Risco GT 600 Programming manual

The
GT 600 / 601
Control Panel
Quick Start Instructions
Download the complete GT 600 / 601 Installation Manual at
www.riscogroup.co.uk
RISCO Group UK Ltd
Tel: 0161 655 5500 Fax: 0161 655 5501
Int Tel: +44 161 655 5500 Fax: +44 161 655 5501
Internet: www.riscogroup.co.uk
e-mail: sales@riscogroup.co.uk
Technical Support Tel: 0161 655 5600
Technical Support Fax: 0161 655 5610
(Mon - Fri 08:30-1730)
This Quick Start Guide gives brief installation information for the GT 600 / 601
Control Panels RISCO Group UK Ltd reserve the right to amend the software and features
without prior notice
PR600601QS_3_ Rev1.2
5IN1785

IMPOR
IMPORT
TANT!
ANT!
nput: 600 AC230V +/-10% ~50Hz 125mA Max. 35W Max
nput: 601 AC230V +/-10% ~50Hz 315mA Max. 80W Max
Nominal Temp Range: 0 - 50°C
GT 601
Metal Versions
For Indoor Use Only
GT 600
Plastic Versions
For Indoor Use Only
This equipment is intended only for use as a Security Alarm Control Panel. Adequate
ventilation away from heat and humidity must be provided. The unit must be fixed
securely to a non-flammable surface using suitable fixings.
All mains wiring must conform to the relevant current IEEE wiring regulations (or
appropriate international regulatory standards). See Mains Supply Connection section
within this manual for more detailed instructions.
All wiring must be protected from sharp or jagged edges.
All Low voltage (alarm) wiring must be to the appropriate international regulatory
standards and comply to good wiring practice and should be routed away from the
mains cables. Replacement fuses should be of the same type and rating conforming to
IEC 127.
The
GT 600 / 601
Control Panels are fitted with resettable fuses. The areas protected
are Battery, Aux, Bell, Keypad and Comms. In the event of a fuse tripping or an input/
output not working, remove the source of the load and check wiring for shorts. Check
any added devices for full functionality before any reconnection.
The maximum current draw from the unit for all output combinations must not exceed
the rated output. Please see note:
*Power Supply Rating (Page 5)
.
The unit is intended for use with a suitable re-chargeable lead acid battery
permanently connected to the appropriate terminals.
All documentation and manuals must be thoroughly read by suitably qualified
installation personnel prior to installation.
The unit has no user serviceable parts inside. Internal access should only be by
suitably qualified personnel.
GT 601
Metal Versions
The unit must be Earthed.It is the responsibility of the installation engineer to
ensure that the earth connection to the unit lid is good on completion of the installation
or after service.
GT 600
Plastic Versions
Provision is provided for an earth connection within the mains input connector block,
this connection is for protection of the wiring only and is not functional for the unit.
Page 1

Introduction
The
GT 600 / 601
Control Panels are microprocessor based units that have been
designed to be suitable for all types of domestic and commercial installations. All
zones are fully programmable by the engineer.
On power up / reset, the Control Panel can be set to the old BS, EN2 (Grade 2) or
EN3 (Grade 3) operating standards. Selection for PD6662 2004 /PD6662 2010 stan-
dard can also be set at this point. (See page 14 for further details).
Note: Due to changes within the standards, the
GT600
is only BS or EN2
(GRADE 2) compliant.
Upon completion of the installation the engineer may, if required, re-program several
factory set options so as to tailor the Control Panel to suit the requirements of the
system.
It should be noted that if the engineer code has been locked into the system it
may only be changed by using the code again (default to factory settings will
have no effect).
We recommend that the Installation manual and the user manual are read and fully
understood before any installation of the system is carried out. This Quick Start Guide
is intended for use by engineers who have experience in installing GT security equip-
ment. Greater detail is given in the full Installation Manual available from our website.
Planning the Control Panel Location
Consideration in locating the fixing position of the Control Panel should be given to:
Access for the routing of cables for the system from detection devices,
sounders (internal and external), remote keypads, mains, etc.
The position of the underside retaining screw.
The fixing of a 3 amp unswitched fused spur.
When fitting the RKP(s) consideration should be given to:
Operation of the keypad.
Readability of the display.
The Panel should be fixed to the wall using appropriate wall plugs and No.8 screws at
least 30mm long. Do not tighten the screws at this stage, wait until all your wiring is in
place.
Mains Supply Connection
A 230V a.c supply should be taken directly from the consumer unit. In order to
comply with the relevant current wiring regulations this should be via a 3 Amp fused
spur with disconnection facility.
Page 2

