manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Mandik
  6. •
  7. Fire And Smoke Damper
  8. •
  9. Mandik FDMS User manual

Mandik FDMS User manual

2
These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) FDMS / FDSM-VAV.
It is valid for production, designing, ordering, delivery, assembly and operation.
In case of products with "P-mark" certification from RISE Institute in Sweden these technical specifications must be meet in
addition to the standard design:
■In addition to activation by means of thermal fuses or links in the actuator, the damper must also be activated by smoke
detectors and/or heat detectors that have been installed in suitable positions.
■The smoke and heat detectors used together with the fire damper must be designated and constructed in accordance with
one of the following standards EN 54-5, EN 54-7, EN 54-12 or EN 54-20.
■The damper must be controlled by an actuator connected to a higher-level supervisory and constrol system.
■Correct operation of the damper must be verified by automatic testing of its function at least once per 48 hours.
After reaching o these requirements the product will be provided with this certificate:
■Certified body - RISE Certifiering.
■Number of the certificate - SC1433-17.
Description........................................................................................................................................................
3
Damper design FDMS.......................................................................................................................................
4
Damper design FDMS-VAV...............................................................................................................................
9
Dimensions and weights of FDMS.....................................................................................................................
13
Dimensions and weights of FDMS-VAV.............................................................................................................
14
Placement and assembly..................................................................................................................................
15
Installations opening.........................................................................................................................................
16
Statement of installation....................................................................................................................................
16
Descriptions of particular installations...............................................................................................................
17
Pressure loss....................................................................................................................................................
28
Pressure loss....................................................................................................................................................
29
Air volume flow..................................................................................................................................................
29
Operating mode and setup................................................................................................................................
30
Noise data FDMS / FDMS-VAV.........................................................................................................................
31
Entry into service and revisions........................................................................…..............................................
36
3
Fire dampers are shutters in ventilation duct systems that preventing spreading the fire and combustion gases from one fire compartment
to the other one by shutting of closing the air duct in the positions of fire separating constructions. In the case of FDMS the fire dampers
blade closes automatically air duct using a shutting spring or an return spring of its actuating mechanism in case of fire. In the case of
