SDC 923PW EntryCheck User manual

The EntryCheck™ 923PW narrow indoor/outdoor Wiegand proximity reader with integral digital keypad is designed to interface with
most Access Control Systems. It offers a 125KHz HID-compatible proximity reader with standard 26-bit Wiegand output. The built-in
keypad may be programmed to output 26-bit Wiegand data, or a 4-bit word for high-security applications that require dual
authentication (Card + PIN).
The backlit keys are bright and easy-to-read. A heavy cast, vandal resistant housing design with narrow mounting plate allows the
923PW to be mounted on a rugged surface, mullion, or on a recessed single-gang electrical box.
Two long lasting solid state LED indicators show the status of the system. The left bi-color indicator lights red to indicate power, or
green to indicate an authorized access (controlled externally by host). The right indicator flashes yellow to indicate that the keypad is
in programming mode.
P:\INSTALLATION INST\Access Controls\INST-923\INST-923PW.vsd Rev A 09-17 Page 1
INSTALLATION INSTRUCTIONS
923PW EntryCheck TM
801 Avenida Acaso, Camarillo, Ca. 93012 • (805) 494-0622 •
www.sdcsecurity.com • E-mail: service@sdcsecurity.com
Features
12 key illuminated 2x6 digital keypad with configurable
illumination: always on, timed, off
HID-compatible (125KHz RFID) proximity reader
Suitable for Indoor/Outdoor use: Weather & vandal
resistant
Standard 26-bit Wiegand output for universal
compatibility
Programmable Site Code
Programmable Keypad Operation:
- 26-bit Wiegand, or
- 4-bit word
Surface, mullion, or recessed single-gang mount
Built-in tamper switch
Two LED status indicators
Audible annunciation of keystrokes with adjustable
sound level: normal, low, off
Tactile metal keys
Includes wiring harness
Optional privacy & rain shroud available
Operating Voltage: 5 - 16 Volts DC
Current Consumption: 30mA (typical), 60 mA (max)
Operating Temperature: -4° to 140°F (-20° to 60°C)
Humidity: 5% to 95% non-condensing
Dimensions (H x W x D): 7.3125" x 1.75" x 1.375",
(1.4375" wall projection)
Housing: Weather-resistant cast metal
Cabling: 6" wiring harness
Reader Output: 26-bit Wiegand
Keypad Output: 26-bit Wiegand or 4-bit word
Max. Cable Distance to Host: 328ft (100m) @12VDC,
100ft (30m) @ 5VDC, using 18AWG cabling
Recommended cable (shielded, multi-conductor) or
equal:
-Belden 5504FE (6 Cond)
-Belden 5506FE (8 Cond, for Tamper Switch)
Tamper switch: Form “C”, 1A @ 30VDC
Specifications
923PW WIRING
See Fig. 3 for an example of a basic door installation. The
923PW is mounted adjacent to the door. An electric door
strike is mounted in the door jamb to release the door lock.
A magnetic switch is mounted on top of the door jamb for
detecting when the door is open. The access host
controller is located at a maximum distance of 300ft of the
keypad reader, depending on the reader voltage provided.
Refer to the Fig. 4 or Fig. 5 for wiring details.
To avoid damage to the unit from static discharges,
connect the mounting plate to a good earth grounding
point. Suggested wiring size is 18 AWG for earth ground.
P:\INSTALLATION INST\Access Controls\INST-923\INST-923PW.vsd Rev A 09-17 Page 2
Fig. 3 Basic Door Installation
Fig. 5 Installation Wiring to IPDCE Single-Door Controller
6 wires for
KP Reader
SDC IP Pro™ Single Door Controller
or 3rd Party Access Control
2 wires for
Door Sensor
2 wires for
Strike Power
923PW
Keypad
FRONT
YELLOW
“PROGRAM”
INDICATOR
RED/GREEN
POWER/ACCESS
INDICATOR
KEYPAD
PROX
Antenna
2 wires for
Remote
Release
WIRING
HARNESS
Fig. 4 Wiring Harness Connections
RED
BLK
WHT
GRN
ORG
YEL
BLU
PNK
VIO }
C
N/O
N/C Tamper
Buzzer
SDC P/N:
IPDCE or IPDSE
SENSE
CLOCK
DATA
+12V
0V
RED
GREEN
WireColor Designation
RED +VDC(5‐16V)
BLACK GND
WHITE WIEGANDD1
GREEN WIEGANDD0
ORANGE GREENLEDCONTROL
YELLOW BUZZERCONTROL
BLUE TAMPER(N.O.)
SALMON TAMPER(COM)
VIOLET TAMPER(N.C.)
920PWWiringHarnessConnections
7.3125
1.375
1.75"
BEEPER
LEVEL
JUMPER
(JP1)
BACK
9-PIN WIRING
HARNESS
ANTI-
TAMPER
SWITCH
MASTER CODE
RESET JUMPER
(JP2)
923PW
Grn Wire
To earth ground
earth
ground
FACTORY DEFAULTS
Master Programming Code………..…………………..….…...123456
Keypad Output Mode………………………………..…26-bit Wiegand
Keypad Output Site Code………………………………………..…000
Beeper Sounds When Key Pressed……………………...………Yes
Beeper Volume…………………………………………….……Normal