Gardtec 600 PCB Fitting Instructions
Fitting the 600 PCB (plastic case)
Make sure all mains power is disconnected before fitting the PCB.
After fitting the case to the wall, and feeding the cables through the relevant
entries, mount the 600 PCB as shown in the figure 1:-
1. Make sure that the inner retaining clips are in place and the PCB sits squarely
on the support pillars. (See figure 1). Make sure the PCB is secure.
Note the orientation of the PCB, the terminal strip is facing the mains transformer.
2. Connect the two orange transformer wires to the two terminals marked A.C. on
the PCB. (See figure 1).
3. Connect the two battery wires to the battery terminal on the PCB. Note the
polarity. Black -, Red +. (See figure 1).
Fitting the 601 PCB (metal case)
When fitting the 601 PCB to the metal case follow the B26 Enclosure Assembly
Guide then follow the additional steps outlined below.
1. Leave the tamper spring in place.
2. Connect the Tamper Cable to the right angled pin header next to the tamper
switch. (JP2 on the PCB). (See figure1). Note the orientation, the
connector will only fit one way round.
Page 3

Fig1. 600 PCB (plastic case).
Page 4

Output Terminal Descriptions
Speaker Terminals
This pair of terminals provide connection for:-
System Speaker(s)
Optional 16/32 Ohm Panel Speaker
A speaker is supplied in each keypad. If any additional speakers are fitted they should
present a minimum impedance of 16 Ohm.
PGM 1, 2 & 3 Terminals
The PGM1 & 2 terminals are an open collector output held at 12V through an integral
1k resistor. Max current sink into PGM 1 & 2 terminals is 50mA. The terminals are
programmable for various uses if required.
Note: PGM3 terminal is the strobe- terminal and is only available as a
programmable option if the Strobe terminal is not used for the
External Sounder e.g. when NovActive sounders are used.
*
Power Supply Rating
Gardtec 601 metal version maximum output current - 2A
Gardtec 600 plastic version maximum output current - 1A
It should be noted that the 600 plastic control panel has 1Amp available for the
full system. However, for the purpose of compliance to EN and PD6662 stan-
dard, the capacities of the power supply have to be specified differently. For a
Grade 2 system you have 72 hours to charge the battery. With the 600 plastic
control panel, 90mA is available for battery charging. This defines a theoretical
maximum standby battery capacity of 8.0Ah and a maximum of 666mA avail-
able for system power. If a smaller capacity battery is used then the rating has
to be reduced accordingly. For example: If a 7Ah battery is used it will recharge
in 72 Hrs and will theoretically provide 910mA (1000-90mA) for the system.
However, the supply rating for that system under PD6662 is still 7.0Ah/12hrs =
583mA. Sounders, detectors and other auxiliary items should be included when
calculating current drawn by the system. Any damage caused through
overloading the control panel supply will not be covered by the warranty. We
recommend that additional power supplies are used to supply detectors on
long cable runs.
AUX 12V Terminals
This pair of terminals supply the + and - supply for the detectors.
Strobe Terminals
This pair of terminals are the output for the Strobe. The negative terminal is switched
during an alarm period.
Bell Terminals
This pair of terminals are the output for the Bell or external sounder. The negative
terminal is switched during an alarm period.
Keypads
The + and - terminals supply power to the keypads.
Page 5

