S&P PV-DEDPV User manual

MODEL PV-DEDPV
Dryer Exhaust Duct Power Ventilator
PVDEDPV_V.1_112020
INSTALLATION, OPERATION AND MAINTENANCE MANUAL

2
WARNINGS
READ AND SAVE THESE INSTRUCTIONS (LIRE AND CONSERVE INSTRUCTIONS). FAILURE TO
COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY
DAMAGE! IMPORTANT SAFETY INSTRUCTIONS (INSTRUCTIONS IMPORTANTES POUR LA
SÉCURITÉ) SAVE THESE INSTRUCTIONS (CONSERVEZ CES INSTRUCTIONS).
WARNING (AVERTISSEMENT): TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO
PERSONS, OBSERVE THE FOLLOWING (AVERTISSEMENT — POUR REDUIRE LE RISQUE D’INCENDIE,
DE CHOC ELECTRIQUE OU DE BLESSURE, RESPECTER LES CONSIGNES QUI SUIVENT):
(1) Your clothes dryer installation incorporates a dryer exhaust power ventilator (DEDPV) which may
be in a different location than your dryer, such as in an attic, crawl space or basement (Votre secheuse
est equipee d’un ventilateur auxiliaire qui peut etre installe loin de la secheuse, comme dans un grenier,
un vide sanitaire ou un sous-sol).
(2) Your clothes dryer depends on the DEDPV for its safe and efficient operation. Operating your dryer
without a functional DEDPV will result in inefficient dryer operation, excess energy consumption and a
possible fire hazard. See warning on the alarm notification panel (Le ventilateur auxiliaire est essentiel
au fonctionnement securitaire de la secheuse. Desactiver ce ventilateur nuira au fonctionnement de
la secheuse, entrainera un augmentation de la consummation d’electricite et possiblement un risque
d’incendie. Lire la mise en garde sur le panneau d’indication d’alarme).
(3) The notification/annunciator panel shall be permanently installed within the space in which the
clothes dryer is installed. In the case of a dryer installed in an alcove provided with a door or doors
the notification/annunciator panel shall be installed within the alcove or be installed immediately
adjacent to the doors of the alcove. The notification/annunciator panel shall be located where it
will be readily visible after the dryer is installed without having to open any doors other than those
necessary to access the dryer (Le panneau d’alarme doit etre installe de facon permanente dans
l’espace ou se trouve la secheuse. Si la secheuse est installee dans une alcove fermee par une porte,
le panneau d’alarme doit etre installe dans l’alcove ou a proximite immediate de la porte de l’alcove.
Le panneau d’alarme doit etre visible une fois la secheuse installee sans avoir a ouvrir une porte autre
que celle donnant acces a la Secheuse).
(4) LED Indicator Light: A flashing light or no light indicates failure of the DEDPV. Immediately stop
using clothes dryer until DEDPV has been serviced, repaired or replaced. A constantly illuminated light
indicates normal DEDPV operation.
(5)RISK OF FIRE. This Clothes Dryer installation includes a Dryer Exhaust Duct Power Ventilator
(DEDPV).
(6) NE PAS UTILISER LA SECHEUSE SI UNE ALARME RETENTIT OU UN MESSAGE D’ERREUR
VISUEL S’ALLUME. APPELEX UN REPARTEUR.
(7) RISQUE D’INCENDIE. CETTE SECHEUSE EST DOTEE D’UN VENTILATEUR AUXILIAIRE. UN
SIGNAL LUMINEUX CLIGNOTANT OU L’ABSENCE DE SIGNAL LUMINEUX INDIQUE UNE
DEFAILLANCE DU VENTILATEUR AUXILIAIRE. CESSER IMMEDIATEMENT D’UTILISER LA SECHEUSE
JUSQU’A CE QUE LE VENTILATEUR AIT ETE REPARE. UN SIGNAL LUMIINEUX PERMANENT
INDIQUE QUE LE VENTILATEUR AUXILIAIRE FONCTIONNE CORRECTEMENT. NE PAS RETIRER
NI COUVRIR CE PANNEAU.
(8) Use this unit only in the manner intended by the manufacturer. If you have questions, contact the
manufacturer.
(9) Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting
means to prevent power from being switched on accidentally. When the service disconnecting means
cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
(10) Installation work and electrical wiring must be done by qualified person(s) in accordance with all
applicable electrical and mechanical building codes and standards, including fire-rated construction.

