Rice Lake RD-300 User manual

RD-300/RD-232
Remote Displays
Version 2.1
Installation/Operation
Manual
33210

2920i Installation Manual

Contents
1.0 Introduction.................................................................................................................................. 1
1.1 Scale Indicator Formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1.1 Standard Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1.2 Standard Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1.3 Optional Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.0 Installation ................................................................................................................................... 3
2.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Electrical Service Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2.1 All Models - AC - Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2.2 DC Models Voltages 6.2 - 18 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Indicator Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Serial Data Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4.1 RS-232 C - SW2-8 Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4.2 20 mA Active Current Loop - SW2-8 On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4.3 20 mA Passive Current Loop - SW2-8 On. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4.4 Configuring the RD-300/RD-232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.5 Powering up With the RD-300/RD-232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
3.0 Mounting Procedure for Panel Mount RD-300/232 ................................................................... 15
4.0 Appendix .................................................................................................................................... 19
4.1 RD-300 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.2 RD-232 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

2RD-300/232 Installation & Operation Manual

Introduction 1
1.0 Introduction
The RD-300 is a high performance serial remote data display. It receives digital indicator serial data signals
through either 20 mA Current Loop or RS-232C, and displays weight data on a high contrast, 1" LCD. Status
indicators are provided for LB, Kg, g, GROSS, NET, OZ, PCS, TN, ZERO, and additional specialty
annunciators for COUNT, TOTAL S1, S2, S3, S4, UNDER, OVER, and OK. The RD-300 supports 15 popular
serial scale formats plus a special “Smart Receiver” for indicators not listed. Custom interfaces to other
indicators or instruments are available. The RD-300 is direct-sunlight readable. It features black characters on a
silver reflective background, and is ideal for outdoor applications from 40°C to -25°C (104°F to -13°F). The
RD-300 can monitor up to four scales (S1, S2, S3, S4), and is available for either AC or DC power.
The following diagram illustrates the front panel of an RD-300 remote display.
The RD-232 is a high performance serial remote data display designed for indoor use. It displays weight data on
a high contrast 0.8" LED. Status indicators are provided for LB, Kg, GROSS, and NET. The RD-232 supports 15
popular serial scale formats plus a special “Smart Receiver” for indicators not listed. Custom interfaces to other
indicators or instruments are available. The RD-232 features bright red characters and is ideal for indoor display
applications from 40°C to -25°C (104°F to -13°F).
The following diagram illustrates the front panel of an RS-232 remote display.
3&.05&%*41-":
3%
3%
505"-4444
;&30 6/%&30,07&3
/&5(3044
$06/5
LH
-#
0;
5/
1$4
3&.05&%*41-":
3%
3%
-#4
,(
6/*54
(34
/&5
.0%&

2RD-300/RD-232 Installation & Operation Manual
1.1 Scale Indicator Formats
Rice Lake IQ plus 310, IQ plus 800/810 use 20 mA Current Loop only for the RD-300/RD-232.
• Rice Lake IQ 700
• Rice Lake UMC Series
• A&D Instruments 4322, 4323, 4316, 5000
• Weightronix WI-110, WI-120, WI-125, and WI-130
• Toledo Indicators with high-speed data format
• Masstron M-2500 and M-5000
• Flex-Weigh DWM-4
• Analogic AN5315, AN5316, and AN5322 (use 20 mA current loop only for the RD-300/RD-232)
• Fairbanks 90-164 series and meters with continuous scoreboard outputs
• Doran indicators Model 4100 and 4200
• Cardinal 738 and 748
• GSE 450/550 meters
• Sartorious balances with RS-232 continuous serial outputs
• Hardy 2151 indicators
• Computers, PLCs, or terminals with programmable ASCII
• Special generic Smart Receiver
1.1.1 Standard Software
The standard software for the RD-300 or RD-232 receives and displays serial data from 15 different types of
scale indicators. The receiver can accept either RS-232C or a 20 mA active or passive current loop. The standard
unit also re-transmits the data via a 20 mA active current loop. The data is transmitted either “as received” or in a
Condec continuous serial format at the incoming baud rate.
1.1.2 Standard Hardware
The standard RD-300 or RD-232 is comprised of a single circuit board housed in a JIC standard 8" X 6"
Fiberglass Reinforced Plastic (FRP) enclosure that is NEMA 4X rated.
Standard units are powered by either 117 VAC 50/60 Hz line power or DC voltages of 8.2 - 18 VDC. Voltages as
low as 6.0 VDC can be used to power the unit with the addition of one jumper.
1.1.3 Optional Har dware
Both the RD-300 and RD-232 can be ordered in a stainless steel NEMA 4X enclosure, an explosion-proof
NEMA 7CD, 9EFG, 4-enclosure panel mount, or as a board-only product for OEM applications. Consult the
factory for alternate enclosures.
An optional long-life LCD backlight is available for the RD-300. The LCD color is yellow/green and has a rated
life of 100,000 hours.