FDMS-VAV the fire damper has an additional function of the variable air flow controller. The return spring of the actuator is started when
the thermal fuse is activated or the actuator is without power supply. In the case of thermal electrical fuse the activation (closing)
procedure starts, when a reset button on fuse is pushed or when a power supply of the actuating mechanism is stopped. In case FDMS
of mechanical control with thermal fuse, the return spring is activated after the moment, when thermal fuse is melted. The damper´s blade
is sealed with a silicon gasket/packing preventing smoke penetration after closing the blade. At the same time, the damper´s blade will
be tighten by intumescent tape, which will be expanding in the case of fire. Dampers have no inspection door. For inspection of the
damper, there is an inspection hole for camera. For others service works there must by installed inspection door externally on the duct,
next to the fire damper. The damper is equipped with additional collar, around the position of the blade. On the collar, there are positioned
several metallic plates (fixtures for easy installation on the wall or ceiling construction.
■CE certified acc. to EN 15650
■Tested in accordance with EN 1366-2
■Classified acc. to EN 13501-3+A1
■Fire resistance EIS 45, EIS 60, EIS 90
■External casing leakage class min. C, internal leakage class 2 acc. EN 1751
■In case of FDMS cycling test in class C 10 000 acc. to EN 15650.
■In case of FDMS-VAV cycling test in class C 20 000 acc. to EN 15650 - CMOD classification
■Corrosion resistant acc. to EN 15650
■ES Certificate of conformity No. 1391-CPR-2020/0131
■Declaration of performance No. PM/FDMS/01/20/2, PM/FDMS-VAV/01/20/2
■Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19b
Fire damper´s proper functioning is determined by the following working conditions:
■Maximum air speed: 12m/s.
■Maximum pressure difference: 2500 Pa.
■Operation of the dampers does not depend on the direction of air-flow (circulation). In case of FDMS-VAV the direction of
air-flow is strictly given.
■FDMS can be located in any (arbitrary) position.
■Dampers are suitable for ventilation air systems not containing any abrasive, chemical and adhesive particles.
■Dampers are designed for macroclimatic areas with mild climate according to EN 60721-3-3.
■Temperature in the place of installation is permitted to be in the range from -30°C to +50°C.
4
Design with mechanical control with a thermal protective fuse which actuates the shutting device within 120 seconds, when the
nominal temperature reaches 72°C. Automatic initiation of the shutting device is not activated if the temperature does not exceed 70°C.
Design with mechanical control can be complemented with a limit switch signaling the damper´s blade position "CLOSED". Limit switch
is possible connect to the building management system or superordinate control system by wires, which are mounted to the switch.
Design with mechanical control can be complemented with a limit switch signaling the damper´s blade position "CLOSED". Limit switch
is possible connect to the building management system or superordinate control system by wires, which are mounted to the switch.
AC 230V / 5A
IP 67
-25°C … +120°C
1(COM) - black wire
2(NC) - gray wire
4(NO) - blue wire
This limit switch is possible to connect in following two versions:
a) if the arm is moving … connect wire 1+2
b) if the arm is moving … connect wire 1+4
5
The damper can be equipped with electric actuating mechanism. There are several actuators: BELIMO BFL, BFN 230-T (version .40)
or BFL, BFN 24-T (version .50). After connection to the power supply AC/DC 24V or AC230V, the actuating mechanism displaces the
damper blade into operation position "OPEN". At the same time is pre-stretched back spring inside the actuator. When the actuator is