3
Installation work and electrical wiring must be inspected and accepted by local authorities having
jurisdiction.
(11) Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney)
of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturer’s
guideline and safety standards such as those published by the National Fire Protection Association
(NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
(12) When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden
utilities.
(13) Ducted fans must always be vented to the outdoors.
(14) To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray,
construction duct, etc. off power unit.
(15) Not for Use in Kitchens.
CAUTION (ATTENTION):
(1) For General Ventilating Use Only. Do Not Use To Exhaust Hazardous Or Explosive Materials and
Vapors.
(2) Do not exhaust air in excess of 75 C(167 F).
(3) Do not install less than 5 linear feet (1.52 linear meters) or more than 40 linear feet (12.2 linear
meters) from clothes dryer exhaust outlet.
(4) A secondary lint trap must be installed between the clothes dryer and the (DEDPV) if the (DEDPV)
is located less than 15 linear feet (4.6 linear meters) from the exhaust of the clothes dryer.
(5) This fan is suitable for operation within indoor environments only.
(6) Do not install in an exhaust duct of a clothes dryer whose instructions prohibit the installation of a
clothes dryer (DEDPV) (NE PAS INSTALLER DANS LE CONDUIT D’EVACUATION DE LA SECHEUSE
SI LES INSTRUCTIONS INTERDISENT L’INSTALLATION D’UN VENTILATEUR AUXILIAIRE).
(7) Do not install in an exhaust duct where the equivalent duct length is < 25 feet (7.62 meters)
(NE PAS INSTALLER DANS UN CONDUIT D’EVACUATION MESURANT 7,62 METRES (25PI) DE
LONGUEUR OU MOINS.
(8) The PV-DEDPV is suitable to overcome a maximum equivalent duct length of 120 feet (36.58
meters) of 4 inch diameter galvanized steel duct, and to maintain an air velocity of 1200 fpm (6.10
m/s).
(9) The PV-DEDPV is suitable to overcome a minimum equivalent duct length of 30 feet (9.14 meters)
of 4 inch diameter galvanized steel duct, and to maintain an air velocity of 2200 fpm (11.2 m/s).
(10) The PV-DEDPV is suitable for use with gas or electric clothes dryers.
(11) Insulated dryer duct shall not be used upstream of the ventilator.
(12) The ventilator must NOT be used in conjunction with high output dryers.

4
PRE-INSTALLATION INSPECTION
The PV-DEPV has been manufactured in accordance with rigorous standards of production. All the
components have been checked and tested at the end of the manufacturing process. We recommend that
you check the following after receiving this product:
(1) The correct size has been received.
(2) The correct model has been received.
(3) The details on the rating label correspond to the electrical supply: voltage, frequency etc.
Remove the unit from packaging and inspect for shipping damage within FIVE (5) days of receipt. If
the product is found to be damaged, immediately contact your local authorized supplier. DO NOT
OPERATE THE UNIT IF DAMAGED. These instructions should be considered as a supplement to EPA
standard practices, as well as all state and local building code regulations.
Before installing the product check the following points:
(1) The fan impeller turns freely.
(2) There are no obstructions to the airflow.
ENVIRONMENT
The PV-DEDPV is suitable for operation within indoor environments only. It is suitable
for environments within the temperature ranges of -40°F up to +140°F (-40°C up
to +60°C).
FAN MOUNTING
Choose a mounting location which allows maintenance accessibility and ensure the
fan is oriented so that air flows in the correct direction (exhaust).
The PV-DEDPV must be mounted per the orientation diagrams below to ensure
proper operation. A robust mounting bracket is included and enables easy and
quick installation of the fan. Install headers (not included) between the joists if
necessary. Locate the fan so that the mounting bracket is centered on the headers or
joists and secure with properly sized screws (not included). A minimum of 2 screws
are required to mount the DEDPV.
#14 X 1/2 PHILLIPS PAN
HD TYPE A SCREW
WOOD SCREWS
BY OTHERS