Installation 3
2.0 Installation
The following section describes the installation procedures used with the RD-300/RD-232.
2.1 Mounting
The standard NEMA 4X enclosure is a JIC standard 8" X 6" pattern. It is approximately 8" high, 9.5" wide, 5.25"
deep, and weighs 4 lb. Mounting is via four mounting holes on 8.75" horizontal by 4" vertical centers. Use 1/4"
hardware (not furnished) and mount the enclosure securely. The enclosure is hinged on the bottom side of the
box. The installation environment is not critical, but the RD-300/RD-232 should be located as far as practical
from major sources of electromagnetic interference (EMI) or radio frequency interference (RFI). Also, care must
be taken to ensure that the front panel display is easily visible.
Figure 2-1. RD-300 Mounting Footprint

4RD-300/RD-232 Installation & Operation Manual
2.2 Electrical Service Connections
2.2.1 All Models - AC - Service
You will need a source of 117 VAC ± 10% 60 Hz. 1 Phase to power the RD-300/RD-232. The standard unit has
an 8' #18-3 AWG polarized line cord. This can be plugged into a standard duplex receptacle if the
RD-300/RD-232 is used in a dry area. If the environment around the RD-300/RD-232 is wet or dirty, use a “Bell
Box” or other gasketed receptacle or hard wire the AC directly to the RD-300/RD232. The cord grip furnished is
mounted in a hole suitable for 3/8" NPT fittings.
If you hard wire power to the RD-300/RD-232, you will use the three position connector marked TB-1(shown in
Figure 2-2). Connect the L1 (Black or Hot) wire to terminal #1, the right hand terminal nearest the fuse. Strip the
wire approximately 3/16". Use a small screw driver or ball point pin to press the white latch release. While
holding the lever down, insert the wire and release the lever. Pull on the wire to assure a good connection. You
must use #14 AWG or smaller wire. Strip and insert the L2 (white or neutral) wire into TB1-3. Pull on the wire to
assure a good connection. Strip and insert the ground (green) wire into TB1-2. Pull on the wire to assure a good
connection.
Figure 2-2. AC Power on Input TB1
To prevent injury or product damage, do not turn on the power yet. Wait until you have successfully worked
through this manual and reached the section Powering Up the RD-300.
2.2.2 DC Models Voltages 6.2 - 18 VDC
The RD-300/RD-232 will also work on DC power. To use a DC power source between 10 and 18 VDC, connect
the + DC source to terminal TB2-1 and the DC- source to terminal TB2-2 as shown in Figure 2-3. The current
requirement is 30 mA without the backlight option and 160 mA with the LED backlight. If the unit has no
backlight installed, then it will work with voltages of 6.6-24 VDC without modification. If the optional backlight
is installed on the RD-300, the operating voltage range is 8.2 to 18 VDC without modification. Consult the
factory for other voltages.
Figure 2-3. DC Voltage Settings
5#
)PU-
(/%
-
$
'64&
AC Power
Input
#AUTION