4 Wire Remote Keypads
Up to seven remote keypads may be fitted to the
GT 600 / 601
control panels.
A four core connection will be required between the control panel and remote key-
pad(s), keypads may be in a 'daisy chain' or ‘star’ format.
For installing the keypad please refer to the instructions supplied with the 4 wire key-
pad.
6 Wire Keypads
6 Wire Keypads can be used with the GT 600 / 601 Control Panel. Please refer to the
installation instructions supplied with the 6 wire keypads. Please note that only one
type of keypad can be used. 4 wire and 6 wire keypads cannot be mixed.
Fig2. RKP Connections
Page 6

PGM1
SPKR
+
-
AUX 12V
+
-
+
-
+
-
STROBE
BELL
BELL HOLD-
SAB TAMP
Supply for Detectors
RKPs Etc
Strobe
Light
Sounder/SAB Unit
Speaker
Programmable terminal for
latching detectors etc.
12V Tri g
0V
Tamp
Ret
Fig4. Control Panel Output Connections
Page 7
16 Ohm
Min
Digi Modem - The
GT 600 / 601
control panels feature an onboard Digi modem.
The Digi provides all the features of an eight channel communicator whilst the Modem
provides facilities for Gardtec Remote Upload/Download software package.
Vo-Comm - (If fitted) Is a method of transmitting signals to a standard land-line
or mobile telephone, giving information regarding the status of your security system.
If On is selected, the Vo-Comm menu will now appear in the USER mode. Please
refer to
GT 600 / 601
User Guide for further programming information.
Fig3. Telephone Connections
A5
IN
B2
IN
C3 B2 A5
Terminal 5
(on existing BT socket)
OR
Terminal A
(on BT Terminal Block)
Terminal 2
(on existing BT socket)
OR
Terminal B
(on BT Terminal Block)
Standard
Telephone
Connection
Serial
Telephone
Connection
(depending on model)
Terminal positions may differ.
A5
IN
B2
IN
C3 B2 A5
Terminal 5
(on existing BT Master socket)
Terminal 2
(on existing BT Master socket)
Term nal 3
(on existing BT Master socket)
Term nal 5
(on other extension sockets)
Term nal 2
(on other extension sockets)
Term nal 3
(on other extension sockets)

Fig6. Control Panel Input (Zone) Connections
Fig5. Typical Novagard 2G/4G Connections
Page 8
+12V
0V
S-
ST-
R TMP
F TMP
BELL+
BELL-
SAB TMP
BELLHOLD-
STROBE-
GT 600 / 601
Control Panel
AZ1
+ -
AZ2
+ -
AZ3
+ -
AZ4
+ -
AZ5
+ -
AZ6
+ -
AZ7
+ -
AZ8
+ -
TZ
+ -
N/O Devices (PA etc)
connect across Tamper & Zone
N/C Devices
multiple devices are in series
N/C Devices
N/C Devices
N/C Devices
N/C Devices
N/C Devices
N/C Devices
AZ1
+ -
AZ2
+ -
AZ3
+ -
AZ4
+ -
AZ5
+ -
AZ6
+ -
AZ7
+ -
AZ8
+ -
N/C Devices
N/C Devices
N/C Devices
N/C Devices
N/C Devices
N/C Devices
6k8
6k8
6k86k8
6k86k8
6k8
6k8
N/C Devices
N/C Devices
6k8
6k8
4k7
4k7
4k7
4k7
4k7
4k7
4k7
4k7
TZ
+ -
Standard (2 Wire) Zone Wiring
End of Line Zone Wiring.
Novagard 2G/4G
(Strobe terminals omitted)
Please see Page 25 for further
wiring modes where Anti-Mask
detectors are used.
Multiple units can only be
used with BS Standard. If
using EN2 / 3, one unit per
zone.