Keypad Backlight Mode………………………30 sec after activation
Keypad Timeout…………………………………………..………5 sec
923PW OPERATION
The 923PW EntryCheck™ integrates an HID proximity reader with
a 12-key digital keypad. Presenting a card/fob to proximity reader
will transmit the credential’s facility (site) code and card number in
a standard 26-bit Wiegand output.
The Keypad may operate in one of two modes:
(1) Wiegand Mode (default) – In this mode, the keypad will
emulate a reader credential. Entering a ‘card’ number followed by
‘#” will transmit the programmed facility code plus the card
number as a 26-bit Wiegand output. The card number entered
must be > 0 and < 65,535.
(2) PIN Mode – When this mode is enabled, each key press
generates a 4-bit sequence. Enable PIN mode if the host
controller supports (Card + PIN) mode, and dual authentication is
desired.
Entering Programming Mode
The 6-digit Master Programming Code (default = 123456) is
used to enter Programming Mode.
Press: # 9 # Master Code #
Master Code = the current 6-digit Master Programming Code
P:\INSTALLATION INST\Access Controls\INST-923\INST-923PW.vsd Rev A 09-17 Page 3
BASIC PROGRAMMING
While the 923PW is in Programming Mode the yellow indicator
will blink slowly.
After a programming function is selected, the yellow indicator
will flash rapidly while the keypad is waiting for user input data.
You will have 5 sec. between programming commands once a
function is selected. The green indicator will light if the data is
accepted. The red indicator will light if any programming data
is entered incorrectly, and the function will have to be fully re-
entered.
Exiting Programming Mode
Press: #
The red indicator will light after exiting Programming Mode
Note: The 923PW will automatically exit Programming Mode
after 2 minutes of inactivity
Changing the 6-Digit Master Programming Code
It is recommended that the Master Programming Code be changed
after the installation is finalized.
Press: 98 # Master Code # Master Code #
Master Code = The new 6-digit Master Programming Code
Changing the Beeper Sound Level
The Keypad’s beeper can be set to normal or low level.
Remove jumper JP1 to reduce beeper sound level.
PROGRAMMING COMMANDS
Enter Programming Mode before performing any of the following
commands.
Beep Sounds on Keystrokes Default: Yes
Selects whether or not the keypad beeps as each key is pressed.
Press: 40 # Sound #
Sound=1 for Yes, =0 for No
Selects mode for Keypad LED Backlight Default: 30 Secs.
Selects whether or not the keypad back light stays OFF, lights for 30
seconds when activated or stays ON.
Press: 52 # Output #
Output = 0, Light always OFF
= 1, 30 sec light when activated (default)
= 2, Light always ON
Change Facility (Site) Code Default: 000
Selects the Site Code when using the Keypad in Weigand Mode.
Press: 82 # Site Code #
Site Code = New 3-Digit Site Code (000-255)
Change Keypad Operation Mode Default: Wiegand Mode
Selects the Keypad Operation Mode.
Press: 83 # Mode #
Mode = 0, Wiegand Mode
= 1, PIN Mode
NOTE: Once the keypad is placed into PIN Mode, it can only be
returned to the default Wiegand Mode by following the Master Reset
procedure below.
Master Reset
Resets all programming options. NOTE: The Master Code will NOT
be reset.
STEP 1 Disconnect power from the keypad.
STEP 2 Press and hold down the * and # keys.
STEP 3 Apply power to the keypad, continue holding the keys
down until the red indicator starts flashing
STEP 4 Release the keys. The red and yellow indicators will
remain lit until the process is complete, then the yellow
indicator will go out.
Resetting the Master Code
STEP 1 Remove the 923PW from the wall and disconnect
power from the keypad.
STEP 2 Locate & remove jumper JP2. Reference page 2.
STEP 3 Re-apply power. You will get a single beep and
the yellow LED will flash momentarily.
STEP 4 Replace jumper on JP2. The Master Code is now
123456.
RESETTING THE KEYPAD READER
ERROR ANNUNCIATION (Wiegand Mode only)
KeypadAction Indication
Keypresstimeout(instandby) DoubleBeep
0,ornumber>=65535isentered RedLEDflashw/beep(x3)
*isentered RedLEDflashw/beep(x3)
MasterCodeerror RedLEDflashw/beep(x3)
P:\INSTALLATION INST\Access Controls\INST-923\INST-923PW.vsd Rev A 09-17 Page 4
WALL MOUNT
MULLION MOUNT
1.375
7.3125
1.750
4X Mount at holes
With supplied
screws and hole
expansion anchors
SURFACE MOUNT
GASKET
MOUNTING
PLATE

