RNA ESG 1000 User manual

Operating Instructions
Controller for vibratory drive systems
SCU1000
ESG1000

Rhein-Nadel Automation GmbH 2
VT-BA-ESG1000-EN-2020 / 07.10.2020 SJ
Table of Contents
1. Technical data........................................................................................................................4
1.1.Functional description............................................................................................................4
1.2.EC - Conformity.....................................................................................................................4
1.3.Technical data.......................................................................................................................4
2. Safety notes...........................................................................................................................5
3. Information for starting. ..........................................................................................................5
3.1.Explanations on the term OPERATING MODE.....................................................................6
3.2.Switching over to a different mains voltage ...........................................................................6
3.3.Setting the minimum and maximum output voltage...............................................................7
3.4.Switching over to a different mains voltage ...........................................................................7
3.5.Releasing the function by external components....................................................................7
3.6.Canging the soft start time.....................................................................................................7
4. Plan showing the position of the operating elements on the boards ......................................8
5. Scale Drawing........................................................................................................................9
6. Connecting Diagram ..............................................................................................................9

Rhein-Nadel Automation GmbH 3
VT-BA-ESG1000-EN-2020 / 07.10.2020 SJ
Declaration of Conformity
According to the Low-Voltage Directive 2014/35/EU
and Electromagnetic Compatibility Directive 2014/30/EU
We hereby declare that the product meets the following requirements:
Low-Voltage Directive 2014/35/EC
Electromagnetic Compatibility Directive 2014/30/EU
Applied harmonised standards: DIN EN 60204 T1
EN 61439-1
Remarks:
Rhein-Nadel-Automation
---------------------------------
Managing Director
Jack Grevenstein

Rhein-Nadel Automation GmbH 4
VT-BA-ESG1000-EN-2020 / 07.10.2020 SJ
1. Technical data
1.1. Functional description
The compact design of the control unit can supply all RNA-control units up to a load current of 6 ampere. It is intended
for individual installation directly at the oscillating drive and completely pluggable. The correcting range for the potenti-
ometer in the front plate has been adjusted in the factory at a reference drive and allows the adjustment of the output
voltage from 40 to 280 volteff .
The illuminated rocking switch in the front plate separates the control unit with 2 poles from the mains. For frequent
switching or operation with a superordinated control unit there is the possibility of wattless disconnection by means a
potential-free contact as well as by 16-30VDC voltage signal. The intervention into the device necessary for that is
described under point 3.5, Release of the function by external components.
The soft start, a time-controlled bringing-up of power to the adjusted value after switching on, is fixed with approx. 0.5
seconds. If necessary this time can be changed in the device.
1.2. EC - Conformity
The control device corresponds to the following regulations:
Low voltage directive 2014/35/EU
EMC directive 2014/30/EU
Applied harmonized standards:
DIN EN 60204 T1
EN 61439-1
The control device corresponds also to the UL/CSA regulations.
1.3. Technical data
Mains connection:
230 Volt AC, 50/60 Hz, +10 -15% or
115 Volt AC, 50/60 Hz, +10 -15% , internally selectable
Output voltage:
40...208 Volt (eff.) adjustable, (230 V mains)
20...105 Volt (eff.) adjustable, (115 V mains)
Load current:
max. 6 Amp.(eff)
Safety fuse:
Fine-wire fuse 5 x 20; 6,3 MT time-lag
Operating modes:
1. symmetric full wave operation
(oscillating frequency = double mains frequency)
2. asymmetric half wave operation
(oscillating frequency = mains frequency
Operating mode selection:
Encoding bridge in the load plug
Function release:
selectable by internal jumpers
Release by external contact:
potential-free make contact, load approx. 6 mA
Release by external signal:
Reverse battery protected input, level 16...30 VDC
at 24 Volt approx. 8 mA
Soft start:
internally adjustable, standard approx.. 0,5 sec.
Insulation type:
IP 54
Radio interference suppression:
according to EMV - regulations
Dimensions:
104 x 213 x 153 (width x height x depth)

