ENGLISH 2/8
MI003432-E
Selectable between: 16.66 ms(reiection 60Hz)
or 20 ms (reiection 50Hz)
The input signal filter’s level can be configured:from 0 to 19
Scale span configurable: from 0V to 10V. Input impedance:
120kAutomatic out of range detection.
Current input mode
(active / passive
module)
Scale span configurable: from 0mA to 20mA. Internal shunt: 50
Power supply of sensor loop: from sensor to module (passive
module) or from module to sensor(actvive module) by terminal 7
(Max 25 mA a Max 17 V) .with short-circuit protection
Automatic out of range detection.
Scale span configurable: from 1% to 100%.
Potentiometer input value from 1k to 100k(a R=330
parallel circuit must be added). Energising current:1mA. Input
impedance: >5MAutomatic out of range detection.
thermocouples (TC)
input mode
TC type: J, K, R, S, T, B, E, N. input impedance: > 5 M
Automatic burn-out detection
thermoresistances
(RTD) input mode
RTD type: PT100, PT500, PT1000,NI100. (2, 3 or 4 wires
resistance measurement). Energising current: 1.1mA (PT100) and
0.11mA (PT1000, PT500) Automatic burn-out detection
Two relay SPST 3A 250V with one output contact in common.
Available input types: voltage (mV), current (mA ), potentiometer (%),
thermocouples TC (C°), thermoresistances RTD (C°)
2
Removable terminals with section of 2.5 mm
Possibility of USB configuration.
If current input then sensor powered by 2-wire technique is available: 17 V Max
stabilised, 20mA Max with short-circuit protection (terminal 7).
1500V isolation between input and power supply outputs.3000 V to the
Possibility to set: input type, input filter, alarm output, reiection, burn-out, etc..
(See: www.seneca.it)
Front panel display: power on, out of range or burn out error and alarms status.