Compact. Easy installation. Universal. Cost effective. Safe.
Product views and applications
Description Highlights
Safety damper Ball valve Throttle valve
Electrical rotary actuators
for use in safe areas
3-pos. / 0...10 VDC / 4...20 mA control mode, with feedback, 24...240 VAC/DC, 95° angle of rotation
50/75 Nm, 100 Nm without and 30 Nm, 50 Nm with safety operation (spring return)
InMax ¼ turn actuators – size M
►Industrial use
►Universal supply unit from 24…240 VAC/DC
►5 different motor running times 40–60–90 –120–150 s /90°, adjustable on site
►2 different spring return running times ~ 20 s/90°, selectable on site
►3-pos. and 0...10 VDC, 4...20 mA control mode with or without spring return function
► Feedback signals 0...10 VDC and 4...20 mA
► Reverse function
►30– 50– 75– 100 Nm actuators in the same housing size
►100 % overload protected
►Compact design and small dimension (L × W × H ~ 288 × 149 × 116 mm)
►Direct coupling to the damper shaft with double square connection 16 × 16 mm
►95° angle of rotation inclusive 5° pretension
►Robust aluminium housing (optional with seawater resistant coating)
or in stainless steel
►IP67 protection
►Simple manual override included + preparation for comfortable manual override
►Gear made of stainless steel and sinter metal
►Weight only ~ 9,5 kg
►Integrated heater for ambient temperatures down to −40 °C
►Integrated safety temperature sensor
►Integrated equipment for manual adjustment (push button, lamp, switch)
►Preparation for adaptable and adjustable auxiliary switches type ...Switch
►Wide range of accessories
The InMax actuators are a revolution for safety, control and shut-off
dampers, VAV systems, ball valves, throttle valves and other motorized
applications for HVAC systems in chemical, pharmaceutical, industrial
and offshore/onshore plants.
IP67 protection, small dimensions, only 9,5 kg weight, universal functions
and technical data, an integrated heater and an optional stainless steel
housing guarantee safe operation even under difficult environmental
conditions. High quality brushless motors guarantee long life.
All actuators are programmable and adjustable on site. Special tools or
equipment are not required. Motor running times and torques as well as
spring return times, according to the actuator type, are selectable or
adjustable on site. The integrated universal power supply is self adaptable
to input voltages in the range of 24...240 VAC/DC. Furthermore it is
possible to perform control signal inverting and compulsion control by
certain connections. The actuators are 100 % overload protected.
...Max-...-YF actuators are equipped with spring return fail safe function.
Standard shaft connection is a double square direct coupling with
16 × 16 mm.
Different accessories are available to adapt auxiliary switches, terminal
boxes or adaptions for ball valves and throttle valves and other armatures.
Type Torque Supply Motor running time Spring return Control mode Feedback Wiring diagram
InMax- 50.75 - Y 50 / 75 Nm 24...240 V AC/DC 40 / 60 / 90 / 120 / 150 s/90° – 3-pos., 0...10 V DC, 4...20 mA 0...10 V DC, 4...20 mA SB 4.0/4.1
InMax-100 - Y 100 Nm 24...240 V AC/DC 40 / 60 / 90 / 120 / 150 s/90° – 3-pos., 0...10 V DC, 4...20 mA 0...10 V DC, 4...20 mA SB 4.0/4.1
InMax- 30 - YF 30 Nm 24...240 V AC/DC 40 / 60 / 90 / 120 / 150 s/90° ~ 20 s/90° 3-pos., 0...10 V DC, 4...20 mA 0...10 V DC, 4...20 mA SB 4.0 / 4.1
InMax- 50 - YF 50 Nm 24...240 V AC/DC 40 / 60 / 90 / 120 / 150 s/90° ~ 20 s/90° 3-pos., 0...10 V DC, 4...20 mA 0...10 V DC, 4...20 mA SB 4.0 / 4.1
InMax- ... - CTM Types as above with aluminium housing and seawater resistant coating (cable glands brass nickel-plated)
InMax- ... - VAM Types as above with stainless steel housing for aggressive ambient (cable glands brass nickel-plated)
1 / 4
EXPLOSIONPROOF
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-M-Y_en
V04 – 9-Nov-2018
InMax-...-Y InMax-...-YF
Special option ... -CTM ... -VAM
Technical data InMax- 50.75 -Y InMax- 100 -Y InMax- 30 -YF InMax- 50 -YF
Approbations Special solutions and accessories
...-CTM Types in aluminium housing with seawater resistant coating,
parts nickel-plated
...-VAM Types in stainless steel housing, parts nickel-plated
InBox-Y/S... Terminal boxes
MKK-M Mounting bracket for boxes type ...Box-... directly on actuator
InSwitch 2 external aux. switches, adjustable
