
The Normally Closed (N.C) contacts of one
or more additional Low Voltage Controls
may be connected to ERV unit's Terminals 1
& 4. Do not apply power to these terminals.
Unit's 24VAC
Power Supply
ERV INTERNAL CONTROL
C
Isolation
Relay Coil or
Damper
Actuator Coil
WIRING (SIMPLIFIED)
1
2
3
4
5
1
2
3
4
5
TC7D-WTC7D-E
5
4
3
2
11
2
3
BLACK
RED
YEL
1X, 1.5RT-LE
C
FIGURE 3.1.5 HE1XRT, HE1.5RT WITH INDEPENDENT BLOWER CONTROL AND HE2X THROUGH LE10X SCHEMATIC
24VAC Class II Power Supply
provided by other
1
2
3
4
5
TC7D-WTC7D-E
5
4
3
2
1
65
4 3 2RC
0-10VDC
24 VAC
COMMON
RH-W
CTH-291
0-10VDC THERMOSTAT
Supplied with RH-W Heaters
When Normally Closed (NC) contacts open at desired times, the thermostat
will operate in Comfort Mode. When NC contacts are across RH-W
thermostat terminals the thermostat will operate in Economy Mode which
reduces the RH-W heater outlet set-point temperature by 8 degrees F.
RH
NOTE: Remove
supplied wires from
the time clock spade
terminals prior to
wiring to a RH-W thermostat
as shown.
FIGURE 3.1.6 RH-W ELECTRIC HEATER SCHEMATIC
NOTE: For HE1XRT
and HE2X through
LE10X models built
prior to 1/22/2011,
please call RenewAire
Customer Service at
800-627-4499 or email
RenewAireSupport@
RenewAire.com.
1
2
3
4
5
TC7D-WTC7D-E
5
4
3
2
11
2
3
Unit's 24VAC
Power Supply
ERV INTERNAL CONTROL
CIsolation Relay
Coil or Damper
Actuator Coil
WIRING (SIMPLIFIED)
1
2
3
10
The Normally Open (N.O.) contacts of one
or more additional Low Voltage Controls
may be connected to ERV unit in parallel
with the TC7D-E and TC7D-W.
EV450 +EC
FIGURE 3.1.3 EV450 ECM SCHEMATIC
1
2
3
4
5
TC7D-WTC7D-E
5
4
3
2
11
2
3
1X and 1.5 +EC
Unit's 24VAC
Power Supply
ERV INTERNAL CONTROL
C
Isolation Relay
Coil or Damper
Actuator Coil
WIRING (SIMPLIFIED)
1
2
8
1
2
8
C
Isolation Relay
Coil or Damper
Actuator Coil
TB
(EA/RA)
TB
(OA/FA)
The Normally Open (N.O.) contacts of one
or more additional Low Voltage Controls
may be connected to ERV unit in parallel
with the TC7D-E and TC7D-W.
FIGURE 3.1.4 HE1X AND HE1.5 ECM SCHEMATIC

About RenewAire
For over 30 years, RenewAire has been a pioneer in enhancing indoor air quality (IAQ)
in commercial and residential buildings of every size.This is achieved while maximizing
sustainability through our fifth-generation, static-plate, enthalpic-core Energy Recovery
Ventilators (ERVs) that optimize energy efficiency, lower capital costs via load reduction and
decrease operational expenses by minimizing equipment needs, resulting in significant energy
savings. Our ERVs are competitively priced, simple to install, easy to use and maintain and have
a quick payback. They also enjoy the industry’s best warranty with the lowest claims due to
long-term reliability derived from innovative design practices, expert workmanship and Quick
Response Manufacturing (QRM).
As the pioneer of static-plate core technology in North America, RenewAire is the largest ERV
producer in the USA. We’re committed to sustainable manufacturing and lessening our
environmental footprint, and to that end our Waunakee, WI plant is 100% powered by wind
turbines. The facility is also one of the few buildings worldwide to be LEED and Green Globes
certified, as well as having achieved ENERGY STAR Building status. In 2010, RenewAire joined
the Soler & Palau (S&P) Ventilation Group in order to provide direct access to the latest in energy-
efficient air-moving technologies. For more information, visit: renewaire.com
201 Raemisch Road | Waunakee, WI | 53597 | 800.627.4499 | RenewAire.com
Member of the S&P Group
Family of Brands
2019 © RenewAire LLC
138200_006_JUN19