RNA ESR 3000 Series User manual

Operating Instructions
Controller
for vibratory drive systems
ESR 3000
ESM 3000

Rhein-Nadel Automation GmbH 2
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
Table of Contents
1. General ..................................................................................................................................5
1.1. EC Conformity.....................................................................................................................5
2. Function .................................................................................................................................6
2.1. Track control.......................................................................................................................6
2.2. Operating with two speeds (2 set points for coarse/fine switching).....................................6
2.3. Control inputs and output....................................................................................................6
2.3.1. Enable input .................................................................................................................6
2.3.2. Sensor input for track control........................................................................................6
2.3.3. External set point..........................................................................................................7
2.3.4. Output status relay.......................................................................................................7
2.3.5. Time-Out output 24 VDC..............................................................................................7
2.3.6. Air valve output 24 VDC...............................................................................................7
2.4. Display................................................................................................................................7
3. Construction...........................................................................................................................7
3.1. Enclosed units.....................................................................................................................7
3.2. Panel mounting units ..........................................................................................................7
4. Technical Data.......................................................................................................................8
5. Ordering Codes (Standard units) ...........................................................................................8
6. Settings..................................................................................................................................9
7. Control elements..................................................................................................................10
7.1. Settings.............................................................................................................................10
8. Commissioning.....................................................................................................................11
8.1. Assembling position..........................................................................................................11
8.2. Preliminary steps ..............................................................................................................11
8.2.1. Important points..........................................................................................................11
8.2.2. Operating frequency of the feeder coil .......................................................................11
8.2.3. Measurement of the output voltage and current.........................................................11
8.3. Putting the equipment into operation ................................................................................11
9. Setting Instructions...............................................................................................................12
9.1. User adjustment of throughput..........................................................................................12
9.2. Tuning the feed system.....................................................................................................13
9.2.1. Feeder settings...........................................................................................................13
9.2.2. Track control...............................................................................................................14
9.2.3. Sensor time out..........................................................................................................14
9.2.4. Set point source .........................................................................................................14
9.2.5. Pulse feed ..................................................................................................................15
9.2.6. Determining the resonant frequency ..........................................................................15
9.2.7. Display actual current and frequency.........................................................................15
9.2.8. Save selected parameters..........................................................................................15
9.2.9. Recall user or factory settings....................................................................................16
9.2.10. Hide parameter menus............................................................................................16
10. Error messages / ERROR reset...........................................................................................17
11. Connections for enclosed construction ................................................................................18
11.1. Connections for enclosed construction..........................................................................19
12. Connections for 6 A panel mounting versions......................................................................20
13. Dimensions - Enclosed construction....................................................................................21
13.1. Dimensions –Panel mounting.......................................................................................22
14. Service appendix..................................................................................................................23
14.1. Service Menu.................................................................................................................23
14.2. Frequency adjustment range.........................................................................................23
14.3. Current limiting ..............................................................................................................24

Rhein-Nadel Automation GmbH 3
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
Declaration of Conformity
According to the Low-Voltage Directive 2014/35/EU
and Electromagnetic Compatibility Directive 2014/30/EU
We hereby declare that the product meets the following requirements:
Low-Voltage Directive 2014/35/EC
Electromagnetic Compatibility Directive 2014/30/EU
Applied harmonised standards: DIN EN 60204 T1
EN 61439-1
Note:
Rhein-Nadel-Automation
---------------------------------
Managing Director
Jack Grevenstein

Rhein-Nadel Automation GmbH 4
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
Technical safety instructions for the user
This description contains the necessary information for the correct application of the product described below. It is
intended for use by technically qualified personal.
Qualified personnel are persons who, because of their training, experience and position as well as their knowledge of
appropriate standards, regulations, health and safety requirements and working conditions, are authorised to be
responsible for the safety of the equipment, at all times, whilst carrying out their normal duties and are therefore aware
of, and can report, possible hazards (Definition of qualified employees according to IEC 364)
Safety Instructions
The following instructions are provided for the personal safety of operators and also for the protection of the described
product and connected equipment.
Isolate from mains before installation or dismantling work, as well as for fuse changes or post installation
modifications.
Observe the prescribed accident prevention and safety rules for the specific application.
Before putting into operation check if the rated voltage for the unit conforms with the local supply voltage.
Emergency stop devices must be provided for all applications. Operation of the emergency stop must inhibit any
further uncontrolled operation.
The electrical connecting terminals must be covered!
Earth bonding must be tested for integrity after installation.
Specified Use
The units described herein are electrical controllers for installation in industrial plant.
They are designed for controlling vibratory feeders.
For use in NFPA 79 Applications only
Adapters providing field wiring means are available from Rhein-Nadel Automation GmbH.
Refer to Rhein-Nadel Automation GmbH.
Attention
Hazardous Voltage Failure to observe can kill, cause serious injury or damage

