1.800.627.44994
TC7D Series Digital Time Clock
ACCESSORY
OVERVIEW
1.0 OVERVIEW
1.1 SPECIFICATIONS
NOTE: When the
time comes to
replace the battery,
use a coin to
remove the battery cover
to avoid stripping the
plastic cover.
Operating Voltage: 24VAC 50/60Hz
Switching: Single Pole, Single Throw [SPST]
(can be field-modified to Single Pole, Double Throw [SPDT])
Power consumption: 3.5VA
CR2032 lithium battery back up for the timer-battery needs to
be replaced approximately 2–3years
Switch rating: 16 Amps at 131°F
Operating Temperature Range: 32°F–140°F
Connections (TC7D-W): (3) 16 GA pigtails (wire nuts not provided)
Connections (TC7D-E): (3) copper screw terminals
Functional description of buttons on panel:
uTIMER: Programs review & setting programs
uMANUAL ON AUTO OFF: To select “ , or ”
uCLOCK: To adjust current DAY and TIME
uDAY: To adjust day of week
uHOUR: To adjust Hour
uMIN: To adjust minute
u: Reset Timer’s setting
uLED: To indicate ON/OFF status
Press button to reset Timer before programming.
Setting Options:
u16 pairs of on-off time of day cycles can be programmed.
uEach on-off cycle can be assigned to any one day of the week, or to the following groups
of days:
Monday–Friday; Monday–Saturday; Monday–Sunday; Saturday and Sunday;
Monday–Wednesday; Thursday–Saturday; Monday/Wednesday/Friday; Tuesday/
Thursday/Saturday.
uManual Over-ride provided by “On/Auto/Off” switch.
uProgram Reset button clears all settings. First, using a small pointed object push the reset
button to clear all settings. The reset button is just above the “MIN” dark gray button.
Enclosure (TC7D-W): Requires a 4" x 4" electrical box by others.
uBox must accommodate (4) mounting screws (see drawing).
uMinimum box depth 1.5". White wall plate and mounting screws provided.
Enclosure (TC7D-E): NEMA 3R (see drawing page 4).
P
P