Installation 5
2.3 Indicator Setup
Determine what indicator will supply the data to the RD-300/RD-232. Once determined, there are certain setup
parameters which you will need to know. Common indicators are discussed below.
• Rice Lake IQ series (600-700), IQ plus series (810 and 310*) - All of the IQ and IQ plus series indicators
work with the setup for continuous output and have the Consolidated Controls output. The IQ plus 810
set in the stream mode has the same format as the Condec indicators. The IQ plus 310 can match the
format of several indicators: CARDINAL 738, WI 120, AN 5316, the Toledo Hi-Speed output, and
Consolidated Controls (Condec). Match the baud rate you wish to use and program this into the
RD-300/RD-232. Baud rates from 300 to 19,200 are supported. If the meter you are using has a
selectable bit pattern, the preferred is 1 start bit, 8 data bits, and no parity. The RD-300/RD-232 will,
however, receive 7 data bit patterns of any parity as well.
• Condec, Rice Lake IQ plus 310* - All models in the Consolidated Controls line should be set up for
continuous output. Any baud rate from 300 to 38,400 is supported. Condec meters will work with either
the Universal or Condec setting.
• AND Instruments 4322,4321,4316, - These indicators can be set up for either “current loop” (passive) or
“RS232”, using the “stream mode” at 2400 baud, Format 1. The RS-232 can be used with either the
Universal receiver or the AND setting. The passive current loop input requires the current supply from
the current loop output.
• AND Instruments Model 5000 - This indicator can supply either RS-232 or 20 mA active current loop.
Configure port two to transmit continuously in the Condec format. Use the Condec setting for this meter.
• Weigh-Tronix 110 and 120 meters - with continuous data outputs - These indicators can be set up for
either “current loop” or “RS232”, in the continuous mode. Baud rates from 300 - 38,400 are supported.
Both new and old data formats are supported.
Note: a special EPROM may be required from Weigh-tronix for the required continuous serial output. Use the Universal mode or
the Weigh-tronix setting with these indicators. Switch 7 can be used to control unwanted time out if very slow update rates are
chosen.
• Weigh-Tronix Models WI-125 - Connect the RS-232 signals (TB2-1 is ground and TB2-2 is transmit
data) to the RD-300/RD-232. Set the Serial String to Auto = ON and Broad = ON. Layout - 1=Display,
2=ASCII -13-10-3-End, End. Set the baud rate to match the baud rate selected in the meter.
• Weigh-Tronix Models WI-130 - There are two ports, one and two. Port one uses either RS-232 or
RS-485. Port two uses either 20 mA current loop or RS-232. Select one of the two ports. Set
handshaking to off. You must program a BASIC program to get the meter to send the data continuously.
Use the following steps to set up a basic ticket string.
1. Program the string as: <G OR N><SP><7 WEIGHT BYTES><SP><LB OR KG><SP><CR><LF>
2. Use the sample program given below:
Under system setup-
Set Timer (2,0.5); set timer 2 to 0.5 seconds
SUB SYSTEM Timer2
If Actvalue=0 then
GN$="G"
SVAL$=GROSS
else
GN$="N"
SVAL$=NET
end if
IF UNIT=0 then
LK$="LB"
else