Rhein-Nadel Automation GmbH 5
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
1. General
The ESR 3000 –ESM 3000 range comprises special, adaptable controllers for use with vibratory feeders. The units
generate an output frequency, to drive feeders, that is independent of mains frequency and so exact tuning with
springs is not necessary. The feeders also run quieter because of the sinusoidal output signal. The adjusted output
frequency corresponds to the mechanical vibrating frequency of the feed system. The optimum frequency setting for a
feeder can determined manually or automatically in regulation mode.
Depending on the version, the controller can be used in regulation mode, working in conjunction with an accelerometer
fitted to the feeder, to operate at resonant frequency. In this way a constant component feed rate that is unaffected by
load changes can be achieved. In regulation mode the vibrating frequency is also dynamically adjusted to compensate
for resonant frequency changes caused by load changes. In normal operating mode (without accelerometer) the
feeder remains constant at the set frequency. In both operating modes the feeder throughput is determined by the
output voltage level.
Totally enclosed or panel mounting units can be supplied.
Notable Features:
•Adjustable output frequency, independent of mains
frequency
•Adjustable minimum and maximum limits for the frequency
range
•Adjustable current limit for the maximum coil current
•Constant feeder throughput irrespective of mains
fluctuations
•Regulation control, with independent frequency search
(resonance)
•On/Off status relay
•Track control
•24 VDC output for operating a solenoid e.g air valve
•Four user setting memory locations
•Optional RS232 or Profibus-DP interface for remote
parameter setting.
1.1. EC Conformity
The control device corresponds to the following regulations:
Low voltage directive 2014/35/EU
EMC directive 2014/30/EU
Applied harmonized standards:
DIN EN 60204 T1
EN 61439-1
Enclosed version
Panel mounting
version

Rhein-Nadel Automation GmbH 6
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
2. Function
The unit is set up by using the touch panel on the front plate (buttons and LED display). All settings can be made by
using the touch panel and a series of menus. The various parameters can be selected by entering operator codes. A
fuller description of the parameters can be found In the section on settings. Alternatively, the feeder throughput can
adjusted by using an external potentiometer, an external voltage signal 0...10 V, DC or a current signal 0(4)...20 mA (the
chosen option must be selected in menu 003). A relay with potential free contacts is provided for feeder status indication
and this operates in conjunction with the feeder enable signal. Terminals for these contacts can be found inside the
controller.
During normal operation the set point is displayed as a percentage in the LED window. In the programming mode the
selected dimension, as described in the setting up instructions, is shown. Changed settings can be stored by leaving
the programming mode or automatically saved by not pressing a key for a period of 100 seconds.
The control units can provide a frequency range from 5…300 Hz, which can be limited by adjustable, upper and lower
frequency limits. The usable adjustment range cannot exceed a ratio of 1:4, i.e. the upper frequency limit cannot be
more than four times the lower frequency limit. It is possible to have a narrower setting of the limits and this provides a
margin of safety against too wide a difference in the vibrating frequency.
The maximum output current drawn by the coil can be determined by integrated current limiting.
Critical parameters such as the current limit and vibrating frequency range are held under a special service menu. This
menu cannot be accessed through the normal menu structure and an additional code number has to be used to gain
access. This prevents unauthorised adjustment of these sensitive parameters.
An interface option can be used to provide an RS232 or Fieldbus (Profibus-DP) connection.
2.1. Track control
The output can be switched
ON and OFF from a track
component sensor, using
internal, adjustable time
delays (ton and toff).
The queue of components
rises above and drops
below the track sensor
position. The controller
output switches on when
the sensor cannot detect product and a switch-on time delay has elapsed. The output is switched off when product is
detected and a switch-off time delay has elapsed (FULL displayed in the LED window). Gaps in the product feed cause
resetting of the time delay. The time will always be precise from the last or first component, respectively. The ON and
OFF time delays are set in the programming menu. The first decimal point in the display blinks to indicate that an internal
timer is running.
An additional “Sensor-Time-out timer is started when the feeder switches on. This can be set (30...240 sec.) to switch
off the feeder if no product is sensed in the time out period. The status relay indicates that the feeder is not running and
the LED window displays ERROR and SE alternately. This function is optional and must be selected in the Track Settings
Menu with function EE = 1.
2.2. Operating with two speeds (2 set points for coarse/fine switching)
Coarse/Fine control can be used instead of track control (Menu C 003). The second set point is activated through the
same sensor input that is used for track control. Either contacts or a 24 VDC signal can be used to change the set point
from coarse to fine. The second set point is activated, immediately, by applying a 24 V signal
(The track control function is invalid)
2.3. Control inputs and output
2.3.1. Enable input
External switch or 24 VDC signal voltage.
External control function to switch the power output ON or OFF e.g. Networking of several controllers from a central
PLC.
2.3.2. Sensor input for track control
Sensor for monitoring the queue of components on the track or an input for switching to the second set point 24 VDC
(PNP).
t ON
t OFF
Sensor
Feeder
ON
OFF
ON
OFF
Soft Start
Soft Stop

