Advanced GSM/GPRS device for telecontrol
MyALARM2-3
INSTALLATION MANUAL

ENGLISH - 2/8
MI004930-E
t
3GSM/GPRS module for civil and industrial applications, for domotics, for safety: alarm management system
and datalogger
3Display LCD 128 x 32 Dots
3: 8 hLithium-ion rechargeable battery, autonomy up to
3Nr.4 digital inputs (available on internal terminals)
3Nr.2 analog inputs V / mA (available on internal terminals)
3Nr.1 temperature sensor input (NTC)
3Nr.1 GSM replaceable antenna on SMA connector
3Power ON / OFF button and display scrolling button
3Power Supply / Device Status LED and GSM status LED
3SIM card slot (SIM dimensions: 15 x 25 mm)
3Micro SD card slot
3 for internal battery charging and module configurationMicro USB plug in
3Nr.2 relay digital outputs (optional board)
GENERAL CHARACTERISTICS
MODULE LAYOUT
Weight
150 g.
Case
Polycarbonate / ABS material.
80 mm
108 mm
32 mm
8 mm
LED SIGNALLING ON FRONT PANEL
LED
Status
LED’s meaning
GSM
(Yellow)
Slow Blinking
0.8s ON n 0.8s OFF o
nnnnoooonnnnoooo
MyAlarm2-3 is Connected to GSM Network
Fast Blinking
0.1s ON n 0.1s OFF o
nononononononono
GSM Network Searching or Missing Signal
PWR
(Green)
ON n
MyAlarm2-3 Powered ON
OFFo
MyAlarm2-3 Turned OFF
Fast Blinking
0.2s ON n 0.2s OFFo
nononononononono
Micro SD card Access
Medium Blinking
2.8s ON n 0.4s OFF o
nnnnnnnnnnnnnnoo
Active Datalogger Function

ENGLISH - 3/8
MI004930-E
t
POWER SUPPLY
Voltage
Consumption
Internal battery
6 – 15 VC, 500 mA Max.
3.5 W Max.
Lithium ions 3.7 V - 1000 mAh, rechargeable not replaceable.
Dimensions: 53 mm x 34 mm x 6 mm
ENVIRONMENTAL CONDITIONS
Temperature
Humidity
Storage Temperature
Protection degree
Seneca recommends use from 0 to 45 ° C for proper operation.
With external power supply: -20 – +55°C.
With battery power supply (in discharge): -20 – +45°C.
Possible recharging range: 0 – +45°C.
30% – 90% non condensing.
from -20 °C to +20 °C < 1 year
from -20 °C to +45 °C < 3 months
from -20 °C to +60 °C < 1 month
IP20
DIGITAL OUTPUTS
Type
2 outputs
Relay 3 A max (on common terminal) - 250V SPST (with common terminal)
RELAYS (OPTIONAL) BOARD SPECIFICATIONS
TECHNICAL SPECIFICATIONS
MOTHER BOARD SPECIFICATIONS
DIGITAL INPUTS
Type
Max. Frequency
Threshold OFF
Threshold ON
4 inputs
Reed, contact, PNP, Pulscap
30 Hz
0 – 3 VC, I < 1mA
6 – 24 VC, I > 3mA
ANALOG INPUTS
Type
Accuracy
2 inputs
Voltage 0 – 30 VC / Current 0 – 20 mA
0.1% of full-scale
VOLTAGE OUTPUT
+12 VC, 50 mA (Max. current)
TEMPERATURE SENSOR
Termistor NTC
USB PORT
1 micro USB socket for battery charging and device configuration
DISPLAY
LCD 128 x 32 dots, visible area 39 mm x 8.6 mm
Micro SD slot Type / Memory
Push-Push for SD card and SD HC card / max 32GB
SIM slot Type
Push-Push for mini SIM (15 x 25 mm)
GSM
Quad band (850 / 900 / 1800 / 1900 MHz)

ENGLISH - 4/8
MI004930-E
t
TECHNICAL SPECIFICATIONS
CASE SYMBOLS
ON/OFF button (PWR)
SIM card slot
GSM antenna
micro SD card slot
Display scroll button (SCR)
micro USB socket
SD
SIM
INSTALLATION RULES
The device can be installed on a wall or on a DIN rail EN 60715, in vertical position.
Never place this device inside metal cabinets or near heat sources.
INSTALLATION ON IEC EN 60715 DIN RAIL AND WALL FIXING
Insertion on DIN rail:
1) Insert the three hooks of support for DIN rail into the three
holes in the rear side of the MyALARM and fix the device to 2-3
the support.
2) Hook support and device to the CEI EN 60715 DIN rail.
Wall mounting:
1) The two holes on the support for DIN rail allows to fix it to the
wall with included plugs and screws.
2) Fix the device on the support to the wall by the three holes in
the rear side of the case.
STANDARDS
ETSI EN 301 489-7
EN301 511
EN301 489-1
IEC / EN 60950
CONNECTIONS
Push-wire terminals, pitch 3,5 mm, Micro USB socket
SMA connector for GSM Antenna.
INCLUDED ACCESSORIES
12 V C power supply (with crimp terminals), DIN rail IEC EN 60715
support, Nr. 2 screws, Nr. 2 expansion plugs for wall fixing, GSM
antenna, installation manual and USB cable.
CPU
ARM 100 MHz 32bit
INTERNAL MEMORIES
FLASH 2M Byte (log)