6RD-300/RD-232 Installation & Operation Manual
LK$="KG"
end if
DO L
IFKEN(SVAL$)<7 then
SVAL$= " " +SVAL$
else
exit DO
end if
LOOP
DISPSTR$ =GN$ + CHR$(32) + SVAL$ + CHR$(32) + LK$ + CHR$(32) + CHR$(13) + CHR$(10)
PRINT #1 DISPSTR$;PRINT TO PORT #1 (#2 FOR PORT 2)
• Toledo Indicators (with high speed data format) - Most Toledo indicators support this format. Older
indicators can only be set up as “current loop” (active) at 4800 baud. RS-232 and 20 mA current loops
are supported. Baud rates of 300 - 19,200 may be used. Use the Toledo receiver for these meters.
• Flex-Weigh DWM-4 - This indicator can be set up for either “current loop” (active or passive) or
“RS232”, using “MODE 1 - Status, Weight, Tare Data”. Baud rates of 300 - 19,200 may be used. Set the
data preamble to “FF, FF, FF” and the postamble to “FF, FF, FF”. The LB/KG units display does not
function with this meter. Use the Flex-Weigh receiver for this meter.
• Analogic AN5315, AN5316, AN5322, Rice Lake IQ plus 310* - These indicators can be set up for
“current loop” in the continuous mode. Do not use “RS-232.” Baud rates of 300 - 19,200 can be used.
This meter supports the grams and tons display mode. Use the Analogic receiver mode for these meters.
• Masstron M2500, M5000, Toledo meters with this output (814X) - These indicators are set up for 4800
baud via the continuous remote display output normally used with Masstron accessories. This meter
supports the grams and tons mode. Use the Masstron receiver for these meters.
• Fairbanks 90-164 - This indicator is set up for 1200 baud “current loop” via Port “C”. Enable the
Lampbank output in the continuous mode. Other Fairbanks meters such as the 90-167 will work with the
RD-300/RD-232 if they have continuous data outputs. Use the Fairbanks receiver for these meters.
• Streeter Amet 9000 - This indicator is set up for “current loop”. The baud rate can be 1200, 2400, or
4800. Do not use 9600 baud! Program the output for Gross/Net Weight as 01/10/00 or in the print
program for 03/10/00. Use the Universal receiver for this meter.
• Cardinal 738 and 748, Rice Lake IQ plus 310* - These indicators can be set up for either the “current
loop” or “RS232”, using the “computer” setting (S3=10001010). The baud rate can be 1200, 2400, 4800,
or 9600. This meter supports the tons display annunciator. Use the Cardinal interface for these meters.
• Doran Indicators and Scales - Models 4100 and 4200 are supported. Use either port one or two in either
RS-232 or 20 mA current loop mode. Set the selected output port for continuous data and print format
#11.
Note: The RD-300/RD-232 does not support the lbs and ounces mode!
• GSE 450/550 - Models 450 and 550 are supported. A sample program and port configuration is shown
below:
RS-232
Printer Port - RS-232 or current loop
COM port - RS-232 with no handshake
Set number of characters transmitted per number to 8 <P208.08>

Installation 7
Example:
P210.02 - Sets custom transmit 1 to continuous
P211.01 - Sets custom transmit 1 to send through the printer port
Send a custom transmit. Set for continuous transmission mode and the port selected.
Set up custom transmit 1:
1000ASCII - 02
1001DISPLAY DATA - 98
1002STATUS DATA - 97
1003ASCII - 03
The serial data is as follows:
<02><8 WEIGHT BYTES><SP><LB OR KG><SP><GROSS OR NET SP SP><STAT><SP><M OR O OR SP><03>
• Sartorius Balances with RS-232 data output - RS-232 is supported. Set for space parity, 1 stop bit, auto
output print without stability, no ID code, and software handshake. The output data must use the 16
character format.
• Hardy 2151 - Configure the standard serial port for RS-232. You must hardware jumper the RTS to the
CTS pins even if the software handshake is enabled. Select the baud rate and eight data bits with no
parity. To send the gross weight continuously, program G - - - - - into the output parameter value. To
send the net weight continuously, program - N - - - - into the output parameter value.
• Universal Data Receiver - This receiver can receive serial data in a wide variety of intuitive formats. It
can be used in either RS-232 or current loop. Use when all else fails. This receiver keys on carriage
returns (CR), end of text (ETX), or end of transmission (EOT) characters in the data string. The receiver
looks for G, g, N, n, K, k, L, l, (-) characters and reconstructs the data string from this information.
When the RD-300/RD-232 senses that the universal receiver has been selected, use switch SW2-6 to tell
the unit if the serial string contains a kilogram sign as a K or a KG. The universal receiver always looks
at the data string from back to front. This keeps the receiver from confusing the “g” in kg with a g for
gross mode. If the string uses a single character for kilograms, SW2-6 should be OFF.
• Other Indicators... Many indicators have programmable serial outputs and can be programmed to work
with the RD-300/RD-232, if , and only if, the output formatting exactly matches what the display has
been programmed to accept. If a computer or terminal is going to be used with an RD-300/RD-232, the
universal format is probably the easiest to use if the data is sent continuously. Several other meters have
been interfaced for use with the RD-300/RD-232. Consult the factory for special application needs.
• Choices- Some meters have multiple outputs. Some can have two or more RS-232 outputs or current
loop outputs which can be active or passive. The preferred interface is an active current loop from the
meter. RS-232 is always the least desirable because the ground planes of the two devices must be tied
together. The output data must be continuous. Demand ports are mostly unusable unless the meter uses
the universal, Condec, Fairbanks, or Cardinal formats. If a demand format must be used or the display
must show the last data transmitted, SW2-4 can be used to disable display timeout. Turn SW2-4 ON to
disable display timeout.
*IQ plus 310 has multiple data formats and can be used with multiple receivers