Rhein-Nadel Automation GmbH 5
VT-BA-ESG1000-EN-2020 / 07.10.2020 SJ
2. Safety notes
The safety notes shall in any case be read and understood. Their observance secures the conservation of valuable
material and avoids health impairment.
The symbol of the pointing hand is shown in these operating instructions at points, which must be particu-
larly observed, so that recommendations, regulations, notes and the correct procedure of work can be ob-
served, as well as damage and destruction of the machine and/or other equipment parts is avoided.
Electric danger, eg. at work under voltage
Work at electrical equipment of the machine/equipment may only be carried out by a qualified electrician or
by trained personnel under direction and supervision of a qualified electrician according to the electronic
regulations!
All safety and danger notes at the machine / equipment must be observed!!
The electrical equipment of a machine / equipment must be examined regularly. Faults, eg. loose connec-
tions or damaged cables, must be eliminated immediately!
Before opening the device unplug the power plug!
3. Information for starting.
Before the mains connection is made and the control unit is switched on, the following points must in any
case be checked:
•Is the control unit closed properly and with all screws?
•Are the existing plug fixing devices locked into place/screwed down?
•Are all cables and ducts undamaged?
•Is the INTENDED USE guaranteed?
•Does the mains voltage indication comply with the local power supply network?
•Does the mains frequency indication at the oscillating drive comply with the local power supply net-
work?
Is the correct operating mode set at the control unit? (on that read explanation operating mode)
Only if all above mentioned questions can be answered with yes, the control unit can be put into operation.
At initial starts or starts after repair work or exchange of control units/oscillating drives the minimum output
should be set at the control unit before switching on the device. When bringing up the output it must be
taken care for correct function.

Rhein-Nadel Automation GmbH 6
VT-BA-ESG1000-EN-2020 / 07.10.2020 SJ
3.1. Explanations on the term OPERATING MODE
RNA - Oscillating drives are mechanical spring vibrators, which, according to weight and/or size, are adjusted to an
oscillating frequency near the mains frequency. Two operating modes are possible:
1. Asymmetrical half-wave operation - the oscillating
drive operates with mains frequency.
2. Symmetrical full-wave operation - the oscillating
drive operates with double mains frequency.
From that the following details result for the oscillating frequency:
Mains frequency
50 Hz
60 Hz
Operating mode 1
Oscillating frequency50 Hz = 3000 min-1
Oscillating frequency 60 Hz = 3600 min-1
Operating mode 2
Oscillating frequency 100 Hz = 6000 min-1
Oscillating frequency 120 Hz = 7200 min-1
At a mains with 50 Hz only oscillating drives with 50 Hz or 100 Hz oscillating frequency can be operated, at a mains with
60 Hz, however, only oscillating drives with 60 H7 or 120 Hz oscilllating frequency. The control unit can operate in both
operating modes. It must, however, be switched into the correct operating mode. The mains frequency is of no im-
portance for the control unit.
3.2. Switching over to a different mains voltage
The selection of the operating mode takes place by entering a code into the load plug of the oscillating drive. A jumper
in the plug from connection 3 to 4 switches the control unit into operating mode 2: 100 or 120 Hz. If this connection is
missing, the control unit operates in the operating mode 1: 50 or 60 Hz.
As a standard oscillating transport units are provided with the correct code in the plug. To assist the user, the threaded
cable fitting has distinguishing colours on the connector jack for better recognition
BLACK for operating mode 1, 50 Hz or 60 Hz, GREY for operating mode 2, 100 Hz or 120 Hz.
Threaded fitting M20
grey –2, 100 Hz oscillation frequency
black –1, 50 Hz oscillation frequency
metal-EMV-threaded fitting
for frequency regulated devices