Page 9
Zone/Output/ID Expander Card Connections
Upto 4 zone expander cards (or 1 ID Expander card) can be fitted to the 600. Up to
16 zone expander cards (or 2 ID Expander card) can be fitted to the 601. These are
all fitted to a common expander bus via a serial connection lead (part No. 1CB 6046).
This lead is fitted to the plug on the front of the control panel PCB and the cards
wired as shown below. Refer to page 11 for ID compatibility and output cards.
Fig7. Expander Card Connections
To Other Expanders
Notes:
Remove power from panel before
connecting Expander Cards.
Zone Expansion Types (ZEX or ID)
are programmed via option 72
Zone Expander Cards are pro-
grammed via options 75 & 76.
Ensure ident jumper on Zone
Expander is in position 1 to 4 as
required.
Zones numbers on Expander No.1
start at 21(e.g AZ1 on expander 1 =
zone 21).
Zones numbers on Expander No.2
start at 31(e.g AZ1 on expander 2 =
zone 31).
Zones numbers on Expander No.3
start at 41(e.g AZ1 on expander 3 =
zone 41).
Zones numbers on Expander No.4
start at 51(e.g AZ1 on expander 4 =
zone 51).
If ID zones are used the first zone
on the ID card is Zone 21
For Output Expanders ensure ident
jumper is in required position (1 - 4).
Output Expanders are programmed
via option 83 and may be pro-
grammed only via a LCD RKP.
600 / 601 PCB
For ZEX 9, jumper should be on Address 1
and ZEX 16, jumper should be on Address 8

Page 10
Zone Expander (ZEX) Wiring Modes
Three wiring modes may be programmed for each ZEX these are.
4 Wire Gives 4 zones AZE 1 - AZE 4 and four tampers TZE 1 - TZE 4
2 Wire Gives 8 zones AZE1 - AZE 4 then TZE 1 - TZE 4
End Of Line Gives 8 End Of Line zones AZE 1 - AZE 4 then TZE 1 - TZE 4
All AZE zones are positive loops and all TZE zones are negative loops. when using 2
wire mode please reserve one positive and one negative zone for your tampers.
Tampers should be opposite polarity to the zone being protected.
Before powering up place jumper ZEX on position 1 to 4 (5 - 16, 601).
For the purpose of allocating expander zones the control panel should be viewed as
unit number 1 and the first expander card as unit number 2 all zones on expander
number 1 therefore start with 2 (e.g 21, 22, 23 . ...)and all zones on the second
expander that is unit number 3 start with 3 (e.g 31, 32, 33 . ...)
Fig8. Zone Allocation on Zone Expander Cards (ZEX)
Expander Card Number 1
4 Wire Mode 2 Wire Mode 2 Wire EOL Mode
AZE1 Zone 21 Zone 21 Zone 21
AZE2 Zone 22 Zone 22 Zone 22
AZE3 Zone 23 Zone 23 Zone 23
AZE4 Zone 24 Zone 24 Zone 24
TZE1 Tamper Zone 21 Zone 25 Zone 25
TZE2 Tamper Zone 22 Zone 26 Zone 26
TZE3 Tamper Zone 23 Zone 27 Zone 27
TZE4 Tamper Zone 24 Zone 28 Zone 28
Note: all AZE zones are +ve and all TZE zones are -ve.
Expander Card Number 2
4 Wire Mode 2 Wire Mode 2 Wire EOL Mode
AZE1 Zone 31 Zone 31 Zone 31
AZE2 Zone 32 Zone 32 Zone 32
AZE3 Zone 33 Zone 33 Zone 33
AZE4 Zone 34 Zone 34 Zone 34
TZE1 Tamper Zone 31 Zone 35 Zone 35
TZE2 Tamper Zone 32 Zone 36 Zone 36
TZE3 Tamper Zone 33 Zone 37 Zone 37
TZE4 Tamper Zone 34 Zone 38 Zone 38
Note: all AZE zones are +ve and all TZE zones are -ve.
From Control Panel to Zone Expander Card 100m maximum
From Zone Expander Card to last Device 100m maximum
On long wiring runs do not draw power for detectors from the Zone Expander Card,
use a separate Power Supply for the detectors.