8RD-300/RD-232 Installation & Operation Manual
2.4 Serial Data Inputs
The RD-300/RD-232 can accept serial ASCII data sent in RS-232C, or 20 mA active or passive current loop
formats. To select an RS-232 input signal, Set SW2-8 OFF. To use any current loop signal, set SW2-8 ON. See
Figure 2-4. These formats determine the electrical way that data is transmitted. This has nothing to do with what
data is sent.
Figure 2-4. Switch Setting SW-2
The RD-300/RD-232 can read the data transmission strings sent by 15 of the more popular scale indicator
families. It cannot read data from meters not included in this list unless you use universal mode or the formatting
exactly matches one on the list (or you have a custom program). Set up the RD-300 on the bench with the meter
you intend to use before taking it to the installation site.
Some indicators are built with their RS-232 serial port signal ground combined with the general chassis
ground. When the RD-300 or RD-232 Remote Displays are connected to such an indicator sending RS-232, half of the power
supply is being shorted to chassis ground via the offending RS-232 signal ground connection. The result is extreme heat in the
transformer and premature failure.
With Analogic indicators and other products combining RS-232 signal ground and chassis ground, do not use RS-232 output.
Set both the indicator output and the remote display input to 20 mA current loop instead.
Check your indicator’s electrical schematics—or feel for extreme heat at the RD-300/RD-232 transformer—to determine if your
indicator has a combined RS-232 signal and chassis ground. If so, use 20 mA current loop.
2.4.1 RS-232 C - SW2-8 Off
Data is transmitted as a voltage and alternates between
+10 VDC and -11 VDC. Hybrid “RS-232” signals
can swing between other voltage ranges as long as the
positive swing is greater than 4 VDC and the negative
is less than -1VDC. RS-232 is ground referenced and
therefore, connects the ground planes of the sending
and receiving instruments. RS-232 should never be
run more than 50'. It may work, but it may not work
well all the time. Long RS-232 data cables can act as
a conduit for lightning or other electrical noise to the
instrument. If you need longer cable runs, use a 20
mA current loop. If this is not available on your
indicator, consider an optically isolated protocol
convertor to change the RS-232 to 20 mA loop and
optically isolate the ground planes of the two
instruments.
Connect RS-232 wiring as shown in Figure 2-5
(RS-232, GND). Strip the wires approximately 3/16".
Press on the white lever to open the connector. Insert
the wire and release the lever. Test the tightness by
gently pulling on the wires. Tighten the strain relief
fitting around the RS-232 cable with a wrench or
pliers.
Figure 2-5. RS-232 Wiring Assignment
0''
37
#AUTION
#,
23
$#
4"
$#
'.$
#,
#,
#,
/54
).

Installation 9
2.4.2 20 mA Active Current Loop - SW2-8 On
In this mode data is transmitted as a current and is
passed through an optical isolator. This current
causes an LED to emit light onto a phototransistor,
which converts this light into a TTL signal. Current
transmission can be made over long distances and is
quite immune to transient surges or RFI/EMI noise.
The distance a current loop can transmit is limited by
the voltage source available to the current loop and the
speed of transmission which data is sent. The
maximum baud rate is set by the quality of the
indicator transmitter. The RD-300/RD-232 can
receive data at baud rates of up to 38,400.
An active current loop means that the instrument
which sends the data also supplies the voltage to
power the loop. This voltage can be as small as 3.5
VDC to as much as 24 VDC. When the loop goes
through an optocoupler, a “drop” occurs. This drop is
about 2 VDC. A current loop can power as many
drops as there is voltage to power the loop. For
example, if a current loop is powered by 5 VDC, it can
normally drive two “drops”. If the same loop were
powered by 24 VDC, it could power about 11 remote
displays or other devices. Determine that your
indicator has an active current loop and connect it as
shown in figure 6. Strip the incoming wires
approximately 3/16". Press on the white lever to open
the connector. Insert the wire and release the lever.
Test the tightness by gently pulling on the wires.
Tighten the strain relief fitting around the serial data
cable with a wrench or pliers.
The 20 mA receiver in the RD-300/RD-232 is an
HP-4200 high speed current loop receiver. The photo
coupler and requires current swings of less than 4 mA
as a mark and greater than 12 mA for a space. The
output of both the RS-232 and the current loop is sent
through an LED on the circuit board. See Figure 2-6.
This LED will be OFF when nothing is connected to
the board, and will flash when serial data is being
received. Please note that when the LED flashes, it
means that something is being received that looks like
a serial signal. It does not guarantee that the signal is
correct.
Figure 2-6. LED Location
2.4.3 20 mA Passive Current Loop - SW2-8 On
A passive current loops means that the instrument
which sends the data does not supply the voltage
source to power the loop. The voltage must come
from the RD-300/RD-232. To use a passive current
loop, wire the unit in the following way.
1. Jumper TB2-3 to TB2-6 (Gnd to CL- IN).
2. Connect the CL+ from the meter to the CL+
Output (TB2-7) and the CL- Output to TB2-5
(CL+ IN).
3. Strip the incoming wires approximately
3/16".
4. Press on the white lever to open the
connector.
5. Insert the wire and release the lever.
6. Test the tightness by gently pulling on the
wires.
7. Tighten the strain relief fitting around the
serial data cable with a wrench or pliers.
Note: Using this configuration changes the current loop
output to a passive transmitter!