Rhein-Nadel Automation GmbH 7
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
2.3.3. External set point
The feeder amplitude set point can be provided from and external, analog 0...10 V, DC, 0(4)...20 mA, or a 10 kR
Potentiometer. Parameter ESP in Menu C003 must be set to 1, for an external set point source to be used (not on 16A
units).
Setting the minimum output value when external set point = 0:-
Before changing the ESP parameter to accept an external set point source, the minimum value can be adjusted by using
the cursor keys, on the front panel, and this will remain when the ESP is changed over from 0 to 1.
2.3.4. Output status relay
Status-Relay contact 250 V/1 A (changeover). Relay closes when the feeder is running –the relay opens when there is
no enable signal or a fault displayed.
2.3.5. Time-Out output 24 VDC
"Time Out" message active, if after adjusted time no material is recognized by the sensor (adjustable with parameter
"E."). (not on 16 A units)
2.3.6. Air valve output 24 VDC
Output for air blast, comes on with feeder and switches off, 4 sec., after feeder stops (not on 16A units)
2.4. Display
Initialisation phase, when supply voltage is connected (left decimal point blinks).
Normal Mode: The throughput set point is displayed
Output locked via enable input
Output switched off via keyboard (“0” key)
Output switched off by the track control sensor
Under voltage, input voltage is to low.
3. Construction
The units are available as stand-alone, enclosed or panel mounting versions.
3.1. Enclosed units
•Mains switch
•Touch panel with display
•Mains cable with plug
•Output cable or output socket for connecting to the feed system
•Sensor socket. The standard unit has provision for 24 VDC sensors with a PNP output
3.2. Panel mounting units
•Touch panel with display
•Terminals for electrical connections
•Screw hole fixings for mounting

Rhein-Nadel Automation GmbH 8
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
4. Technical Data
Model Type
ESR 3000 / 6A
ESR 3000 / 12A
ESM 3000 / 6A
Supply voltage
110 V, 240 V +/- 10 %, 50/60
Output
0...95 V, 0...205 V
Output current
Max. 6 A
Max. 12 A
Max. 6 A
Recommended
Protection
10 A Anti-surge 16 A Anti-surge 16 A Anti-surge 16 A Anti-surge
Type D current trip device
Fine-wire fuse
internally
Fine-wire fuse 5x20 10 Amp. T-T
Enable
24 V, DC input (connect to internal 24 V reference)
Status relay
Change-over contacts, 250V, 1 A
Sensor supply
24 V, DC, 100 mA
Sensor type
PNP output
Status output
Relay, change-over contact 1A, 250 VAC , 60 VDC
Solenoid valve
output
24 VDC / 50 mA switched with feeder unit (PNP), short- not provided
circuit protected
Operating
temperature
0...+45 °C
Storage temperature
-10...+80 °C
Altitude
1000 m 0,5 % rated current reduction for each additional 100 m
The units are provided with switch-on, current damping. However it is still possible that some internal capacitor,
energising, current spikes will be generated, especially when several units are switched on simultaneously.
Therefore, fuses and overload trips should have anti current surge characteristics.
5. Ordering Codes (Standard units)
Type
Construction
ESR 3000 / 6 A –IP54
6 A, Enclosed construction with track control and accelerometer
regulation
ESR 3000 / 12A –IP 54
12 A, Enclosed construction with track control and accelerometer
regulation
ESM 3000 / 6A –IP20
6 A, Panel mounting with track control and accelerometer
regulation
For use in NFPA 79 Applications only E217179
Adapters providing field wiring means are available from Rhein-Nadel Automation GmbH.
Refer to Rhein-Nadel Automation GmbH.