Page 11
ID Expander Detector Wiring
One ID Expander Card may be fitted to the
GT 600
control panel giving 8 panel
zones plus up to 30 ID zones using industry standard ID Biscuits or ID Detectors. ID
zones numbers are 21 through to 50. Two ID Expander Cards may be fitted to the
GT
601
Control Panel. The 2nd ID card will be zones 51 - 80.
Typical wiring for ID Biscuits is shown below.
Red +12V
Black 0V
Blue > ID-
Yellow > ID +
YBW
BWY
Y = Yellow
B = Blue
W = White
Key -
+ - Ta per Alar Fault/Mask
+-TAMPER ALARM
Supply+
Supply-
L+
L-
White
Blue
Yellow
ID Biscuit
Yellow
Blue
White
Reed Switch
(PA / Contact)
Supply+
Supply-
L-
L+
Fig9. ID Biscuit Wiring Diagram
Fig10. Detector Using Wired Biscuit
Fig11. PA Using Wired Biscuit
Up to four Output Cards may be fitted, each Output Card has four change over
relays.
The recommended maximum distances for ID wiring is as follows:-
From Control Panel to ID Expander Card 100m maximum.
From ID Expander Card to last ID Device 100m maximum.
On long wiring runs do not draw power for detectors from the ID Expander Card, use
a separate Power Supply for the detectors.
Note: For ID pairing,
biscuit numbers
MUST be in sequence...
Example: PIR1 = Biscuits 1& 2,
PIR2 = Biscuits 3 & 4 etc...

GT 600 / 601
Connection Details
If powering up the Control Panel with battery only, connect battery and short out JP1
for approx. 5 seconds. Key pad and Control Panel will then become active.
On the
GT 600
the
BAT. jumper can be
found under the pcb
plastic cover.
Fig12.
Panel Tamper (601 ONLY)
Connect flying lead from
Tamper Switch to JP2.
Page 12

Page 13
Initial Power Up
When the Control Panel is powered up it will be either set or unset dependent on the
state of the Control Panel when it was powered down. The factory default state will be
unset.
Reset to Default Modes
Note: It is
ESSENTIAL
that a 4 6 Yes No reset is done to all new systems
before commencement of programming.
The Control Panel is now back to factory defaults.
If you intend to program the control panel via Gardtec Remote you should default the
panel using 5 5 YES NO This will default the control panel and set-up all the remote
comms options.
Two other reset modes are also available:
3 7 YES NO defaults the system and codes but leaves user names and zone descrip-
tors intact.
1 9 YES NO defaults the Master User to 5678 and Engineer to 1234
Note: If the engineer code has been ‘Locked’ into the system resetting to
default modes will have no effect on the engineer code. The only
way to release this state is to return the PCB to the factory (please
note this is a chargeable service)
System Programming
The system may be programmed by the engineer by use of the engineer code (1234
factory default). Other Engineer/User functions are also available to the engineer,
these are as follows.
Set Unset Remove
Test Log Chime
Note: Details of the above functions are given in the User Manual.
Program Engineer Code
Programming of the Engineer Code is only possible via the Engineer Code (e.g
1234). See Engineer Programming.

Engineer Programming Mode
Engineer Programming
Although LED keypads may be used, ONLYthe LCD keypads can be used to
programme the
GT 600 / 601
Control Panels.
To enter the engineer programming mode follow the steps outlined below:-
1. Remove all power from the system for at least 10 seconds.
2. Apply mains power to the control panel. The display will show, for example:-
3. Whilst this display is showing (the first five sec-
onds) press for the reset required. (E.g 4 6 Yes No).
The display will then show:-
This may show for several minutes.
The display will then show:-
The display may differ from the sample shown
.
Note: Due to changes within the standards,
the
GT600
is only BS or EN2
(GRADE 2) compliant.
Selecting 1:BS - Panel may be programmed to comply with the old BS4737
Standards. DD243 requirements will still apply.
Selecting 2:EN2 - Panel may be programmed to comply with EN50131-1 for Grade 2
Systems. DD243 requirements will still apply.
Selecting 3:EN3 - Panel may be programmed to comply with EN50131-1 for Grade 3
Systems. DD243 requirements will still apply.
4. Select 2:EN2.
Note: This document assumes that 2:EN2 has been selected. For differences
between EN2 and EN3 please refer to the GT600 / 601 Engineer’s Reference Guide.
The manual is available from the web site.
The display will show:-
This may show for several minutes.
Note: For EN3 installations, User Codes and
Engineer Codes MUST be six digits in length
.
Gardtec60x xx - xx
Please WAIT
Select Standard
1:BS 2:EN2 3:EN3
Please WAIT
Version
Page 14