10 RD-300/RD-232 Installation & Operation Manual
2.4.4 Configuring the RD-300/RD-232
The RD-300/RD-232 must be properly configured. To do this, you must know:
• Which indicator?
• What Baud Rate?
• How does the display handle a loss of signal?
• Are you going to use the universal mode?
• Do you want to retransmit data in Condec format or in the format it was received?
Once this information is known, it is entered through SW1 and SW2, DIP switches on the CPU board. (See
Figure 2-7, and table below).
Figure 2-7. DIP Switch Settings
Meter Number Receiver SW1-1 SW1-2 SW1-3 SW1-4
0 Universal On On On On
1 IQ plus, Condec On On On Off
2Toledo OnOnOffOn
3 Flex-Weigh On On Off Off
4 Analogic On Off On On
5 Fairbanks On Off On Off
6Cardinal On Off Off On
7 Masstron On Off Off Off
8AND OffOnOnOn
9 Weigh-tronix Off On On Off
10 Spare Off On Off On
11 Doran Off On Off Off
12 Sartorious Off Off On On
13 GSE Off Off On Off
14 Hardy Off Off Off On
15 Spare Off Off Off Off
Table 2-1. DIP Switch Settings

Installation 11
Enter the baud rate from the table listed below.
Select the interface type, RS-232 or 20 mA with SW2-8.
Note:
IF YOU ARE USING TOLEDO, MASSTRON, FLEX-WEIGH, OR ANALOGIC (or IQ plus 310 IN ANALOGIC MODE) METER
SETTINGS, USE THE FOLLOWING SWITCH DATA
Toledo, Flex-Weigh, Analogic, and Masstron meters all transmit data continuously. They also have special
information available in their formatting which allow the RD-300/RD-232 to perform additonal useful
functions. With these meters, the timeout function is always enabled. SW2-4,5,6 and 7 have the following
meanings:
The RD-300/RD-232 will display the data selected by SW2-6 and 7 regardless what is showing on the scale
indicator.
IF YOU ARE USING ANY OTHER METER SETTING, USE THE FOLLOWING SWITCH DATA ON PAGE 12.
Baud Rate SW2-1 SW2-2 SW2-3
38,400 On On On
19,200 Off On On
9,600 On Off On
4800 Off Off On
2400 On On Off
1200 Off On Off
600 On Off Off
300 Off Off Off
Table 2-2. Baud Rate Settings
Input Type SW2-8
20 mA CL On
RS-232 Off
Table 2-3. Interface Type
Retransmit Data Format SW2-4
Condec data format On
As received Off
Table 2-4. SW2-4 Data Format Settings
Display on Time Out SW2-5
“No sig” On
Last data received Off
Table 2-5. SW2-5 Time Out Settings
Displayed Weight Mode SW2-6 SW2-7
Current displayed weight On On
Gross weight only Off On
Net weight only On Off
Tare weight only Off Off
Table 2-6. SW2-6/7 Displayed Weight Settings