ENGLISH - 5/8
MI004930-E
t
PWR SCR
ANTENNA
ANTENNA
micro
USB
The MyALARM2-3 is delivered in “shipping mode”.
This mode avoid unnecessary discharge of the battery during storage and shipping.
When you switch ON the device, for the first time, please supply power by Usb port or by the included
power supply. This procedure allows the exit from “shipping mode”.
WARNING: When the device is turned ON for the first time, it must be supplied, without any interruptions, for at
least 4 hours in order to charge the internal batteries.
3POWER ON BUTTON AND SCROLL BUTTON
The device has the PWR button, placed in the upper left side (front view).
By pressing this button the module can be switched on.
Hold down the PWR button for a few seconds to turn off the module.
The device has the SCR button, placed in the upper right side (front view).
By pressing of this button you can scroll the display parameters.
3USB PORT AND POWER SUPPLY
The device has a micro USB socket placed on the left side of case, which can
be used to configure the device, to update the firmware and to recharge the
internal battery.
You can recharge the internal battery with:
- The included 12 V power supply connected to the terminals + and - (GND).
- A PC through the USB socket.
- An USB power supply (accessory) through the USB socket.
Power supply the device from USB socket is not suitable for fixed installations,
or configurations where relays or digital inputs are used.
3AUTO POWER-OFF
If the display indicates "LOW BAT" then the internal battery is almost empty and the device switches off
automatically after 60 seconds.
To recharge the battery to an appropriate value: power supply the device with one of the above
recommended ways.
SWITCHING THE DEVICE ON FOR THE FIRST TIME
Disposal of electrical & electronic equipment (applicable throughout the EU and other
countries with separate collection programs). found on this product or on its The symbol
packaging,indicates that this product it must be handed over to an authorised collection point for the
recycling of electrical and electronic equipments.
Before performing any operation it is mandatory to read the full contents of this manual.
The module may only be used by qualified and skilled technicians in the field of electric installation.
www.seneca.it.Specific documentation is available for download at website:
Only the Manufacturer is authorized to repair the module or to replace damaged parts.
The product is susceptible to electrostatic discharge, take appropriate countermeasures
during any operation.
The warranty is null and void in case of improper use or tampering of the module or devices
supplied by the Manufacturer, necessary for its correct operation and if the instructions in this
manual have not been complied with.
PRELIMINARY WARNINGS

ENGLISH - 6/8
MI004930-E
t
3INSERTION AND REMOVAL FROM THE TERMINALS WITH PUSH-WIRE CONNECTION
3PUSH-WIRE TERMINALS
ELECTRICAL CONNECTIONS
The MyALARM2-3 has 15 push-wire terminals inside of the case
For access to the terminals: unscrew the screw in the center of the black top
cover placed in the lower part of the case, lift and remove the cover.
In the figure on side, the top cover has been removed.
CAUTION: If the relay board is present, then the mobile wiring of the cables
connected to the terminals is not allowed. To conveying the cables outwards from the
terminals in order and in safety conditions, use the four detachable passages
located at the rear of the enclosure. When the wiring is finished, fix the black cover on
the device, with the screw, to prevent any accidental contact.
SAFETY INFORMATIONS
Push the
wire down Suggested
wire stripping:
8-9 mm
Insertion of
a solid cable
B Insert
the wire
A Press down with
the screwdriver
Insertion of
a flexible cable
B Pull up
the wire
A Press down with
the screwdriver
Extraction
of a cable
1 2
3
45 6 78 9 10 11 12 -
+
13
Digital output 1 - relay N.O. (*)
Digital output 2 - relay N.O. (*)
Relays common (*)
Ground
Ground
Power supply
(6 – 15 VC)(**)
Digital input 1
Digital input 2
Digital input 3
Digital input 4
+12 VC output
(max 50 mA)
Analog input 1
Analog input 2
Ground
1
2
3
4
5
6
7
8
9
10
11
12
13
+
(*) Available
only with
relay board
(optional)
4
5
6
7
9
4
5
6
7
10
8
11
12
10
11
-
-
PP
A
A
(**) Recommended: connect
a protection fuse by 1 A
-
READING KEY
Digital Signal 6 – 24 VC
Digital Contact
Current analog signal
(loop 4 – 20 mA)
P
A
NTC
sensor input
Voltage / Current analog signal

ENGLISH - 7/8
MI004930-E
t
SIM
card
SD
card
3SIM CARD INSERTION
MyALARM2-3 has a SIM slot, placed in the right side of the case.
Before inserting the SIM card into the slot, make sure that the SIM card’s contacts are
facing to the left (as shown in the figure).
3MICRO SD CARD INSERTION
MyALARM has a SD card slot, placed in the right side of the case.2-3
The SD card can be used for data logging and for MyALARM3 firmware update.
Before inserting the make sure that the SD card’s contacts areSD card into the slot,
facing to the left (as shown in the figure).
SIM-CARD AND SD-CARD INSERTION

ENGLISH - 8/8
MI004930-E
t
Technical support
Product Informations
CONTACTS
ORDER CODES
Code
Description
OPTIONS
EXAMPLE:
«MY2B-R-0-M-G» MyALARM2-3 Base with two relay outputs, push-wire terminals and grey case.
RELAYS
0=Absent
R=Present
COLOR
B=Blue
G=Grey
TYPE
B=Base
S=Security
MY2 B S - 0 R - 0 - M - B G