5
DUCTING
All duct and duct termination
construction/location must comply
with local and national building
codes. The PV-DEDPV comes with (2)
8” long, 4” diameter duct cleanout
sections and (4) band clamps. Ensure
the duct system is designed for
these components for planning and
maintenance purposes.
Determine the total length of duct by
adding all of the straight pieces of
duct together (this includes all duct
between the dryer exhaust outlet and
the dryer vent cap). Then add 5 feet
for every 90 degree elbow/bend,
2.5 feet for every 45 degree elbow/
bend, and 5 feet for the dryer vent
cap to determine the total equivalent
duct length.
Example: The dryer exhaust system
consists of 50 feet of straight duct, 2
90 degree elbows, and 1 dryer vent cap.
50 feet of straight duct + [5 feet x 2 elbows (90 deg) = 10 equivalent feet] + 5 feet
for the dryer vent cap = 65 feet, total equivalent duct length
LINT TRAP
(OPTIONAL)
BAND CLAMPS
LED INDICATOR
LIGHT WALL
PLATE ASSEMBLY
LED INDICATOR LIGHT
50' COMMUNICATION
CABLE
6' POWER CORD
PRESSURE SENSOR TUBING
DUCT CLEANOUT SECTION
CLOTHES DRYER
90
ELBOW
MOUNTING JOIST
115V ELECTRIC OUTLET
WALL CAP (NO
SCREEN)
4” RIGID DUCT
90
ELBOW
DUCT CLEANOUT SECTION
FAN MOUNTING(CONT)

6
Ensure the total equivalent duct length is within the minimum and maximum allowable
values below.
•MINIMUM allowable equivalent duct length: 30 feet (9.14 meters)
•MAXIMUM allowable equivalent duct length: 120 ft (36.58 meters)
•Do NOT install the DEDPV less than 5 linear ft (1.52 linear meters) or more than 40
linear feet (12.2 linear meters) from clothes dryer exhaust outlet.
•A secondary lint trap MUST be installed between the clothes dryer and the DEDPV if
the DEDPV is located less than 15 linear feet (4.6 linear meters) from the clothes dryer
exhaust outlet.
•A secondary lint trap SHOULD be installed between the clothes dryer and the DEDPV
if the DEDPV is located less than 25 linear feet (7.6 linear meters) from the clothes
dryer exhaust outlet.
S&P recommends round 4” rigid duct for best air performance and code compliance.
Keep the length of duct and number of elbows to a minimum for best air performance.
Duct connections and penetrations should be sealed with duct tape, duct fast-clamps,
or caulk (available through your local distributor) to create an air-tight path from the
clothes dryer to the building exterior.
Connect the duct to the fan with the provided band clamps and rated tape as necessary.
Do NOT use screws to connect the duct and fan. Ensure that the outlet duct is properly
connected to a properly sized, low restriction dryer vent cap with weather hood and
backdraft damper. Dryer vent caps shall NOT include a screen as this will cause lint
buildup and fan blockage.
Drill a 3/8” hole in the duct adjacent to the fan (4-5”) between the fan inlet and the
clothes dryer. Insert the provided grommet taking care to avoid burrs. Connect one end
of the 1/4" OD clear tubing to the pressure sensor on the fan housing and insert the other
end into the grommet.
A
DETAIL A
CC
SECTION C-C
A
DETAIL A
CC
SECTION C-C