12 RD-300/RD-232 Installation & Operation Manual
Other meters may transmit data intermittently, slowly, or in a demand mode where the data is only sent once.
Enabling the time out function causes the RD-300/RD-232 to do the following. If new data hasn't been received
for approximately two seconds, then the display shows what is selected by SW2-5, either the last valid weight or
all dashes. If no valid data is received after ten seconds, the RD-300/RD-232 initiates a power on reset, clear all
data, read the switches, and waits for new data. For these meters SW2-4,5,6 and 7 have the following meanings:
Time Out Enable SW2-7
Time out counter disabled (cn dis) Off
Time out counter enabled (cn ena) On
Table 2-7. SW2-7 Time Out Enabled Setting
Display on Time Out SW2-5
“No sig” On
Last data received Off
Table 2-8. SW2-5 Time Out Settings
Universal KG Character Type SW2-6
A single character is sent, K, k Off
KG, Kg, or kg is sent On
Table 2-9. SW2-6 Character Type Settings
Retransmit Data Format SW2-4
Condec data format (rd con) On
As received (rd rec) Off
Table 2-10. SW2-4 Data Format Settings

Installation 13
2.5 Powering up With the RD-300/RD-232
Make sure all wiring is per the manual and is properly terminated.
APPLY POWER-
The RD-300/RD-232 enters the power on clear mode. All status switches are read at this time and the unit is
configured for baud rate, indicator type, and input signal type. The RD-300/RD-232 display goes through a
power up sequence which provides valuable information about the operating condition and setup.
LAMP TEST-
The first display during power on clear is a lamp test. This test lights all display segments and decimal points.
If the display is too bright, adjust the multi-turn pots located on the RD-232 CPU board (see below). The RD-232
Figure 2-8. RD-232 Trim Adjusting Pot Location
remote display has two, 20K - 10 turn pots to adjust the intensity of the LED displays. The pots are located on the
backside or component side of the display board located to the top outside of the circuit board. The pot to the
right side adjusts the intensity of the three displays on the right side of the display board. The pot on the left side
adjusts the intensity of the three displays on the left side of the display board.
Note: If the display intensity is adjusted to high, it will cause the micro’s voltage and current to drop causing the remote to
continually cycle it’s power-up sequence. To correct this, turn the pots counter clockwise about half the adjustment or five turns.
Repeat this adjustment on both pots to balance the display intensity.
PRODUCT SOFTWARE ID-
The unit should show rd 300.
SOFTWARE REVISION NUMBER-
Next the software revision number, rev 2.1 is displayed.
CURRENT BAUD RATE SETTING-
The RD-300/RD-232 next shows the current baud rate setting it has read from switch SW1. The display will
show baud 3, for 300 baud, baud 6, for 600 baud, baud12, for 1200 baud, baud24 , for 2400 baud, baud48, for 4800
baud, or baud96, for 9600 baud, baud19, for 19,200 baud, or baud38, for 38,400 baud.
INDICATOR TYPE-
The RD-300/RD-232 will show the indicator type you have chosen through SW1. This is displayed as Ind 0
through Ind 15.
INDICATOR INTERFACE TYPE -
The RD-300/RD-232 shows either, C loop or rs 232.
DISPLAY ON LOSS OF SIGNAL -
The RD-300/RD-232 shows either, no sig for no signal, or las da for the last valid data received.
,%$
$2)6%2 $2)6%2
$)30,!9-/$5,%
,%$"!#+,)'(4
-)#2/02/#%33/2
0''
()'(6/,4!'%
37
4"
,
,
'.$
42)-!$*
42)-!$*
0''
37
#,
23
$#
4"
$#
'.$
#,
#,
#,
/54
).
Trim adjust pots
by using a small
screwdriver to
turn.