Rhein-Nadel Automation GmbH 9
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
6. Settings
After checking the correct operation of the controller in conjunction with the vibratory feed system it is
advisable to restrict the user to feeder throughput settings only.
Setting the feeder throughput:
Press the P key twice and adjust the throughput with the cursor keys (Code C. 000).
Parameter:
Code
Factory
setting:
Entry Code:
Vibratory feeder
•Amplitude (throughput)
0...100 %
A.
0 %
000, 002
The following variable parameters are available for setting up the feed system
Parameter:
Display
Factory
setting:
Entry Code:
Vibratory feeder
•Amplitude (throughput)
0...100 %
A.
0 %
000, 002, 020
096
•Maximum control limit (Umax)
5...100 %
P.
90 %
008, 020, 096
•Vibrating frequency
35...140 Hz
(5...300 Hz)
F.
100 Hz
008, 020
040, 096
•Soft start ramp up
0...60 Sek.
/.
0,1 Sec.
020, 096
•Soft stop ramp down
0...60 Sek.
\.
0,1 Sek.
020, 096
•Switch to external set point
0 / I
E.S.P.
0
003
•Set point 0(4)...20 mA
0 / I
4.20
0
003
•Potentiometer set point
0 / I
POT.
0
003
•Coarse / Fine control
0 / I
S.P.2.
0
003
•Invert enable
0 / I
-En.
0
003
•Pulse feed
0 / I
HOP.
0
064
•On time delay (only if HOP. = I)
0...60 Sec.
H.
1,0 Sec.
004, 064
•Off time delay (only if HOP. = I)
0...60 Sec.
h.
1,0 Sec.
004, 064
•Invert hopper sensor (not active)
0 / I
-Ho.
0
004, 064
Track control
•Switch on time delay
0...60 Sec.
I.
1 Sec.
007, 167
•Switch off time delay
0...60 Sec.
O.
1 Sec.
007, 167
•Invert sensor
PNP / PNP
invers
-SE.
PNP
007, 167
•Sensor Time-out
0 / I
E.En.
0
015, 167
•Sense time delay (Sensor Time-out)
1...240 Sec.
E.
180 Sec.
015, 167
•Switch off time air valve
0...60 Sec.
A.i.
4 Sec.
015
Service
•Display actual output current
i.
040
•Display actual frequency
F.
040
•Save user settings
PUSH.
143
•Recall factory settings
FAC.
210
•Recall user settings
US.PA.
210
•Hide programming menus
0 / I
Hd.C.
0
117
•Hide set point adjustment
0 / I
di.S.
0
137
•Display software version
001

Rhein-Nadel Automation GmbH 10
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
7. Control elements
7.1. Settings
The six buttons and a LED display found in the
front panel, are used for operating and setting up
the unit. All operating methods and adjustable
parameters can be set up through this panel.
The “I“ and “O“ buttons are used for switching the
unit ON and OFF, however, these do not provide
mains isolation, they simply inhibit the power
semiconductors
The “P“, “F“ and “Cursor Buttons“ are used for
parameter adjustment. Parameters are set by
using menu controls which are called up by
entering operator codes. The functions are
described in greater detail in the section on setting
instructions.
The display value can be increased or decreased
by units, or tenths of units, by a short press of the
cursor buttons. Holding the buttons down will
cause the display to change in units of ten.
To prevent accidental or unauthorized adjustment the adjustment parameters, in the user menus, are protected. A code
must be entered to open the user menus. There are different pass codes for each function group.
Setting adjustments are automatically saved upon leaving the programming mode or if no button is pressed for
a period of 100 seconds.
All setting routines are commenced by pressing the programming button “P“. The following diagram should clarify the
sequence in which keys are pressed:-
1. Press the “P“ key.
2. Select the code number with the cursor keys.
3. Press the “P“ key. This displays the first menu point. The required menu point can be found by repeatedly
pressing the “P“ key (scrolling).
4. The value in the menu point can be changed with the cursor keys.
5. Scroll to the next menu point or to the end of the menu, which returns the display to the set point value, by
pressing the “P“ key. To exit the menu and return back to the normal display, quickly, depress the “P“ key for 5
seconds.
6. To return back to the previous position in the menu, press the “F“ key.
PP
P
P
P P
I
0
P
F
ON
OFF
Display
ACCEPT
or SKIP FUNCTION
Reduce
Increase
Back