7
WIRING
CAUTION: Ensure that power is turned off and locked out before making any wiring
connections. The PV-DEDPV operates on a standard 120V 50/60Hz AC electrical supply.
All wiring must be carried out by a qualified electrician in accordance with National
Electrical Code and all applicable state and local buildings codes. Electrical connections
are made at the factory per the wiring diagram below.
The PV-DEDPV is provided with a factory-wired 6’ power cord and ready to be plugged
into a standard 120V receptacle. The unit is provided with a LED indicator light panel and
50 feet of 2-wire communication cable. Connect the communication cable plug to the
DEDPV control board and route the cable from the unit to the LED indicator light panel
mounting location (in the laundry room).
S
&
P
PV-DEDPV WIRING DIAGRAM
GREEN WITH
YELLOW STRIPE
WHITE
NOTES:
INSTALL WIRE NUTS ON ALL NOT USED WIRE LEADS.
1.
LEADS CAN BE CUT TO LENGTH AS NEEDED.
2.
FAN MOTOR
RED
LED
TUBING
ORANGE
BLUE
BLACK
BROWN
GREEN
WHITE
BLACK
YELLOW
YELLOW
115V
NEUTRAL
SCALE: 1:1
DO NOT SCALE DRAWING
UNLESS OTHERWISE SPECIFIED DIMENSIONS
ARE IN INCHES TOLERANCES ARE
DRAWN BY
--/--/--
SHEET
08/06/18
XX ± .03
REV.
B
DATE
± 1°
ANGLES
---
SIZE
FRACTIONS
1 OF 1
XXX ± .005
MATERIAL
NT
APPROVALS
CHECKED BY
± 1/16
DECIMALS
REV
REVISIONS
DATE
--
1
ECN
BY
DESCRIPTION
CAD FILE
--
SH.
---
-----------------------------
-------
08/06/18
PART NO.
Soler & Palau USA
-----------------------------
--/--/--
-------
--/--/--
-------
---
NT
RELEASE FOR MANUFACTURING
JACKSONVILLE, FLORIDA
A
THIRD ANGLE
PROJECTION
ESTIMATED WEIGHT(LB)
PROJECT NO.
EST. SHIPPING DIMS (INCH)
Terminal Description
R Fan Motor Capacitor
M Fan Motor Capacitor / Fan Power
TH2 Temperature Sensor Lead 2
TH1 Temperature Sensor Lead 1
L Voltage Hot (120Vac)
N1 Voltage Neutral (120Vac)
N2 Fan Motor Neutral
H1 Hall Sensor Voltage
H2 Hall Sensor Signal Output
H3 Hall Sensor Ground

8
OPERATION
The PV-DEDPV is a pressure sensing fan and operates automatically once positive pressure
(0.08” w.g. from the clothes dryer) is sensed for more than 10 seconds. Once activated,
the DEDPV will continue operating until positive pressure from the clothes dryer is no
longer present. The DEDPV will then continue operating for 5 minutes in a “cool down”
period. The ventilator includes a “one shot” thermal fuse (196 F, 91 C) located inside the
fan to immediately shut off power to the motor in case of a dryer fire. The PV-DEDPV is
equipped with a low voltage LED indicator light panel. This panel indicates whether the
fan is operating correctly. Ensure that the panel is connected to the fan PCB with the 50’
of communication wire provided. See table below for fan operation indicators. If further
assistance is required, please contact our Support Services department.
WARNING: A flashing red light or no light indicates failure of the DEDPV. Immediately
stop using clothes dryer until DEDPV has been serviced, repaired or replaced. A constantly
illuminated green light indicates normal DEDPV operation.
Mount the LED indicator light panel in the 2 gang wall plate provided and mount the wall
plate so that it can be seen in the dryer area (refer to page 5-7 for mounting location
requirements). Ensure the wiring connections are correct. The panel can be mounted
directly to the wall. Ensure that the WARNING label is applied to the open area on the
wall plate.
LED Color LED Light Function Fan Operation
Green Solid Normal operation
Red Flashing, once every 5 seconds
Fan speed is below normal indicating
possible lint buildup causing the impel-
ler to drag. Inspect the fan immediately.
Red Flashing, twice every 5 seconds
Fan speed is above normal indicat-
ing possible duct blockage due to lint
buildup. Inspect the fan and duct system
immediately.
Red Flashing, three times every 5 seconds
Fan speed is zero indicating a locked
rotor condition. Inspect the fan im-
mediately.
Red Flashing, once every 1 second
Fan temperature has exceeded the max
allowable temperature (196 F, 91 C),
removing the electrical power supply
to the fan permanently. Inspect the fan,
duct system, and dryer immediately.
Replace thermal fuse.
CONNECT COMMUNICATION
CABLE TO FAN CONTROL BOARD
APPLY WARNING
LABEL HERE