HV-MK Comfortable manual override for ...Max actuators size M
AR-16-xx Reduction part for 16 mm square connection to 14 or 12 mm shafts
Kit-S8 Cable glands nickel-plated
Adaptions for dampers and valves on request
Torque motor (min.) 50 / 75 Nm selectable on site 100 Nm 30 Nm 50 Nm
Torque spring (F) – – min. 30 Nm min. 50 Nm
Torque blockade In blockade and end positions torques are higher than above specified torques for motor and spring.
Dimensioning of external load Upon spring return the external load should be max. 80 % of torque spring (F), but min. 10 Nm
Supply voltage / frequency 24...240 VAC/DC ± 10 %, self adaptable, frequency 50...60 Hz ± 20 %
Power consumption max. starting currents see Extra information (in acc. with voltage, I start >> I rated ), approx. 5 W holding power, approx. 16 W for heater
Protection class Class I (grounded)
Angle of rotation and indication 95° incl. ~ 5° pretension, mechanical value indication
Working direction Selectable by left/right mounting to the damper/valve shaft
Motor running times 40 / 60 / 90 / 120 / 150 s/90° selectable on site
Motor Brushless DC motor
Control mode Y 3-pos., 0…10 VDC, 4…20 mA in acc. with wiring, selectable on site. Galvanic separation between supply and Y-signal
Feedback signal U 0…10 VDC, 4…20 mA in acc. with wiring, selectable on site, both signals are available at the same time
Resistance of Y and U signals Input signal: YU0...10 VDC at 10 kΩ, YI4...20 mA at 100 Ω. Feedback signal: UU 0...10 VDC at 2.000...∞ Ω, UI4...20 mA at 0...800 Ω
Reverse function Bridge between wiring 3 and 4 (signal wise) gets a reverse function of Y and U
Compulsion control In modulation mode an On-off compulsion control can be performed by external connection/wiring independently from the modulating signal
Adjustment of Y and U In case of external mechanical limitation of the angle of rotation, it is possible to perform an adjustment drive started by touching the button
Spring return (F) – – spring return upon voltage interruption
Spring return response time – – up to 1 sec. after voltage interruption
Spring return running time (F) – – ~ 20 s/90°
Safety operations at 20 sec. (F) – – min. 10,000 acc. to construction of damper and ambient
Axle of the actuator Double square 16 × 16 mm, direct coupling, 100 % overload protected
Electrical connection 2 cables ~ 1 m each, wire cross section 0.5 mm², equipotential bonding 4 mm². Connections require a terminal box!
Diameter of cable ~ Ø 7.1 + 7.4 mm ~ Ø 7.1 + 7.4 mm ~ Ø 7.1 + 7.4 mm ~ Ø 7.1 + 7.4 mm
Cable gland M16 × 1.5 mm
Manual override Use delivered socket wrench, max. 4 Nm
Heater Integrated, controlled heater for ambient temperature down to −40 °C
Housing material Aluminium die-cast housing, coated. Optional with seawater resistant coating (...-CTM) or stainless steel housing,
№1.4581 / UNS-J92900 / similar AISI 316Nb (...-VAM)
Dimensions (L × W × H) ~ 288 × 149 × 116 mm, for diagrams see Extra information
Weight ~ 9.5 kg aluminium housing, stainless steel ~ 15 kg
Ambients Storage temperature −40…+70 °C, working temperature −40…+50 °C
Humidity 0...90 % rH, non condensing
Operation mode 80 % of ED are permitted (ED = duty cycle)
Accuracy electrically ~ 100 steps
Self adjustment If you select 40 sec. or 60 sec. mode for motor running time or rotation angle < 90° you need to start the self adjustment mode
Maintenance Maintenance free relative to function, maintenance must comply with regional standards, rules and regulations
Wiring diagrams SB 4.0 / 4.1 SB 4.0 / 4.1 SB 4.0 / 4.1 SB 4.0 / 4.1
Scope of delivery Actuator, 4 screws M8 × 140 mm, 4 nuts M8, Allen key for simple manual override
Parameter at delivery 50 Nm, 90 s/90° 100 Nm, 90 s/90° 30 Nm, 90 s/90° 50 Nm, 90 s/90°
CE identification CE
EMC directive 2014/30/EU
Low voltage directive 2014/35/EU
Enclosure protection IP67 in acc. with EN 60529
2 / 4
EXPLOSIONPROOF
InMax- 50.75-Y ►
InMax- 100-Y ►
InMax- 30-YF ►
InMax- 50-YF ►
50 Nm
100 Nm
30 Nm
50 Nm
▼
75 Nm
▼
40 s/90° ►
60 s/90° ►
90 s/90° ►
120 s/90° ►
150 s/90° ►
00
01
02
03
04
05
06
07
08
09
InBox
a b
+
~
+
~
−
~
−
~
PE
PE
1
1
2
2
3
3
4
4
6
6
1
1
2
2
3
3
5
5
4
4
PA
PA
YmA
YmA
YVDC
YVDC
T
VDC/mA
T
VDC/mA
UmA
UmA
UVDC
UVDC
S
T
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-M-Y_en
V04 – 9-Nov-2018
InMax-...-Y InMax-...-YF
Special option ... -CTM ... -VAM