The display will then show:-
From Control Panel Version 2 ONLY.
5. Select either 1 or 2 depending on which standard you require.
The display will show:-
This may show for several minutes.
The display will then show:-
6. Enter Engineer code.
(1234 default).
7. Enter the Authorisor code. The Authorisor code is
the Master User, (default 5678).
The display will show:-
8. Press Yes. The display will show:-
From this point the panel is Engineer Mode and all Tampers will be disabled.
Note: At any point when three underscores are shown on the display you are
viewing a Header. You may move to the next Header by Pressing the NO
Key or access the functions under the Header by Pressing the YES Key.
You are able to jump to various common options when programming by
entering the relevant menu numbers. With a Header showing, key in the
appropriate menu number, then press Yes.
Page 15
Do you want to . .
Use ENGNR. Mode ?
Enter Authorisor
Code . . . . . .
Program . . . . - - -
Zones ?
A Header is indicated by three
underscores on the display.
Select PD6662
1: 2004 2: 2010
Please WAIT

Page 16
Note: Throughout the programming routine you may use the 0 (zero) Key to
escape back one level. This does not apply when a numeric entry is
expected, in this case complete the input before using the 0 Key to
escape.
Factory Default Codes:
Engineer BS / EN2 - 1234
EN3 - 001234
User 1 (Master) BS/EN2 - 5678
EN3 - 005678
Users 2 - 31 (32 - 99, 601 only) Unprogrammed.

Below is shown the Headers (menu numbers, see page 19) that are available and the
options that appear under each Header.
Available Headers & Options
Program Zones...
Zone Types
Zone Descriptors
Zone Wiring
Zone Attributes
(Test/Part/Chime/Cleaner/Walk)
Zone Double Knock, Arm, Log
Zone E/E Mode
Zone Event Tags
Program Setting Modes...
Setting for Full Set
Setting for Part 1 Set
Setting for Part 2 Set
Setting for Part 3 Set
Setting Delay
Setting Sounders
Setting Confirmation
Setting for Auto-Part Set
Program Entry Times...
Entry Time 1
Entry Time 2
Program Bells & Sounders...
Bell Type
Bell Delay Number of Arms
Bell & Sounder Ring
Bell Tamper Mode
Bell in Part Set
Program Keypad...
Keypad Alert 1 Keys
Keypad Alert 2 Keys
Keypad Alert 3 Keys
Keypad Number of Keypads
Keypad Backlight Mode
Ace/Prox
Keypad Areas
Program Digicom...
Digicom Type or Test
Vo-Comm
Digicom Delay / Part
Digicom Channels
Digicom Functions
Digicom View Modem Log
Modem Functions
Comms Functions
Comms Off
Site ID
Tel No. 1
Tell No. 2
Line Monitor
Line Security
Restore Reports
Open / Close Channels
Advanced Functions
Modem Functions
Modem Mode
Double Ring
Keypad Lock / In-Use Text
Site ID Code
Password
Tel No. 1
Tel No. 2
Modem Access
Send Keys / Status
Program Linefault Modes...
Linefault Sounders
Linefault In Exit Mode
Linefault Log Mode
Line Fault Detect Time
Program Panic / Duress...
PA Bells Only
Testable / Non-Testable
Duress Off
(To conform with EN
Standards, Duress is defaulted to Off and
cannot be changed)
.
Page 17