under voltage (on power supply), the damper´s blade is in the position "OPEN". The back spring is pre-stretched. Time needed for full
opening of the damper blade from the position "CLOSED" to the position "OPEN" is maximum 60s. If the power supply of the actuator
is cut off (due to disconnection of power supply, or pressing the reset button on the thermo-electrical starting mechanism BAT (thermal
fuse), the back spring displaces the damper´s blade into the safety position "CLOSED". The time needed for displacing of the blade
from the position "OPEN" to the position "CLOSE" takes maximal 20s. In the case that the power supply is restored again (the blade
can be in arbitrary position), the actuator starts re-displacing the damper´s blade position into the emergency position "OPEN". The
thermos-electrical mechanism BAT, which contains two thermal fuses Tf1 and Tf2, is a part of actuator. These fuses are activated
when temperature +72°C has been exceeded. The fuse Tf1 measures the temperature in the outside of the damper and Tf2 measure
the temperature inside the air duct. Both fuses, they are in serial connection. It means in fact, that when one of them is activated, the
power supply of the actuator is cut-off and the actuator displaces the blade in safety position "CLOSED". The signalization of damper
position "OPEN" or "CLOSED" is provided by two limit switches, which are built-in inside the actuator. The thermal fuse BAT can be
also installed separately, into the spiral air duct, outside of the fire damper (order code for this option is .4V or .5V - see the product
code).
12 S3
S1 S2 S5S4 S6
NL1
<5° <80°
BAT
Tf Tf LED
12 S3
S1 S2 S5S4 S6
<5° <80°
BAT
Tf Tf LED
~
- +
6
AC 230 V 50/60 Hz AC 24 V 50/60 Hz
DC 24 V
- motoring
- holding
3,5/5 W
1,1/2,1 W
2,5/4 W
0,8/1,4 W
6,5/10 VA (Imax 4 A @ 5 ms) 4/6 VA (Imax 8,3 A @ 5 ms)
II III
IP 54
- motor
- spring return
<60 s
~ 20 s
- normal duty
- safety duty
- non-operating temperature
- 30 °C … 55 °C
The safe position will be attained up to max. 75°C
- 40 °C … 55 °C
- motor
- auxiliary switch
cable 1 m, 2 x 0,75 mm² (BFL/BFN 24-T-ST) with 3-pin plug-in connectors
cable 1 m, 6 x 0,75 mm² (BFL/BFN 24-T-ST) with 6-pin plug-in connectors
duct outside temperature 72 °C
duct inside temperature 72 °C
This is design with the communication and supply device BKN230-24 and the actuator BFL (BFN) 24-T-ST. It simplifies electrical wiring
and interconnection of fire damper. This design facilitates checking of the damper on site and enables central control and check of fire
damper during by a simple "2-wire" wiring with superordinate control unit. BKN230-24 is working as a decentralized network device
for supplying of the actuator BFL (BFN) 24-T-ST on one hand and on the other hand it transmits the signal information about the fire
damper position and failure. Control command SWITCH-ON and SWITCH-OFF from superordinate system controls via the same
wiring to the actuating mechanism. To allow more simple connection, the actuator BFL (BFN) 24-T-ST is equipped with two connecting
plugs (one with three jacks and one plug with six jacks). They are inserted directly to BKN230-24. BKN230-24 is supplied with a
conductor and EURO-plug for connecting to the 230V mains. Two wire cable from superordinate system is connected to BKN230-24
by means of clamps 6 and 7 in BKN. If the drive is supposed to be controlled without any signal from the superordinate, it can be
switch-on by means of a bridge between clamps 3 and 4 in BKN. A green LED diode on BKN230-24 is lighting in case the voltage 24V
is present in the drive. If the TEST button on BAT is switched-on or if the power supply (e.g. by a signal from ELECTRICAL FIRE
SIGNALISATION) is disconnected, the fire damper position will be "FAILURE". It means damper blade goes in position "CLOSED".
Communication and supply device BKN230-24 has to be placed near the damper (BKN isn´t mounted on damper body). It is necessary
for easy connection of actuator equipped by BKN230-24 device.
AC 230V 50/60Hz