Electrical connection Parameters, adjustments and failure indication
Parameter selection
Functions, adjustments and parameters
Type
Running times Position of switch S
Torques
Example:
InMax-50.75-Y
Requested parameter:
Torque 75 Nm
Motor running time 90 s/90°
Result:
Switch position 07
All actuators are equipped with a universal supply unit working at a voltage range from
24...240 VAC/DC. The supply unit is self adjusting to the connected voltage!
The safety operation of the spring return function works if the supply voltage is cut.
For electrical connection a terminal box is required (e.g. InBox).
An over-current protection fuse < 10 A has to be provided by installer.
Note: the initial current is appr. 2 A for 1 second.
Installation
supply *
24...240 VAC/DC ± 10 %
* electrical wiring see diagrams
Modulating / 3-pos. – with / without spring return SB 4.0
Modulating – with / without spring return (no enforcement) SB 4.1
Function and enforcement control of switch a and b in modulating mode:
▪a closed – Forced-ON (OFF) in acc. to left /right mounting of actuator
▪b closed – Forced-OFF (ON) in acc. to left /right mounting of actuator
Reverse function:
Bridge 3–4 reverses the
input and output signals
Reverse function:
Bridge 3–4 reverses the
input and output signals
Self adjustment:
To adjust the signal input /output to the angle of
rotation of the damper/valve the button (T) must
be pushed for a minimum of 3 sec.
Self adjustment:
To adjust the signal input /output to the angle of
rotation of the damper/valve the button (T) must
be pushed for a minimum of 3 sec.
24...240 VAC/DC
24...240 VAC/DC
Attention
During commissioning apply a self adjustment drive.
Regard duty cycle at motor running times!
Never use spring return actuators without external load.
A) Self adjustment of angle of rotation
Turn switch (S) to position 02 (low torque) or 07 (high torque). Press button (T) for
a minimum of 3 seconds. The actuator drives to both end positions and detects the
blocking positions. The LED flashes GREEN during adjustment.
The adjustment takes about 180 seconds (90 sec. “On”, 90 sec. “Off”).
B) Selecting motor running time and torque
Adjust parameters only if actuator is in idle state or without applied potential.
Turn switch (S) to the position required for the intended operation acc. to table
above. The selected parameters will be carried out at the actuator’s next operation.
C) Changing modulating operation to 3-pos. operation with feedback
Modulating mode: The LED lights GREEN, potential applied.
Press button (T) briefly 3 times:
▪ each for at least 0.2 seconds
▪altogether within max. 5 seconds
The LED changes from steady GREEN to steady YELLOW*.
D) Changing 3-pos. operation with feedback to modulating operation
3-pos. mode: The LED lights YELLOW*, potential applied.
Press button (T) briefly 3 times.
The LED changes from steady YELLOW* to steady GREEN.
E) Additional information for control in 3-pos. operation with feedback
a closed, b open = direction I a and b closed = motor doesn’t work
b closed, a open = direction II a and b open = motor doesn’t work
The rotation direction (I and II) depends on left/right mounting of the actuator to the
damper. To reverse the rotation direction (by motor) exchange the electrical wiring
of terminal 3 and 4.
In 3-pos. operation with feedback the Y-inputs are without function.
F) Inverting
Bridging signal wires 3–4 (cable B) inverts the function of input signals Y and feed-
back signals U.
* Note: “YELLOW” may vary from yellowish to orange.
Switch – Push button – Lamp
for adjustment
(behind the blanking plug)
10-position switch (S)
3-colour LED
Push button (T)
3 / 4
EXPLOSIONPROOF
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-M-Y_en
V04 – 9-Nov-2018
InMax-...-Y InMax-...-YF
Special option ... -CTM ... -VAM
Important information for installation and operation
Extra information (see additional data sheet)
Additional technical information, dimensions, installation instruction, illustration
and failure indication
A. Installation, commissioning, maintenance
All national and international standards, rules and regulations must be complied with.
Apparatus must be installed in accordance with manufacturer instructions. If the equipment
is used in a manner not specified by the manufacturer, the safety protection provided by
the equipment may be impaired.