Rhein-Nadel Automation GmbH 7
VT-BA-ESG1000-EN-2020 / 07.10.2020 SJ
3.3. Setting the minimum and maximum output voltage
The control units have been adjusted in the factory at a reference drive. In special cases or after modifications a read-
justment may become necessary. Here it must in any case be observed:
The output voltage can only be measured with an oscillating drive being connected!
The measuring device must be designed for real effective measurement. (True-RMS), other measuring
devices indicate random values. The load plug must be plugged in, as otherwise the measurement possibly
takes place in the wrong measuring mode.
As the adjustment of the output voltage requires feeding of the mains voltage, the following safety note is very important:
Feed the supply voltage only by means of a safety transformer! Carry out the measurements in the
rooms/zones permitted for that. This measurement requires the employment of qualified professionals.
After the measuremtn the control device must be put back into the original condition, as otherwise the re-
lease of series is stopped!
Important is the remark that the adjusting devices for the output voltage are not reactionless towards each other. I. e.
that at a change of the maximum voltage the minimum voltage is slightly changed as well - and vice versa. That possibly
means a repeated adjustment of both trimming potentiometers.
3.4. Switching over to a different mains voltage
The control unit can be operated at 230 V, 50/60 Hz as well as at 115 V, 50/60 Hz, must, however, be switched over to
this voltage,
Changing from 230V to 115V:
Take the plug out of the electrical socket and open the device on the right side. Toggle the switch and close the side of
the device. Test run. UMAX may have to be re-adjusted.
(See the layout plan for the adjustable parts, figure 3)
3.5. Releasing the function by external components
The standard adjustment of the control unit provides that the oscillating drive starts, when the mains switch is
switched on. Should it be preferred that the control unit work in start-stop operation, then the control unit should be
opened —observing all of the precautionary measures listed above —and the jumper S1 re-plugged; see layout
plan, figure 3. Remove the dummy plugs on the side of the casing and install a threaded cable fitting M16 with
strain-relief; the cable will be fed through here for release. Release is achieved in two possible ways:
Release by a contact
This simple, cost-efficient solution works in a way that the control unit is released by making the contact and the oscil-
lating drive operates. The connection is made at the terminals 33 - 34. Some points should be observed:
•The connection is fed with mains voltage! Cable type and colour, insulation regulations must be observed, the
contact must of course be potential-free.
•Starting at 2 m and above, the cable must be shielded; the shielding is situated on one side of the control unit on
the protective earth conductor.
•The cable length should not exceed 5 meter.
•The cable may not be installed in immediate neighbourhood to high-energy switching equipments or strong inter-
ference fields.
3.6. Canging the soft start time
The soft start, the time-controlled bringing up of the output to the adjusted value is an effective protection for the oscil-
lating drive against magnet impacts. At small oscillating drives, which start with high cycle times, the standard time is
not necessary in any case, it does even impede the production flow. At the trimmer SOFT START the run-up time can
be adjusted. As the case must be opened for this change as well, the safety notes mentioned above should be ober-
served.

Rhein-Nadel Automation GmbH 8
VT-BA-ESG1000-EN-2020 / 07.10.2020 SJ
4. Plan showing the position of the operating elements on the boards
Netzkabel
ExternerKontakt
Externe Spannung
24 V, DC
31 32 33 34
12
3456789
Netzschalter
X1
10kOhm
X16
Erdung
Gehäuse
LP1334
Ausgangssteckdose
S1
1 23 4 PE
X8 X18
ESG 1000
Potentiometer
Pos. 52
Pos. 59
Pos. 50 + 51
Detail B
Pos. 80
Freigabe
When replacing the fuse the preset value of M 6,3 A is to be used in any case. A fuse which is rated too
high can lead to breakage of the conrol unit.
Release by voltage signal
The connection is done on the fasteners 31 (GND) and 32 (+24 VDC). The drive starts, when a signal is fed between
10- and 30-volt direct current in correct polarity. The input is protected against faulty polarity. The use of an optocoupler
in the control unit makes the input potential-free and allows the installation with unscreened cables of nearly any length.
Here too high-energy interferences should be avoided.
Token
Commentasy
S0
Switch
110 V –230 V
Electric voltage
S1
External release
Release
External contact
External voltage
24 V. DC
Electric cable Pos. 80
Electric switch Pos.
52
Casing ground
Detail B
Exit xocket
Pos. 50 + 51