3,5 W (operating position)
11 VA (including actuating mechanism)
II
IP 42
- 30 °C … + 50 °C
- 40 °C … + 50 °C
- mains
- drive
- terminal board
Cable 0,9 m with EURO plug of 26 type
6 pole plug, 3 pole plug
screw terminals for conductor 2x1,5 mm
7
Current Failure 15 16 K2 contact is on if all the dampers are
open 14 11
17 18
No Failure 15 16
K2 contact is on if the damper No. 1 is
open 14 12
K2 contact is on if all the dampers are
closed 14 open
BKS24-9A communication and control device is used for group control and checks of 1 to 9 fire dampers with the actuator BFL
(BFN)24-T-ST in connection with the supply and communication device BKN230-24. Signalization of the damper blade position
is individual for each damper (9 LED diodes), but the dampers can be controlled and tested only as a group. BKS24-9A is intended
for use in superordinate control system, which can display operation mode and failure reports of the connected fire dampers.
BKS24-9A receives signals from BKN230-24 through two wire cable. Proper damper operation is indicated by two light LED diodes:
Control LED "OPEN" = damper blade in emergency position OPEN
Control LED "CLOSE" = damper blade in safety position CLOSED
If the damper does not reach the required position within the preset time, the appropriate on-board FAULT LED flashes and, at
the same time, the fault contact K1 is activated (K1 is group alarm for all 9 dampers). This contact is overridden as soon the
defective damper reaches the required position. The on-board FAULT LED remains on, until the fault is reset. Auxiliary contact
K2 is provided for signaling the positions of dampers to a supreme communication controlling system. The function of the auxiliary
contact can be programmed via terminal 14 according the next table.
The BKS24-9A unit can be clipped directly onto a 35mm DIN mounting rail and external wiring is connected by two 9-pin terminal
connectors.
Functional testing can be performed by pressing the TEST pushbutton. While this button is held depressed, the dampers run to
the safe position. Any malfunctions are indicated by the internal FAULT LED´s.
1
2
3
4
5
6
7b
a
1)1)
2)
BAT
1) Bridge has been installed by the manufacturer. If needed, it can be
removed ad replaced with a thermoelectric starting mechanism. If
terminals 1 and 2 are not interconnected, safety function is initiated.
2) Bridge can be used only for starting and without BKS24… !
Two conductor wiring to BKS24
8
AC 24 V 50/60Hz
3,5 W (operating position)
5,5 VA
III (safe small voltage)
IP 30
0 … + 50 °C
Terminals for conductor 2 x 1,5 mm
9
The damper is equipped with electric actuating mechanism. There are several actuators depending on the damper size: GRUNER
340CTA-024D-XX-S2-V/8F12/ST06/BP8. To ensure the VAV function there is an Gruner universal actuator controller GUAC-DM3
for air flow control and GUAC-PM3 for pressure control. After connection to the power supply AC/DC 24V, the actuating
mechanism displaces the damper blade into operation position given by the required air volume flow. At the same time is
pre-stretched back spring inside the actuator. When the actuator is under voltage (on power supply), the damper´s blade is in the
position given by the required air volume flow. The back spring is pre-stretched. If the power supply of the actuator is cut off (due
to disconnection of power supply, or pressing the reset button on the thermo-electrical starting mechanism BAT (thermal fuse),
the back spring displaces the damper´s blade into the safety position "CLOSED". The time needed for displacing of the blade from
the position "OPEN" to the position "CLOSE" takes maximal 20s. In the case that the power supply is restored again (the blade
can be in arbitrary position), the actuator starts re-displacing the damper´s blade position given by the required air volume flow.
The thermos-electrical mechanism BAT, which contains two thermal fuses Tf1 and Tf2, is a part of actuator. These fuses are