14 RD-300/RD-232 Installation & Operation Manual
RETRANSMIT DATA TYPE -
The RD-300/RD-232 next shows the data format of the retransmission. rE-rec means the data is transmitted as it
was received. rE-Con means that the data will be converted and retransmitted in Consolidated Controls
continuous data format.
TIME OUT ENABLE -
The RD-300/RD-232 will show, cn ena if the time out counter is enabled, and cn dis if the time out counter is
disabled.
RECEIVING THE DATA FOR THE FIRST TIME-
After the power up sequence, the RD-300/RD-232 synchronizes with the incoming serial data line and looks for
data to receive. If no readable data is received within a few seconds, the display shows nosig.
When communication is established, the current weight value is displayed. Decimal points are inserted into the
display as indicated by the meter. If the data format from the meter makes LB, kg, Gross or Net status available,
the RD-300/RD-232 displays this information with the appropriate status segments. Some formats do not make
this data available. In this case, the segments are not illuminated.
If you have trouble, remember, you must have continuous data coming from the meter. The most common
problems are non-standard indicator serial outputs, mis-wiring, and mis-programming both in the meter and in
the RD-300/RD-232 setup. Check the LED and see if it is flashing. If it is, then something is being received.
NOTE: This doesn't mean that the format is correct, only that data is appearing at the receiver.
When the display is operating properly, the job is only partially done. Any good installation isn’t finished until
the enclosure mounting is checked and tightened, all conduit and cable entries are wrench tight, and the enclosure
screws have been tightened with a socket or screwdriver.
If the RD-300/RD-232 is located in a wet, damp, or cold environment, it is suggested to use a silica gel desiccant
or better yet, an antioxidant “snowball” made by Hoffman Enclosure Company. These products in the enclosure
will greatly increase product reliability and performance. Change any desiccant at least two times per year.

Mounting Procedure for Panel Mount RD-300/232 15
3.0 Mounting Procedure for Panel Mount RD-300/232
Use the following procedure if panel mounting the RD-300/232. A template for measuring is shown on page 17.
1. Choose a desired location for mounting the RD-300/232. Make sure there are no AC wires or other
obstructions behind the area to be cut out.
2. Use the enclosed template to mark the panel holes. Note that all holes are measured center to center.
3. Transfer the holes onto the desired panel. Start from one side and make all other measurements starting
from that side. Using this method reduces errors. Try to mark the center of the holes. Drill the four
OUTER holes with a #.228 or 15/64" drill bit.
4. Drill the INNER four holes with a #.156 or 5/32" drill bit.
5. When the holes have been drilled and checked for accuracy, cut the hole for the display as shown on the
template. Make the edges as smooth as possible because the front plate must lay flush on top of it.
6. Detach the circuit board from the front plate and remove the nut and lockwashers from the mounting
screws. Place the front plate on the panel from the front and push the mounting screws and studs through
the holes as shown in Figure 3-1.
Figure 3-1. Mounting Procedure for Panel Mount
Have someone hold it or secure it with removable tape while putting the lockwashers and nuts back on
the mounting screws and tighten.
Note: you will find that the mounting studs 8-32 x 3/4", have nuts and lockwashers included. If you lose
one, they can be replaced at most local hardware stores.
7. Check from the front to make sure the edges of the cutout do not show through the window and that the
front plate is lying flat against your panel. Remount the circuit board with the original screw and plastic
washers.
8. Proceed with wiring instructions per manual instructions.
*OOFS4UBOEPGGT"UUBDI
$JSDVJU#PBSEUP'BDFQMBUF
$JSDVJU#PBSE
0VUFS5ISFBEFE4UVE)PMET
'BDFQMBUFPOUP$VTUPNFST1BOFM
$VTUPNFST
1BOFM
1BOFM.PVOU
'BDFQMBUF

16 RD-300/RD-232 Installation & Operation Manual
This manual suits for next models
1
Table of contents
Other Rice Lake Monitor manuals

Rice Lake
Rice Lake LaserLT-60 User manual

Rice Lake
Rice Lake LaserLight3 User manual

Rice Lake
Rice Lake LaserLT-60 User manual

Rice Lake
Rice Lake SURVIVOR IQ L Series User manual

Rice Lake
Rice Lake 1280 Enterprise Series Installation manual

Rice Lake
Rice Lake SURVIVOR IQ F Series User manual

Rice Lake
Rice Lake IQ plus 710 User manual

Rice Lake
Rice Lake MSI-8000 User manual

Rice Lake
Rice Lake EL232 XPCD User manual

Rice Lake
Rice Lake LaserLight3 User manual