Program PGM 2 / 3 / Timers...
PGM2/3 Operating Mode
Timer 1
Timer 2
Timer 3
Program Reset / Mains...
Mains Fail Delay
Alarm 1 Reset
Alarm 2 Reset
Alarm 3 Reset
Tamper Reset
Alarm Restore
Abort Time
Program Sounder Levels...
Chime Level
Entry / Exit Level
Key Beep Level
Program PGM 1 / XP / Custom...
PGM 1 Mode
Expander 1 Output 1 Mode
Expander 1 Output 2 Mode
Expander 1 Output 3 Mode
Expander 1 Output 4 Mode
Expander 2 Output 1 Mode
Expander 2 Output 2 Mode
Expander 2 Output 3 Mode
Expander 2 Output 4 Mode
Expander 3 Output 1 Mode
Expander 3 Output 2 Mode
Expander 3 Output 3 Mode
Expander 3 Output 4 Mode
Expander 4 Output 1 Mode
Expander 4 Output 2 Mode
Expander 4 Output 3 Mode
Expander 4 Output 4 Mode
Custom Outputs 1 - 8
Program Engineer Code...
Code
Lock / Unlock
Program Service...
Service Timer
Service Telephone Number
Lock-Out On / Off
Engineer Mode Constant / Timed
Program Custom Screens...
LCD Status
LED Status
Custom Display On / Off
Program Custom Text
Program Diagnostics / Log...
List Event Log
Change / List Diagnostics
Program Alarm Confirm...
Confirm Window Time
Confirm On Entry
Confirm Sounder Mode
Confirm Reset Mode
Confirm Secondary Time
Confirm ET Mode
Confirm Bell Mode
Confirm Strobe Mode
Confirm Start Delay
Confirm ACE Battery Monitor
Confirm Comms Restore
Confirm Keypad Opening
Although LED keypads may be used
ONL
Ythe LCD keypads can be used
to programme the
GT 600 / 601
Control Panel.
Page 18

Common Options With Menu Numbers
You are able to jump to various common options when programming by
entering the relevant menu numbers. With a Header showing, key in the
appropriate menu number, then press Yes.
For a full list of Common Options please refer to the
GT 600 / 601
Engineer’s Reference Guide which is available on the web site.
Menu Item
12 Full Set Setting Time / Setting Mode
22 No. of Keypads / Multi On Off / K/Switch
28 Entry Time 1
34 Digicom Type
38 Engineer Code
46 Main Fail Delay
47 Tamper Reset Mode
50 Zone Response
52 Zone (Attributes)
155 Confirm Time Window (DD243 Section)
139 PSU Test Time
Note: If any Zones (panel or expander zones) are not used the terminals for that
Zone should be left open (no link) and the Zone should be programmed as Off
Zone Defaults
Zone types by default are
Zone 1 = Entry / Exit Area 1 Non-Removable
Zone 2 = Access Area 1 Non-Removable
Zone 3 = 12Hr Area 1 Non-Removable
Zone 4 = 12Hr Area 1 Non-Removable
Zone 5 = 12Hr Area 1 Non-Removable
Zone 6 = 12Hr Area 1 Non-Removable
Zone 7 = 12Hr Area 1 Non-Removable
Zone 8 = 12Hr Area 1 Non-Removable
All Expander Zones = 12Hr Area 1 Non-Removable
Zones on Expander 1 start at 21 through to 28
Zones on Expander 2 start at 31 through to 38
Zones on Expander 3 start at 41 through to 48
Zones on Expander 4 start at 51 through to 58
Note: Zones 25-28, 35-38, 45-48 & 55-58 will only be available if 2 wire or 2
wire EOL wiring mode has been programmed for that expander card.
Page 19
Other manuals for GT 600
1
This manual suits for next models
1
Table of contents
Other Risco Control Panel manuals

Risco
Risco GT Plus Instruction manual

Risco
Risco gt490x User manual

Risco
Risco GardTec 350+ User manual

Risco
Risco GardTec 350+ User manual

Risco
Risco LightSYS Instruction manual

Risco
Risco RisControl User manual

Risco
Risco GT 600 User manual

Risco
Risco RisControl User manual

Risco
Risco ProSYS 128 User manual

Risco
Risco RisControl User manual