activated when temperature +72°C has been exceeded. The fuse Tf1 measures the temperature in the outside of the damper and
Tf2 measure the temperature inside the air duct. Both fuses, they are in serial connection. It means in fact, that when one of them
is activated, the power supply of the actuator is cut-off and the actuator displaces the blade in safety position "CLOSED". The
signalization of damper position "OPEN" or "CLOSED" is provided by two limit switches, which are built-in inside the actuator. The
fire damper has a part with controller consists of the body of the controller with a control blade and pressure probes for determining
the through-flow of air. A controller is affixed to the body for controlling the control blade, which is in this case the blade of the fire
damper.
10
●Connect via safety isolation transformer!
●The device is not allowed to be used outside the specified field of application.
●It may only be installed by suitably trained personnel. Any legal regulations or
regulations issued by authorities must be observed during assembly.
BU = blue
BN = brown
BK = black
GY = Gray
~
YU
safety transformer
AC 24 V
DC 24 V
~
~
Y/Z U/PP
CAV-modes
(Default)
BU BN BK GY
U
DC 0...10 V
DC 2...10 V
open*
Vmax
closed*
Y
DC 0...10 V
DC 2...10 V
Vmin
2...10 V-close
0...10 V-close if Vmin=0
●Connect via safety isolation transformer!
●The device is not allowed to be used outside the specified field of application.
●It may only be installed by suitably trained personnel. Any legal regulations or
regulations issued by authorities must be observed during assembly.
BU = blue
BN = brown
BK = black
GY = Gray
~
YU
safety transformer
AC 24 V
DC 24 V
~
~
Y/Z U/PP
CAP-modes
(Default)
BU BN BK GY
U
DC 0...10 V
DC 2...10 V
open*
Pmax
closed*
Y
DC 0...10 V
DC 2...10 V
Pmin
2...10 V-close
0...10 V-close if Vmin=0
~
12
TA 72
TF1 TF2
LED
test
>80°
>5°
123456
S1 S2
WH WH WH WH WH WH
BU BN
●Connect through separating transformer!
●Parallel connection of other servo drives is possible. Respect power input data.
●Combination of mains voltage and use of signals from limit switches by very low
voltage is not allowed.
BU1 = blue
BN2 = brown
WH1 = white
WH2 = white
WH3 = white
WH4 = white
WH5 = white
WH6 = white
11
24V AC/DC 50/60 Hz
0,6 W
1,3 VA
III
IP 42
(0)2...10 VDC / Ri > (100 kΩ) 50 kΩ
(0)4...20 mA / Rext. = 500 Ω
(0)2...10 VDC, max. 0,5 mA
closed / Pmin / Pmax / open
- normal duty
- storage temperature
0 °C … +50 °C
-20 °C … +80 °C
- controller
- actuators screw terminals, 4-pin, 0,5...2,5 mm²
cable 1000 mm with Lumberg connector
via diagnostic connector and feedback signal U/PP
300 Pa (static)
PP-Bus (1200 Bd, max. 15 VDC)
24V AC/DC 50/60 Hz
0,6 W
1,3 VA
III
IP 42
(0)2...10 VDC / Ri > (100 kΩ) 50 kΩ
(0)4...20 mA / Rext. = 500 Ω
(0)2...10 VDC, max. 0,5 mA
closed / Vmin / Vmax / open
- normal duty
- storage temperature
0 °C … +50 °C
-20 °C … +80 °C
- controller
- actuators screw terminals, 4-pin, 0,5...2,5 mm²
cable 1000 mm with Lumberg connector
via diagnostic connector and feedback signal U/PP
300 Pa (dynamic)
PP-Bus (1200 Bd, max. 15 VDC)
24V AC/DC 50/60 Hz
- motoring
- holding
6,5 W
2,0 W
7,5 VA
III
IP 54
- motor
- spring return
< 100 s
< 20 s
- normal duty
- safety duty
- non-operating temperature
-30 °C … +50 °C
> +75°C
-30 °C … +50 °C
- motor
- auxiliary switch
cable 1 m, 2 x 0,75 mm²
cable 1 m, 6 x 0,75 mm²
TF1 temperature inside Duct +72 °C
TF2 temperature outside Duct +71 °C
12
Actuating mechanism
flow direction
∆p [ Pa ] - controller pressure loss
∆p
GUAC-DM3
Actuating mechanism
flow direction
Controller GUAC-PM3
∆p [ Pa ] - Static pressure difference between
∆p
duct and surrounding environment
s
s
air outlet
Room
Actuating mechanism
Controller GUAC-PM3
∆p [ Pa ] - Static pressure difference between
room and surrounding environment
s
∆ps
13
= for the actuator - BFL 86mm, BFN 110mm
= the height of the actuator - BFL 48mm, BFN 52mm
2,2 2,6 3,2 3,6 4 4,5 5,1 5,8
–
6,7 7,7 9 10,4 12 14,1 16,7 –
3,3 3,7 4,3 4,7 5,1 5,6 6,2 6,9