For electrical connection a terminal box is required (e.g. InBox-...).
Attention: If the actuator is put out of operation all rules and regulationsmust be applied.
You have to cut the supply voltage before opening the terminal box!
The cablesof the actuator must be installed in a fixed position and protected against
mechanical and thermical damage. Connect potential earth. Avoid temperature transfer
from armature to actuator! Close all openings with min. IP67.
For outdoor installation a protective weather shield against sun, rain and snow should be
applied to the actuator as well as a constant supply at terminal 1 and 2 for the integrated
heater. During commissioning apply a self adjustment drive.
Actuators are maintenance free. An annual inspection is recommended. Actuators must
not be opened by the customer.
B. Manual override
Manual override only if supply voltage is cut. Use delivered socket wrench with slow
motions, usage can be tight.
Attention: Releasing or letting go the Allen key too fast at manual operating actuators
with spring return causes risk of injury!
C. Shaft connection, selection of running time
Actuators are equipped with a direct coupling double square shaft connection of 16 × 16 mm.
The housing of the actuator is axially symmetrically built to select Open-close direction
of the spring return function by left-right mounting. Using the 10-position switch different
motor running times and spring return running times can be selected on site in acc. to
the actuator type.
D. 3-position control mode
...Max actuators are in the best way suitable for the 3-pos. operation. To protect such
elements as gears and mounting elements against harmful influences like minimum
pulse time, ...Max actuators are protected via internal electronics. It ignores impulses
< 0,5 s, the cyclic duration must be min. 0,5 s. At changing direction the pause is 1 s.
E. Spring return
Spring return function works only if the supply voltage for terminal 1 or 2 is cut. In the
event of an electrical interruption, the spring returns to its end position even if supply
voltage is available again during return function. Thereafter operation will continue.
F. Operation at ambient temperatures below −20 °C
All actuators are equipped with a regulated integrated heating device designed for
employments down to −40 °C ambient temperature. The heater will be supplied automatically
by connecting the constant voltage supply on the clamps 1 and 2.
1. After mounting the actuator must bei immediately electrically connected.
2. The heater switches on automatically when actuator reaches internally −20 °C. It
heats up the actuator to a proper working temperature, then heater switches off
automatically. Actuator will not run during heating process.
3. The adjustment options are only ensured after this heating up period.
G. Excess temperatures
All actuators are protected against excess temperature.The internal thermostat works
as a maximum limiter and, in the event of failure at incorrect temperatures, shuts off the
actuator irreversible. An upstream connected temperature sensor stops the actuator
before reaching its max. temperature. This safety feature is reversible, after cooling down
the actuator is completely functional again. In this case the failure must be eliminated
immediately on site!
H. Synchron mode
Do not connect several actuators to one shaft or link mechanically together.
I. Mechanical protection
Actuators must be operated with a minimum external load.
After installing the actuator to the damper/armature a self adjustment drive has to be
performed in order to protect the damper/armature against mechanical overload.
During operation the actuator reduces briefly its speed (motor power) before reaching
the end position for a “gentle” blockade/stop.
Accessory InBox – terminal boxAccessory InSwitch – auxiliary switch
For an end or inclined position indication it is possible to
retrofit external, adjustable auxiliary switches type
InSwitch.
The ...Switch is mounted directly to the actuator. The
switches deliver a potential free output and can be adjusted
separately. They are connected by cable.
For electrical connection of the ...Max actuator a terminal
box is required.
To adapt the ...Box directly to the actuator housing a mounting
bracket is required.
InBox- Y/S for ...Max-...-Y and ...-YF
4 / 4