9
MAINTENANCE
CAUTION: BEFORE CARRYING OUT ANY MAINTENANCE OR SERVICING, ENSURE THE
UNIT IS DISCONNECTED FROM THE MAIN ELECTRICAL SUPPLY.
All PV-DEDPV fans incorporate sealed for life bearings and therefore do not require any
lubrication. S&P recommends inspection of the fan at least once every six (6) months
to avoid excessive accumulation of lint, duct, or dirt on the impeller, but this can vary
depending on clothes dryer usage. To inspect and maintain/clean the unit disconnect
from the electrical supply. Loosen the band clamps and remove the fan from the duct.
Compressed air or a vacuum can be used to remove any lint buildup from the fan. If any
debris is evident on the impeller clean with a damp (not wet) cloth. DO NOT USE any
detergents or abrasive materials for cleaning. Reinstall the fan and tighten the band
clamps, ensuring the fan is properly oriented and the duct connections are sealed.
EXPLODED VIEW
WARRANTY
S&P USA - S&P Canada warrant that the PV-DEDPV fan will be free from defective
materials and workmanship for the period of (5) years from the date of original purchase.
In the event that we find any part is defective the product will be repaired or, in the
Company’s discretion, replaced without charge provided that the product has been
installed in accordance with the enclosed instructions and all applicable EPA Standards
and state and local building codes.
BAND CLAMP
DUCT CLEANOUT
SECTION
BAND CLAMP
BAND CLAMP
BAND CLAMP
DUCT CLEANOUT
SECTION
PRESSURE SENSOR
TUBING
MOUNTING BRACKET
LED INDICATOR
LIGHT WALL PLATE
ASSEMBLY
6' POWER CORD
CONTROL BOARD ASSEMBLY
FAN ASSEMBLY
THERMAL FUSE
LED INDICATOR
LIGHT 50'
COMMUNICATION
CABLE

IF CLAIMING UNDER WARRANTY: Please return the complete product, freight
paid, to your local authorized distributor. All returns must be accompanied by a
valid Bill Of Sale. All returns must be clearly marked “Warranty Claim,” with an
accompanying description stating the nature of the fault.
THE FOLLOWING WARRANTIES DO NO APPLY: Damages from shipping, either
concealed or visible. Claim must be filed with the carrier. Damages resulting from
improper wiring or installation Damages caused by acts of nature, or resulting from
improper consumer procedures such as: Improper Maintenance; Misuse; Negligence;
Alteration; Abuse; Abnormal Use; or Accident or Incorrect Electrical Voltage and
Current. Removal or alteration to the S&P USA - S&P Canada data plate label.
WARRANTY VALIDATION: The end user must keep a copy of the Bill of Sale to verify
purchase date.
THE ABOVE (5) YEAR WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER
WARRANTIES, EXPRESSED, WRITTEN OR IMPLIED, INCLUDING THE WARRANTIES
OF MERCHANTABILITY AND FITNESS FOR USE. IN NO EVENT SHALL Soler & Palau
USA - Soler & Palau CANADA
BE LIABLE FOR ANY SPECIAL, CONSEQUENTIAL, OR INCIDENTAL DAMAGES,
INCLUDING LOSS OF PROPERTY, REVENUES, LOST PROFITS, COSTS OF REMOVAL,
INSTALLATION OR REINSTALLATION
Table of contents
Other S&P Fan manuals

S&P
S&P PCD110 User manual

S&P
S&P TURBO-351 N User manual

S&P
S&P CUL507-18 User manual

S&P
S&P METEOR NT User manual

S&P
S&P ARTIC TOWER M Technical Document

S&P
S&P EDM-80N User manual

S&P
S&P Silent-200 CZ Gold User manual

S&P
S&P HTB-140 Technical Document

S&P
S&P TH MIXVENT Series User manual

S&P
S&P LPD User manual
Popular Fan manuals by other brands

Prominence Home
Prominence Home Hero 51655 owner's manual

Flexit
Flexit Roomie Dual Assembly and operation instructions

Klarstein
Klarstein Standventilator manual

NuAire
NuAire DRI-ECO-HEAT-HC Installation and Maintenance

zenta
zenta RINZLER CSF5610 Assembly and installation instructions

Flex-a-Lite
Flex-a-Lite 10 installation instructions