–
7,8 8,8 10,1 11,5 13,4 15,5 18,1 –
BFL24-T(-ST), BFL230-T 100, 125, 160, 180, 200, 225, 250, 280, 315, 355, 400, 450
BFN24-T(-ST), BFN230-T 500, 560, 630
98 190 – – – 113 313 405 – 12 70 163
123 215 – – – 113 353 445 2 32 90 163
158 250 – – – 113 398 490 24,5 54,5 112,5 163
178 270 – – 2,5 113 448 540 49,5 79,5 137,5 163
198 290 – – 12,5 113 498 590 74,5 104,5 162,5 163
223 315 – – 25 163 558 650 104,5 134,5 192,5 163
248 340 – – 37,5 163 628 720 139,5 169,5 227,5 163
278 370 – – 52,5 163 – – – – – – –
øD
p
222
50 5041
øD 69
øD1
70
øD
146
250
50 5041
øD 54
øD1
A
B 7
caM
caS
14
50
50
41
575
146
125
D
D1
Ø
Ø
2 x D
Ø
min.
2 x D
Ø
min.
C
15
Fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages of fire separating constructions.
Damper assembly procedures must be done so as all load transfer from the fire separating constructions to the damper body is
absolutely excluded. Back-to-back air-ducting must be hung or supported so as all load transfer from the back-to-back piping to
the damper is absolutely excluded. Installation gap must be filled by approved material perfectly in all the installation space volume
(installation gap). To be able to provide inspection, inside of the fire damper is the damper with camera inspection hole standardly
equipped. For other service works, the external access door (inspection hole) must be installed on the air duct, next to the fire
damper.
The distance between the fire damper and the construction (wall, ceiling) must be minimum 75 mm. In case that two or more
dampers are supposed to be installed in one fire separating construction, the distance between the adjacent dampers must be at
least 200 mm according to EN 1366-2 paragraph 13.6.
The control mechanism has to be protected (covered) against damage and pollution during installation process. All fire dampers
has to be closed during installation process. The damper body should not be deformed in the course of bricking in. Once the
damper is built in, its blade should not grind on the damper body during opening or closing.
Collar
* Other values - see the installation details for installation
flange to flange and next to ceiling or/and wall.
4,3 4,8 5,6 6,1 6,6 7,3 8,1 9,1
–
10,9 11,5 14,1 17,3 20,1 23,5 28,9 –
98 190 – – – 313 405 – 12 70
123 215 – – – 353 445 2 32 90
158 250 – – – 398 490 24,5 54,5 112,5
178 270 – – 2,5 448 540 49,5 79,5 137,5
198 290 – – 12,5 498 590 74,5 104,5 162,5
223 315 – – 25 558 650 104,5 134,5 192,5
248 340 – – 37,5 628 720 139,5 169,5 227,5
278 370 – – 52,5 – – – – – –
16
The dimensions of installation opening for the connected air duct depends on the type of sealant- see the table.
Mat: thick 13mm, Paper: thick: 6mm
from outside Firestop Acrylic sealant CFS-S ACR or similar D+28, D+14
Mat: thick 9mm
from outside Firestop Acrylic sealant CFS-S ACR or similar D+20
Firestop Acrylic sealant CFS-S ACR or similar D+10
Orstech LSP H thick 20mm + from outside mastic
Firestop coating CFS-CT or PROMASTOP-P or K or similar D+40
Fire mortar CFS-M RG or similar D+80
Ø D2
Ø D
Solid wall construction (t≥100mm) Dry Fire resistant sealant or stone wool or
glass fiber fabric
Solid wall construction (t≥100mm) Wet Mortar or gypsum
Outside solid wall construction with t≥100mm
(insulation of the pipe between wall and dam-
per made from stone wool)
Dry Fire resistant sealant or stone wool or
glass fiber fabric
Outside solid wall construction with t≥100mm
(insulation of the pipe between wall and dam-
per made from stone wool)
Wet Mortar or gypsum
Solid ceiling construction
110 - Concrete / 125 - Aerated concrete Dry Fire resistant sealant or stone wool or
glass fiber fabric
Solid ceiling construction
110 - Concrete / 125 - Aerated concrete Wet Mortar or gypsum
Outside solid ceiling construction with
110 - Concrete / 125 - Aerated concrete
(insulation of the pipe between wall and dam-
per made from stone wool)
Dry Fire resistant sealant or stone wool or
glass fiber fabric
Outside solid ceiling construction with