Rhein-Nadel Automation GmbH 9
VT-BA-ESG1000-EN-2020 / 07.10.2020 SJ
5. Scale Drawing
6. Connecting Diagram

Rhein-Nadel Automation GmbH 10
VT-BA-ESG1000-EN-2020 / 07.10.2020 SJ
RNA Group
Headquarters
Manufacturing and Sales
Rhein-Nadel Automation GmbH
Reichsweg 19-23
D-52068 Aachen
Phone: +49 (0) 241-5109-0
Fax: +49 (0) 241-5109-219
www.RNA.de
Further RNA group companies:
Manufacturing and Sales
Focus: Pharmaceutical Industry
PSA Zuführtechnik GmbH
Dr.-Jakob-Berlinger-Weg 1
D-74523 Schwäbisch Hall
Phone: +49 (0) 791 9460098-0
Fax: +49 (0) 791 9460098-29
www.psa-zt.de
Manufacturing and Sales
RNA Automation Ltd.
Unit C
Castle Bromwich Business Park
Tameside Drive
Birmingham B35 7AG
United Kingdom
Phone: +44 (0) 121 749-2566
Fax: +44 (0) 121 749-6217
E-mail: RNA@RNA-uk.com
www.rnaautomation.com
Manufacturing and Sales
HSH Handling Systems AG
Wangenstr. 96
CH-3360 Herzogenbuchsee
Switzerland
Phone: +41 (0) 62 956 10-00
Fax: +41 (0) 62 956 10-10
E-mail: info@handling-systems.ch
www.handling-systems.ch
Manufacturing and Sales
Pol. Ind. Famades c/Energia 23
E-08940 Cornella de Llobregat (Barcelona)
Spain
Phone: +34 (0)93 377-7300
Fax:: +34 (0)93 377-6752
E-mail: info@vibrant-RNA.com
www.vibrant-RNA.com
www.vibrant.es
Further manufacturing sites
of the RNA Group
Manufacturing
Lüdenscheid branch
Rhein-Nadel Automation GmbH
Nottebohmstraße 57
D-58511 Lüdenscheid
Phone: +49 (0) 2351 41744
Fax: +49 (0) 2351 45582
E-mail: werk.luedenscheid@RNA.de
Manufacturing
Ergolding branch
Rhein-Nadel Automation GmbH
Ahornstraße 122
D-84030 Ergolding
Phone: +49 (0) 871 72812
Fax: +49 (0) 871 77131
E-mail: werk.ergolding@RNA.de
Manufacturing
Remchingen branch
Rhein-Nadel Automation GmbH
Im Hölderle 3
D –75196 Remchingen-Wilferdingen
Phone: +49 (0) 7232 - 7355 558
E-mail: werk.remchingen@RNA.de
Other manuals for ESG 1000
1
Table of contents
Other RNA Controllers manuals
Popular Controllers manuals by other brands

Alpine
Alpine KTX-H100 owner's manual

Emerson
Emerson KEYSTONE OM13 EPI-2 Installation, operation and maintenance manual

PI
PI P-841.1 user manual

gefran
gefran GF_LOOPER 3.5” quick start guide

Carlisle
Carlisle Ransburg 9060 HV2 Service manual

Kollmorgen Seidel
Kollmorgen Seidel 04S Series Assembly/Installation/Commissioning

MUSCLE Corporation
MUSCLE Corporation Cool Muscle 3 user guide

P&B
P&B MPC2000+ Technical manual

EuroLite
EuroLite DMX LED OPERATOR 6 user manual

Cypress
Cypress CY3280-20x66 Universal CapSense Guide

Emerson
Emerson YARWAY Series Instruction, Operation and Maintenance Manual

AMX
AMX NetLinx Integrated Controller NI-2100 Hardware reference guide