Rhein-Nadel Automation GmbH 11
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
8. Commissioning
8.1. Assembling position
8.2. Preliminary steps
•Check that the unit is correct for the local mains supply (rating plate information) and that it is correctly rated
for the feed system.
•Connect the controller according to the connection diagram
•When applications with frequently on and off cycles are required, use the intended enable input. It is
prohibited to open the current circuit with a switch or a contactor while the feeder is running.
8.2.1. Important points
Using the control units described in this document, it is possible to adjust the feed system that it runs in
resonance. In this condition it is possible to obtain excessive output for a very low set point setting. Therefore
extreme care should be taken to avoid causing damage to the drive coil, through hammering.
In practice it is not possible to run at resonant frequency without accelerometer feedback because the system would be
unstable and uncontrollable. The system must be set safely off resonance i.e. either above or below the natural
frequency.
Resonant frequency: Depending on the spring and mass design of the feeder system it is possible to have resonance
at more than one frequency. These additional resonance points are multiples of the main frequency. For this reason in
critical situations it is possible that the automatic frequency search will not find true resonance and in such cases the
natural frequency must be determined manually.
8.2.2. Operating frequency of the feeder coil
It is possible that the current flowing through the coil will increase for a small frequency adjustment. and so this should
be checked with a true RMS instrument for each new application as well as monitoring the coil for heat build-up.
The coil should be designed for the correct operating frequency to prevent excessive current draw and the consequential
overloading of the coil.
8.2.3. Measurement of the output voltage and current
The voltage and current cannot be measured with a regular instrument because the controller output uses an electronic
inverter with a pulse width modulation signal. An effective measuring instrument such as a moving iron meter (analog)
must be used. It is recommended that an analog instrument is used rather than an electronic multi-meter which will give
a misleading reading.
8.3. Putting the equipment into operation
1. Establish the vibrating frequency.
2. Establish the power of the feed system (maximum permissible current draw).
For a new feeder where settings are unknown: (see also comments below)
Without connecting the feeder, select parameter FAC in menu C210 (reset factory settings), press the cursor key to
reset (SAFE) and press the P key to leave the menu. The factory settings are listed in the table in section 7, headed
settings
! Comments !
It is possible that a special parameter set, for a machine manufacturer, has been pre-stored under a user code and
these can be recalled. In such instances specific machine settings will be loaded and so the next steps are not relevant.
Basic settings:
•Connect feeder.
•Set frequency (refer to feeder data sheet). Menu C096 parameter F.
•Check current limit (refer to feeder data sheet). Menu C040 parameter I (shows the current limit as a
percentage of maximum). If applicable use service menu for setting.
•Increase set point, observe feeder, check running.
Attention
Please fasten the devices on a vibration-free underground and take care for sufficient air circulation.

Rhein-Nadel Automation GmbH 12
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
•Increase set point to maximum and check if power needs limiting (hammering). If necessary adjust the limit
as follows:-
•Adjust set point to zero
•Set parameter P (maximum limit) in Menu C096 to 50
•Adjust set point A to 100%.
•Increase the maximum limit P from 50% until the required amplitude is reached.
•The full set point range of 0…100% can now be used.
Additional settings e.g. soft start, time delays etc. can be set to suit the particular equipment.
Determining the output frequency (vibrating frequency)
It is essential that the output frequency is adjusted with the set point set at a low frequency, otherwise on hitting the
resonant frequency it is possible to achieve a high amplitude with a low output voltage. An analog, effective value,
current indicating unit (moving iron meter) must be connected into the output circuit. Resonant is reached when there
is a maximum amplitude for a minimum output current.
To achieve a stable feed system there must be an offset between the vibrating frequency and resonance
(approx. 1…2Hz). This offset must be determined by the user because different feeders have different running
characteristics.
9. Setting Instructions
9.1. User adjustment of throughput
Code C. 000
A further set point code can be found under C002
(for use in coarse/fine operation)
Feeder amplitude set point
0...100 %
Running mode
P P P
P
P P
P
P
P
P
Feeder amplitude set point
0...100 %
2nd Feeder amplitude set point
0...100%
(only if "SP.2. = I)
Running mode