110 - Concrete / 125 - Aerated concrete
(insulation of the pipe between wall and dam-
per made from stone wool)
Wet Mortar or gypsum
Gypsum wall construction (t≥100mm) Dry Fire resistant sealant or stone wool or
glass fiber fabric
Gypsum wall construction (t≥100mm) Wet Mortar or gypsum
Outside gypsum wall construction with
t≥100mm (insulation of the pipe between wall
and damper made from stone wool)
Dry Fire resistant sealant or stone wool or
glass fiber fabric
Outside gypsum wall construction with
t≥100mm (insulation of the pipe between wall
and damper made from stone wool)
Wet Mortar or gypsum
Sandwich wall (insulated wall panel) construc-
tion Dry Fire resistant sealant or stone wool or
glass fiber fabric
Outside sandwich wall (insulated wall panel)
construction with insulation of the pipe Dry Fire resistant sealant or stone wool or
glass fiber fabric
The damper is designed for installation on a wall or intermediate floor for circular air-duct connection.
17
Fire classification:
Solid wall construction
Spiral pipe
Fire resistant fill (for recommended materials see separate table)
Threaded rod and anchor to the wall (or ceiling) (e.g. threaded rod M8 and anchor type according pipe weight)
Fire protection mastic min. thickness 1mm (e.g. PROMASTOP-P or K)
Fire damper FDMS
Anchor for damper collar (e.g. FISCHER - type ZYKON FZA M8x30)
Fixing part of the pipe between wall and pipe (only recommended)
Hanging ring (e.g. FISCHER - type LGS)
Inspection hole for camera covered with removable air-tight rubber cap
Connecting surface between damper collar
and wall fulfil with fire resistant sealant before
instalation of the damper (recommended type
of sealant - e.g. PROMAT K84 or HILTI CFS-S)
≥ 100
View B:
Ø D
18
Fire classification:
≥ 96 ≥ 47
≥ 47
≥ 96
≥ 96
19
Solid wall construction
Spiral pipe
Fire resistant fill (for recommended materials see separate table)
Threaded rod and anchor to the wall (or ceiling) (e.g. threaded rod M8 and anchor type according pipe weight)
Fire protection mastic min. thickness 1mm (e.g. PROMASTOP-P or K)
Fire damper FDMS
Pipe insulation with min. fire resistance EI60 (e.g. ISOVER Ulimate protect Wired MAT 4.0 ALU1, PAROC hvac Fire Mat BlackCoat)*
Fixing part of the pipe between wall and pipe (optional)
Hanging ring (e.g. FISCHER - type LGS)
Inspection hole for camera covered with removable air-tight rubber cap
≥ 100
Fire classification:
Connecting surface between wall and pipe insulation
fulfil with fire resistant sealant before instalation of
the insulation (recommended type of sealant - see
instalation instructions of the insulation contractor).
Installation of pipe insulation perform according instructions of the manufacturer.
This fixing part isn't mandatory if the installation opening was fulfill by mortar or gypsum. In other cases of the fire
resistant fill is this fixing part of the pipe mandatory. This fixing part can by mounted on the both sides of the wall.
View A:
Ø D
Nut M8 with anchor
8-fixing part of the pipe (see only
example and recommneded type
on this picture)
Holes for rivets
Ø D+
ISOVER with min. density 66 kg/m³, min. th. 100 mm
PAROC with min. density 80 kg/m³, min. th. 50 mm
20
Gypsum wall construction
Spiral pipe
Fire resistant fill (for recommended materials see separate table)
Threaded rod and anchor to the wall (or ceiling) (e.g. threaded rod M8 and anchor type according pipe weight)
Fire protection mastic min. thickness 1mm (e.g. PROMASTOP-P or K)
Fire damper FDMS
Anchor for damper collar (threaded rod and nuts M8 or e.g. anchor FISCHER - type KD8)
Fixing part of the pipe between wall and pipe (only recommended)
Hanging ring (e.g. FISCHER - type LGS)
Inspection hole for camera covered with removable air-tight rubber cap
View B:
Ø D
Fire classification:
≥ 100
Connecting surface between damper collar
and wall fulfil with fire resistant sealant before
instalation of the damper (recommended type
of sealant - e.g. PROMAT K84 or HILTI CFS-S)

