4.3.2 ∆T-regulation
DT O / DT1O / DT2O / DT3O:
switch-on temp. diff.
adjustment range: 1.0 ... 20.0 K
factory setting: 6.0
DT F / DT1F / DT2F / DT3F:
switch-off temp.- diff.
adjustmentrange: 0.5 ... 19.5 K
factory setting: 4.0 K
4.3.3 Maximum store temperature
S MX / S1MX / S2MX:
maximum store temp.
adjustment range: 2 ... 95 °C
factory setting: 60 °C
DT S / DT1S / DT2S / DT3S:
nominal temp. diff.
adjustment range: 1.5 ... 30.0 K
factory setting: 10.0
RIS / RIS1 / RIS2 / RIS3:
rise
adjustment range: 1 ... 20 K
factory setting: 2 K
Maximum temperature limitation
The controller is equipped with an independent tem-
perature differential regulation for which minimum and
maximum temperature limitations as well as correspon-
ding switch-on and -off temperatures can be separately
adjusted. Only possible for Arr = 2, 8, 11, 13, 16, 17, 18, 20,
24, 26 and 30 (e.g. for solid fuel boilers or heat exchange
regulation.)
If MX3O is exceeded, relay 2 is switched off until the
sensor falls below MX3F.
Reference sensor for this function:
S3 at Arr 8, 13, 20, 26 (TSTU)
S4 at Arr 2, 11, 16, 17, 18, 24, 30 (TST2, TFSB)
If the sensor temperature falls below MN3O, relay 3
is switched off until the temperature exceeds MN3F..
Reference sensor for this function:
S4 at Arr 8, 13, 20, 26 (TST2, TFSB)
S3 at Arr 2, 11, 16, 17, 18, 24, 30 (TSTU)
Both switch-on and switch-off temperature differences
DT3O and DT3F are valid for the maximum and mini-
mum temperature limitation.
MX3O / MX3F:
maximum temperature
limitation
adjustment range:
0.0 ... 95.0 °C
factory setting:
MX3O 60.0 °C
MX3F 58.0 °C
Minimum temperature limitation
MN3O / MN3F:
minimum temperature
limitation
adjustment range:
0.0 ... 90.0 °C
factory setting:
Arr = 2
MN3O 5.0 °C
MN3F 10.0 °C
Arr = 8
MN3O 60.0 °C
MN3F 65.0 °C
4.3.4 ∆T-regulation (solid fuel boiler and heat exchange)
Note
The switch-on temperature difference must
be at least 1 K higher than the switch-off
temperature difference.
Note
The controller is also equipped with a non-
adjustable emergency switch-off if the store
reaches 95 °C. The reference sensor is S2 (or
S3 for two store systems).
Once the adjusted maximum temperature is exceeded,
the solar pump is switched off and further loading of the
store is prevented to reduce scald risk or system damage.
The symbol is shown on the display.
First the controller works as a standard differential
controller. If the switch-on difference (DT O / DT1O /
DT2O) is reached, the pump is activated at full speed for
10 seconds. The speed is then reduced to the minimum
pump speed value (nMN / nMN1 / nMN2 = 30 %). If the
temperature difference reaches the adjusted set value (DT
S / DT1S / DT2S / DT3S), the pump speed increases
by one step (10%). If the difference increases by 2 K (RIS
/ RIS1 / RIS2 / RIS3), the pump speed increases by 10 %
respectively until the maximum pump speed of 100 % is
reached. The response of the controller can be adapted
via the parameter „Rise“. If the temperature difference
falls below the adjusted switch-off temperature difference
(DT F / DT1F / DT2F), the controller switches off.
DT O and DT S are locked against each other. DT S
must be at least 0,5 K higher than DT O.