Rhein-Nadel Automation GmbH 13
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
9.2. Tuning the feed system
9.2.1. Feeder settings
Code C. 020, 096
Setting the maximum limit
1. Adjust set point to zero
2. Set parameter P (maximum limit) to 50.
3. Adjust set point to 100%
4. Increase the limit P from 50% until the required amplitude is reached
5. The full set point range of 0…100% can now be used
Soft start 0...60
sssec. SecSek.
Soft stop 0...60
ds2ssSek.
Running
mode
P
P
P
P
P
P
P
P
P
P
P
P
F
Vibration frequency
[Hz]
Max. output 100...5
%

Rhein-Nadel Automation GmbH 14
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
9.2.2. Track control
9.2.3. Sensor time out
9.2.4. Set point source
Code C. 003
POT is not available on 16A units
On time delay 0...60 sec.
Off time delay 0...60 sec.
0 = No sensor inverting
I = Sensor inverting
Code C. 167, 007
0 = Sensor time out not active
I = Sensor time out active
E. = Sensor time out [sec.]
PP
P
P
P
P
P
P
P
P
F
Running mode
P
0 = Sensor time out not active
I = Sensor time out active
E. = Sensor time out [sec.]
P P
P
Code C. 015
P
Running mode
P
PAi. = switch off time air valve
0...60 Sec.
0 = Set point using display
I = External set point
0 = External set point 0...+10 V
I = External set point 4...20 mA
0 = Level sensor control
I = 2nd set point active
0 = Enable
I = Invert Enable
Running mode
P P P
P
P
P
P
P
P
F
0 = 0...10 V/ 0(4)...20 mA
I = Potentiometer
P

Rhein-Nadel Automation GmbH 15
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
Save new parameters
Running mode
P P
PP
PChoose user parameter set
9.2.5. Pulse feed
Code C. 004, 064
9.2.6. Determining the resonant frequency
Manual setting of the vibrating frequency
It is essential that the output frequency is adjusted with the set point set at a low frequency, otherwise on hitting the
resonant frequency it is possible to achieve a high amplitude with a low output voltage. An analog, effective value,
current indicating unit (moving iron meter) must be connected into the output circuit. Resonant frequency is reached
when there is a maximum amplitude for a minimum output current.
To achieve a stable feed system there must be an offset between the vibrating frequency and resonance
(approx. 1…2Hz). This offset must be determined by the user because different feeders have different running
characteristics.
9.2.7. Display actual current and frequency
Code C. 040
9.2.8. Save selected parameters
Code C. 143
Off time delay [sec.]
Invert hopper sensor
(not active)
Running mode
On time delay [sec.]
HOP. = 0 = continuous duty
HOP. = I = pulse feed
P
P
P
PP
P
P
P P
Running mode
P P
P
PActual current (display only)
PPActual frequency (display only)

Rhein-Nadel Automation GmbH 16
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
I = Hide menus
Running mode
P P
P
P
9.2.9. Recall user or factory settings
Code C. 210
9.2.10. Hide parameter menus
Code C. 117
Return to factory
settings
Return to user
settings
Running mode
PP
P
P
P
P
PPChoose user parameter set

Rhein-Nadel Automation GmbH 17
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
10. Error messages / ERROR reset
Errors are indicated by an alternating code and ERROR display
Overload limit
Output level exceeded e.g. incorrect frequency setting, coil air-
gap to wide.
Short circuit trip
Faulty coil, short circuit or defective cable.
Over voltage
Supply voltage too high or back EMF from the coil at lower
frequencies.
Current spike limit
Frequency set too low for installed coil or frequency altered too
rapidly during setting up.
Sensor fault (only when regulation mode is selected)
Accelerometer not working or faulty.
ERROR Reset through Menu C009
Sensor time out
After sensor time out has elapsed
ERROR Reset is achieved by pressing touch panel keys 0 or I during normal operation or by using Menu
C009.
In the event of an error check that this is not caused by incorrect wiring or cable faults. The error message, ERROR
ACC, can also occur if regulation mode is chosen (in Menu C008) and an accelerometer is not connected, for example.
Reset the error in the following manner:-
ERROR RESET
Frequently appearing Errors, which are not described in this chapter, should be reported to the manufacturer.
PP
Clear Error