This manual suits for next models

1

Other Mandik Fire And Smoke Damper manuals

Mandik FDMB Guide

Mandik

Mandik FDMB Guide

Mandik FDMR Guide

Mandik

Mandik FDMR Guide

Mandik FDMB User manual

Mandik

Mandik FDMB User manual

Mandik FDMD User manual

Mandik

Mandik FDMD User manual

Mandik SEDS-L Guide

Mandik

Mandik SEDS-L Guide

Mandik FDMR Manual

Mandik

Mandik FDMR Manual

Mandik FDMR User manual

Mandik

Mandik FDMR User manual

Mandik SEDS-R User manual

Mandik

Mandik SEDS-R User manual

Mandik SEDM User manual

Mandik

Mandik SEDM User manual

Mandik SEDM Guide

Mandik

Mandik SEDM Guide

Mandik SEDM User manual

Mandik

Mandik SEDM User manual

Mandik FDMB Series User manual

Mandik

Mandik FDMB Series User manual

Mandik MSD Square Configuration guide

Mandik

Mandik MSD Square Configuration guide

Mandik FDMC User manual

Mandik

Mandik FDMC User manual

Mandik CFDM User manual

Mandik

Mandik CFDM User manual

Mandik FDMB User manual

Mandik

Mandik FDMB User manual

Mandik MSD User manual

Mandik

Mandik MSD User manual

Mandik FDMC User manual

Mandik

Mandik FDMC User manual

Mandik FDML Guide

Mandik

Mandik FDML Guide

Mandik FDMC Series User manual

Mandik

Mandik FDMC Series User manual

Mandik FDMA-PM User manual

Mandik

Mandik FDMA-PM User manual

Mandik SEDS-L User manual

Mandik

Mandik SEDS-L User manual

Mandik FDMB User manual

Mandik

Mandik FDMB User manual

Mandik FDMD User manual

Mandik

Mandik FDMD User manual

Popular Fire And Smoke Damper manuals by other brands

ETS NORD NORDfire manual

ETS NORD

ETS NORD NORDfire manual

Broan FRESH IN FIN-6MD installation instructions

Broan

Broan FRESH IN FIN-6MD installation instructions

Ruskin actionair ES Series Operating and maintenance manual

Ruskin

Ruskin actionair ES Series Operating and maintenance manual

mercor mcr FID B Operation and maintenance manual

mercor

mercor mcr FID B Operation and maintenance manual

dalap GBV quick start guide

dalap

dalap GBV quick start guide

Ace FYN-N1 Operating and mounting instructions

Ace

Ace FYN-N1 Operating and mounting instructions

HVC NCA 100 Series manual

HVC

HVC NCA 100 Series manual

Johnson Controls FD-1300 Installation

Johnson Controls

Johnson Controls FD-1300 Installation

ATI Technologies LS1 Installation instruction

ATI Technologies

ATI Technologies LS1 Installation instruction

HAG INTACT Installation, operation and maintenance

HAG

HAG INTACT Installation, operation and maintenance

Rf-t ONE-X CU2/B manual

Rf-t

Rf-t ONE-X CU2/B manual

Kitz KE-2015-00 Operation and maintenance manual

Kitz

Kitz KE-2015-00 Operation and maintenance manual

Ingersoll-Rand ARO SB30 Series Operator's manual

Ingersoll-Rand

Ingersoll-Rand ARO SB30 Series Operator's manual

BESA TB/001 Technical bulletin

BESA

BESA TB/001 Technical bulletin

Wildeboer FR90 user manual

Wildeboer

Wildeboer FR90 user manual

Trox Technik AKK Assembly and operating instructions

Trox Technik

Trox Technik AKK Assembly and operating instructions

mercor mcr PL1 Technical and Operational Documentation

mercor

mercor mcr PL1 Technical and Operational Documentation

Trox Technik EK-JZ manual

Trox Technik

Trox Technik EK-JZ manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.