Other SDC IP Access Controllers manuals

SDC EntryCheck 931-KP-4U User manual

SDC

SDC EntryCheck 931-KP-4U User manual

SDC EntryCheck 920PW User manual

SDC

SDC EntryCheck 920PW User manual

SDC IP100HK User manual

SDC

SDC IP100HK User manual

SDC IP100SGK-EM User manual

SDC

SDC IP100SGK-EM User manual

SDC 950 ENTRYCHECK Installation manual

SDC

SDC 950 ENTRYCHECK Installation manual

SDC EntryCheck 936 User manual

SDC

SDC EntryCheck 936 User manual

SDC EntryCheck 920 User manual

SDC

SDC EntryCheck 920 User manual

SDC E4KP ENTRYCHECK User manual

SDC

SDC E4KP ENTRYCHECK User manual

SDC 950 ENTRYCHECK Installation manual

SDC

SDC 950 ENTRYCHECK Installation manual

SDC 920P EntryCheck User manual

SDC

SDC 920P EntryCheck User manual

Popular IP Access Controllers manuals by other brands

HIK VISION DS-K1A802 Series quick start guide

HIK VISION

HIK VISION DS-K1A802 Series quick start guide

Smarti SMNG240 user manual

Smarti

Smarti SMNG240 user manual

D-Link DIR-868L How to set up

D-Link

D-Link DIR-868L How to set up

Soyal AR-723-H manual

Soyal

Soyal AR-723-H manual

Soyal AR-888U manual

Soyal

Soyal AR-888U manual

H3C WX3500H series installation guide

H3C

H3C WX3500H series installation guide

OUZIM BioEngine 3 manual

OUZIM

OUZIM BioEngine 3 manual

Tidomat SO-3392-V installation instructions

Tidomat

Tidomat SO-3392-V installation instructions

Dahua DHI-DEE1010B-S2 user manual

Dahua

Dahua DHI-DEE1010B-S2 user manual

Beninca BE.PROXY manual

Beninca

Beninca BE.PROXY manual

Soyal AR-837 E user guide

Soyal

Soyal AR-837 E user guide

Idemia MorphoAccess SIGMA Extreme Series Quick user guide

Idemia

Idemia MorphoAccess SIGMA Extreme Series Quick user guide

GIGAMEDIA GGM AXA1EMK2K user manual

GIGAMEDIA

GIGAMEDIA GGM AXA1EMK2K user manual

Niko 16-645 manual

Niko

Niko 16-645 manual

Sewosy KRR1 installation instructions

Sewosy

Sewosy KRR1 installation instructions

alcatraz ROCK-1 install guide

alcatraz

alcatraz ROCK-1 install guide

CDVI TERENA installation manual

CDVI

CDVI TERENA installation manual

ZKTeco SpeedFace-V5L user manual

ZKTeco

ZKTeco SpeedFace-V5L user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.