Rhein-Nadel Automation GmbH 18
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
11. Connections for enclosed construction
Internal connections for 3A –8A units
When a potentiometer is connected parameter POT must be set to 1 in Menu C003.
The output cable to the feeder must be screened
to conform with EMC regulations.
0...10V
+
-
24V
25 26 2721 22 23 24 28 29
L
A2
A1
N
PE
PE
L,N,PE / 50/60Hz
5 6 7
1 2 3 4 8 9
E
ESA
10k
+
-
4...20mA
500R
+
+
-
-
+24V
+5V
PNP
Sensor
Coil
INPUT
GND
+24 V
SW...
31 3233 34 35 36 37
GND
+24 V
+24 V
Air valve
Time out
1 = A1
2 = A2
3 = Screen
4 = PE
1
2 3
PE
X4 Track sensor
socket
X40 Accelerometer
socket
X6 Enable input
socket
X5 Status output
socket
X1 Output Feeder
X0 Main supply
110 / 240 V,
50/60 Hz
1 = 24 V
3 = GND
4 = Input
12
34
1
2 3
PE
1 = 24 V
2 = Input
3 = GND
12
34
1 = 24 V
3 = GND
4 = Input
12
34
1 = L
2 = N
3 = nc
4 = PE
X7 Air valve
socket 1 = Output 24 V DC
3 = GND
12
34
1 =
4 =
12
34 3 = GND
5 = Time Out 24 V
5
X7
1
PE
2
3
1 2
34
5
1 2
34
1 2
34
1 2
34
1PE
23
X4
X40
X6
X5
X1
X0
1 2
34
1 = A1
2 = A2
3 = Screen
4 = PE
1
2 3
PE
X4 Track sensor
socket
X40 Accelerometer
socket
X6 Enable input
socket
X5 Status output
socket
X1 Output Feeder
X0 Main supply
110 / 240 V,
50/60 Hz
1 = 24 V
3 = GND
4 = Input
1 2
34
1
2 3
PE
1 = 24 V
2 = Input
3 = GND
1 2
34
1 = 24 V
3 = GND
4 = Input
1 2
34
1 = L
2 = N
3 = nc
4 = PE
1 =
4 =
1 2
34 3 = GND
5 = Time Out 24 V
5
1
PE
2
3
1 2
34
5
1 2
34
1 2
34
1 2
34
1PE
23
X4
X40
X6
X5
X1
X0
1 2
34
1 2
34
X4
X40
X1
X0

Rhein-Nadel Automation GmbH 19
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
11.1. Connections for enclosed construction
Internal connections for 12A unit
Track control sensor
Release
Set point (external)
GND +24 V
+24 V
Air valve
Time out
Status relay
Line input
110/240V
50/60Hz
Output
magnet
Accelerometer
56 7
1 2 3 4 8 9
E
+24V
E
S
A10k 0...10V 0(4)...20mA
+
+
-
-
7
8
7
8R=500 OHM
extern
+10V
12...24V, DC
+
-
4
5
21 22 23
55 54 53 52 51
27 26 29 28
25 24
INPUT
GND
+24 V SW...
31 32 33 34 35 36 37
L N A2 A1 PE PE PE PE PE PE PE
-
Line input
110/240 V
50/60 Hz
Output
feeder
L
N
A1
A2
4
1 = 24 V, DC
2 = Input
3 = GND
4 =
1 = 24V DC
2 =
3 = GND
4 = Input
12
3 4
12
3 4
X4
X40
X7
X6
X5
Output (X1)
1 = A1
2 = A2
= PE
21
21
X4
X40
X7
X6
X5
1
43
2
12
433
3
4
12
4
1 2
Sensor track control (X4)
Sensor accelerometer (X40)

Rhein-Nadel Automation GmbH 20
VT-BA-ESR-ESM3000-EN_2020 / 07.05.2020 SJ
12. Connections for 6 A panel mounting versions
Recommended method of terminating
screen of output cable
The output cable to the feeder must be screened to conform with EMC regulations.
When a potentiometer is connected parameter POT must be set to 1 in Menu C003..
O u tp u t c a b le
C o ntro l u n it
This manual suits for next models
4
Table of contents
Other RNA Controllers manuals