Other manuals for InMax CTM Series

1

This manual suits for next models

7

Other Schischek Controllers manuals

Schischek RedMax CTM Series User manual

Schischek

Schischek RedMax CTM Series User manual

Schischek RedMax-30-BF User manual

Schischek

Schischek RedMax-30-BF User manual

Schischek RedMax F1 Series User manual

Schischek

Schischek RedMax F1 Series User manual

Schischek InMax-8-F1 User manual

Schischek

Schischek InMax-8-F1 User manual

Schischek ExMax F3 Series User manual

Schischek

Schischek ExMax F3 Series User manual

Schischek ExMax CTM Series User manual

Schischek

Schischek ExMax CTM Series User manual

Schischek InMax Series User manual

Schischek

Schischek InMax Series User manual

Schischek ExMax User manual

Schischek

Schischek ExMax User manual

Schischek ExMax Series Quick start guide

Schischek

Schischek ExMax Series Quick start guide

Schischek InMax-8-F1 User manual

Schischek

Schischek InMax-8-F1 User manual

Schischek RedMax-Y Series User manual

Schischek

Schischek RedMax-Y Series User manual

Schischek RedMax BF-VA Series User manual

Schischek

Schischek RedMax BF-VA Series User manual

Schischek ExReg-V CT Series User manual

Schischek

Schischek ExReg-V CT Series User manual

Schischek InMax CTM Series User manual

Schischek

Schischek InMax CTM Series User manual

Schischek RedMax F Series User manual

Schischek

Schischek RedMax F Series User manual

Schischek Redmax Series Quick start guide

Schischek

Schischek Redmax Series Quick start guide

Schischek ExMax CY Series User manual

Schischek

Schischek ExMax CY Series User manual

Schischek RedMax-8-F1 User manual

Schischek

Schischek RedMax-8-F1 User manual

Schischek RedMax S Series User manual

Schischek

Schischek RedMax S Series User manual

Schischek ExMax Series User manual

Schischek

Schischek ExMax Series User manual

Schischek RedMax BF Series User manual

Schischek

Schischek RedMax BF Series User manual

Schischek ExRun Y Series User manual

Schischek

Schischek ExRun Y Series User manual

Schischek InMax SF3 Series User manual

Schischek

Schischek InMax SF3 Series User manual

Schischek InMax-100 User manual

Schischek

Schischek InMax-100 User manual

Popular Controllers manuals by other brands

THORLABS LDC200C series Operation manual

THORLABS

THORLABS LDC200C series Operation manual

Extron electronics CTR 8 Setup guide

Extron electronics

Extron electronics CTR 8 Setup guide

Velleman HQ Power VDPDMXC174 manual

Velleman

Velleman HQ Power VDPDMXC174 manual

Ascon tecnologic XS Series instruction manual

Ascon tecnologic

Ascon tecnologic XS Series instruction manual

Allen-Bradley PowerFlex 700S installation instructions

Allen-Bradley

Allen-Bradley PowerFlex 700S installation instructions

Lenze M MA Series operating instructions

Lenze

Lenze M MA Series operating instructions

Hayward OmniPL Retrofit Kit installation manual

Hayward

Hayward OmniPL Retrofit Kit installation manual

Ledi RGB-DMX-CONT-STICK3 installation instructions

Ledi

Ledi RGB-DMX-CONT-STICK3 installation instructions

Novy 906.270 installation instructions

Novy

Novy 906.270 installation instructions

Rice Lake 1280 Enterprise Series Operation manual

Rice Lake

Rice Lake 1280 Enterprise Series Operation manual

Brivo ACS300-A installation manual

Brivo

Brivo ACS300-A installation manual

Kaysun K03 WIFI LCAC Installation & owner's manual

Kaysun

Kaysun K03 WIFI LCAC Installation & owner's manual

Novar 315 Commissioning instructions

Novar

Novar 315 Commissioning instructions

Extron electronics Basic MediaLink Controllers MLC 52 RS Specifications

Extron electronics

Extron electronics Basic MediaLink Controllers MLC 52 RS Specifications

Federal Signal Corporation SignalMaster SMC14 Installing

Federal Signal Corporation

Federal Signal Corporation SignalMaster SMC14 Installing

aci DSIM-CC installation guide

aci

aci DSIM-CC installation guide

YASKAWA SI-EN3 Technical manual

YASKAWA

YASKAWA SI-EN3 Technical manual

SURUGA SEIKI DS102 Series Operation manual

SURUGA SEIKI

SURUGA SEIKI DS102 Series Operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.