
16 EB 7030 EN
Design and principle of operation
5.2 Controller station
The controlled variable signal x produces a
deection on the bellows measuring system
of the controlled variable display (1.3) which
is transmitted to the pointer over a gear
mechanism.
The set point w can be adjusted at the scale
(1.2) on the front. The position of the set
point adjuster (1.4) is transmitted to the set
point calibrator over a gear mechanism.
This servo system (1.41) converts the adjust-
ed set point into a pneumatic set point signal
(w), which is fed to the controller module.
The controller module compares the con-
trolled variable signal and the set point sig-
nal (x and w) and produces an output signal
yA based on the system deviation and the
adjusted control parameters. The output sig-
nal is connected to the output pressure dis-
play (1.5) and output port y.
The controller station with manual/automatic
switchover (Fig.1 and Fig.3) additionally
contains a manual/automatic switch (1.6),
adjuster for manual mode (1.7) and differ-
ential pressure indicator (1.8).
When the switch is positioned in the AUTO-
MATIC mode, the output pressure display
(1.5) and output port y are connected to the
automatic output signal yA. In MANUAL
mode, the output pressure display and out-
put port y are connected to the manual out-
put signal yH set at the adjuster (1.7).
A bumpless switchover from manual to auto-
matic mode is possible when yAand yHare
the equal each other on the differential pres-
sure indicator (1.8).
5.3 Controller modules
The controller modules are plug-in units.
They are plugged into the self-sealing sockets
of the controller station and held by a fasten-
ing screw.
5.3.1 Type3433 Controller
Modules
The controller modules consist of a compara-
tor tted with four metal bellows arranged in
a square and a base plate with self-seal
push-on ttings. The base plate accommo-
dates the components required for the cho-
sen function, such as relays and restrictors.
The components can be exchanged or up-
graded, allowing the function to be changed
at a later point in time (see section9.1).
Type3433-2 PI Controller (Fig.6, top)
The controlled variable x and the set point w
are transferred as pneumatic signals be-
tween 0.2 and 1bar via turnboard A to the
metal bellows w and x. When x is greater
than w, the controlled variable bellows tilts
the pivoted swashplate toward the set point
bellows, causing the pressure downstream of
the nozzle connected to the swashplate over
a pin to rise. As a result, the output pressure
yA of the booster increases.
The output pressure is fed back via turn-
board B to the bellows R2 onto the swash-
plate.
The position of the swashplate and the out-
put pressure continue to change until the dis-
tance between nozzle and apper plate is
the same as initially and the output pressure