Fire damper BKA-EN
Technical documentation
Description
Construction subject to change
No return possible Version: 2020-07-10 | Page 3
DESCRIPTION
Fire dampers built into ventilation ducts (air-conditioning
systems) are used for the automatic locking of fire lobbies.
The fire damper BKA-EN conforms to EN 15650, EN 13501-3
and EN 1366-2.
The BKA-EN has been tested in compliance with EN 1366-2 ac-
cording to the Declaration of performance no.
DoP-BKA-EN-2020-07-10. Its classification according to EN
13501-3 is EI 30 (ve, i↔o) S to EI 90 (ve, ho i↔o) S.
According to Directive 2014/34/EU, EC Certificate of Confor-
mity number EPS 09 ATEX 2 153 X, its use in areas subject to
explosion hazards is permitted, not only with spring return ac-
tuator ExMax-5.10-BF (X10 - X15), including safety tempera-
ture limiter (FireSafe or ExPro-TT), but also with mechanical
trigger via fusible link (manual actuation with or without ATEX
limit switch ES-Ex). The fire damper is marked as follows ac-
cording to ATEX:
*) when using the safety temperature limiter FireSafe.
The national standards and guidelines must be observed in
connection with this technical documentation "Installation,
mounting and operating instructions". Further information on
ATEX can be found in the additional BKA-EN operating in-
structions according to ATEX 2014/34/EU.
For functional tests, service, retrofitting, etc., inspection ope-
nings must be provided on site in suspended ceilings, shaft
walls, connected ventilation ducts, etc., if necessary. They
must be built in in sufficient numbers and sizes and must not
impair the functioning of the fire dampers.
The fire dampers must be connected to the ventilation system
by means of ventilation ducts either on one or on both sides.
When connected on one side, finishing protective gratings
made of non-flammable building materials (EN13501-1) must
be provided on the opposite side.
The fire dampers can be connected to non-flammable and
flammable ventilation ducts as well as to flexible spigots.
Housing made of galvanised sheet steel (standard)
optionally (at an extra charge):
Housing from stainless steel material no. 1.4301 or 1.4571 (re-
placeable, non-coated parts are made of stainless steel mate-
rial no. 1.4301)
Housing with DD coating (two-component top coat based on
polyurethane varnish) inside or inside and outside (replace-
able, non-coated parts and the U-profile of the damper blade
are made of stainless steel material no. 1.4301)
Moulded connection flanges with centre hole, corner angle
with long hole for simple duct mounting and high stability
Thermal insulation made of silicate boards
Damper blade made of glass-fibre-reinforced abrasion-re-
sistant lightweight concrete
Optionally (at an extra charge): damper blade lined with sheet
steel (galvanised) / DD coating (RAL 7035 / light-grey)
Cold and hot leakage requirements according to EN 1366-
2 are met by means of circumferential rubber and intu-
mescent seals.
Horizontal or vertical position of the damper blade axle
(depending on the mounting situation).
The installation position is independent of the air flow di-
rection.
Thermal trigger via fusible link 72°C or 98°C
Optionally (at an extra charge) by means of electrical,
magnetic or pneumatic release devices
with two inspection openings on opposite sides
Use: max. operating pressure of 1000 Pa at vstirn ≤ 10 m/s
Housing leakage according to EN 1751 class B
Use or connection of a smoke trigger device with general
building supervisory approval (e.g. SCHAKO smoke detec-
tion system RMS, see technical documentation smoke de-
tection system RMS) in connection with suitable electric,
magnetic (magnetic clamp) or pneumatic release devices
of the fire damper is possible; only release devices work-
ing by the "currentless closed/depressurised open" prin-
ciple may be connected to the RMS system; the propaga-
tion of fire and smoke is effectively prevented. Optimal
integration into the building control system by means of
the SCHAKO EasyBus signalling and switching bus system
(see technical documentation EasyBus) or the SCHAKO
fire damper mini-controller BKSYS (see technical docu-
mentation BKSYS).
Attention
Building systems have to be arranged, installed, changed and
maintained in such a way that they prevent fire and propaga-
tion of fire and smoke (fire propagation) and allow evacuation
of people and animals as well as efficient fire extinguishing
work.
Smoke propagation through the air-conditioning and ventila-
tion system can be prevented for example by means of fire
dampers and spring return actuators in combination with ap-
proved smoke detector devices (e.g. SCHAKO smoke detec-
tion system RMS).
II 2 G Ex h IIC T6 Gb
II 2 D Ex h IIIC T80°C Db
II 3 D Ex h IIIC T80°C Dc
*)
EPS 09 ATEX 2 153 X