Sens MicroGenius User manual

GREEN FLASH - Battery is charging in either Boost (steady flash LED) or Refresh mode
(2x short flash LED)
GREEN - Maintaining battery in Eco-float mode.
RED/YELLOW - Battery is connected backwards. Correct connections and retry.
YELLOW - Charger in initial power-on sequence.
RED - No charger output. Verify battery and source voltage are connected.
GREEN/YELLOW - Overvoltage Protection, charger will return to normal operation once
externally caused over voltage condition is removed.
OFF - AC source not connected. Verify source is connected and has proper
voltage and frequency.
Getting Started
The charger automatically starts in Boost mode at power-on or after a battery discharge. It remains in Boost mode until the
battery is fully charged. The charger then shifts to Eco-float mode to lengthen battery life. Refresh mode runs periodically to
insure that the battery remains fully charged. This cycle continues until the next discharge event.
Operation
PATENTED US 9,270,140; 9,385,556; 9,413,186; 9,509,164; 9,948,125
Battery Charger
Need Help?
CONTACT SENS CUSTOMER SERVICE:
3.98
6.46
5.65
1.46
4X
.266
3.41
NOTES:
THIS DRAWING IS FOR REFERENCE ONLY.
1.
SUPPLIED WITH 6FT AC CORD WITH NEMA 5-15 PLUG.
2.
SUPPLIED WITH 6FT DC CORD WITH RING TERMINALS.
3.
D
C
B
A
A
B
C
D
1
2
3
4
5
6
7
8
8
7
6
5
4
3
2
1
DIMENSIONS & TOLERANCES
PER ASME Y14.5 - 2009
20
B
SENS - MGLE
SHEET 1 OF 1
SENS MICROGENIUS LE OUTLINE DRAWING
8/8/2018
ERS
REV
DOCUMENT NUMBER
SIZE
DESCRIPTION
NAME
DATE
CHECKED
DRAWN
THIRD ANGLE PROJECTION
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN
INCHES
DEFAULT TOLERANCES:
ANGLES
1
TWO PLACE DECIMAL
.015
THREE PLACE DECIMAL
.005
DO NOT SCALE DRAWING
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE
PROPERTY OF STORED ENERGY SYSTEMS, LLC. ANY
REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN
PERMISSION OF STORED ENERGY SYSTEMS, LLC. IS PROHIBITED.
© STORED ENERGY SYSTEMS, LLC
1840 INDUSTRIAL CIRCLE
LONGMONT, CO 80501
303-678-7500
WWW.SENS-USA.COM
Enclosure rated IP67
Mount vertically for optimal
cooling using #8 - 1/4-20 inch or
M4 - M6 metric screws
Operating Temp -25C to +70C
• 12V, 6A full spec to +50C
• 12V, 10A and 24V, 5A full
spec to +40C
Time
12.8/25.6V
0
Current accepted
by battery
DYNAMIC BOOST
CHARGE MODE
HELIX
ECO-FLOAT
MODE
HELIX
REFRESH
MODE
14.5/29.0V
14.3/28.6V
Charger determines time in Boost
charge mode automatically
~10 hours ~2
hours
~10 hours ~2
hours
VoltageCurrent
Mounting
LEDs/Troubleshooting
GREEN - Battery is charged. Boost cycle complete, charger now in Eco-float.
YELLOW FLASH - Check battery or load. Boost mode time limit expired indicating exces-
sive load, battery capacity is too large or battery has an internal short.
RED/RED FLASH - Battery bad or disconnected. Battery voltage dropped below preset
threshold within one hour of boost termination. Verify battery
connected. Battery unable to hold charge or has an internal short.
OFF - Battery charging not yet complete.
Note - battery status updated every 100 seconds
Dimensions in inches

For information and service on any SENS product, please contact us at:
Stored Energy Systems, LLC
1840 Industrial Circle, Longmont, CO 80501 USA
1. SAVE THESE INSTRUCTIONS –This guide contains important
safety and operating instructions for MicroGenius®LE battery
chargers.
Conserver ces instructions. Ce manuel contient des instructions
importantes concernant la sécurité et le fonctionnement.
2. Use of an attachment not recommended or sold by the battery
charger manufacturer may result in a risk of fire, electric shock, or
injury to persons.
3. This charger is intended for commercial and industrial use. ONLY
TRAINED AND QUALIFIED PERSONNEL MAY INSTALL AND
SERVICE THIS UNIT.
4. To reduce risk of damage to electric plug and cord, pull by plug
rather than cord when disconnecting charger.
5. Do not operate charger with damaged cord/plug – replace charger
immediately.
6. Do not operate charger if it has received a sharp blow, been
dropped, or otherwise damaged in any way; shut off power at
the branch circuit protectors and have the unit serviced or replaced
by qualified personnel.
7. To reduce risk of electric shock, unplug charger from outlet before
attempting any maintenance or cleaning. Turning off controls will
not reduce this risk.
8. External connections to charger shall comply with the United States
Coast Guard electrical regulations (33CFR183 SUB PART I).
9. WARNING – RISK OF EXPLOSIVE GASES
9.1 WORKING IN VICINITY OF A LEAD-ACID BATTERY IS
DANGEROUS. STORAGE BATTERIES GENERATE EXPLOSIVE
GASES DURING NORMAL BATTERY OPERATION. FOR THIS
REASON, IT IS OF UTMOST IMPORTANCE THAT YOU READ
THIS DOCUMENT AND FOLLOW THE INSTRUCTIONS EACH
TIME YOU USE THE CHARGER.
IL EST DANGEREUX DE TRAVAILLER A PROXIMITÉ D’UNE
BATTERIE AU PLOMB. LES BATTERIES PRODUISENT DES
GAZ EXPLOSIFS EN SERVICE NORMAL. IL EST AUSSI
IMPORTANT DE TOUJOURS RELIRE LES INSTRUCTIONS AVANT
D’UTILISER LE CHARGEUR ET DE LES SUIVRE À LA LETTRE.
9.2 To reduce risk of battery explosion, follow these instructions and
those published by battery manufacturer and manufacturer of
any equipment you intend to use in vicinity of a battery. Review
cautionary markings on these products and on engine.
Pour réduire le risque d’explosion, lire ces instructions et celles qui
figurent sur la batterie.
10. PERSONAL PRECAUTIONS
10.1 Someone should be within range of your voice or close enough to
come to your aid when you work near a storage battery.
10.2 Have plenty of fresh water and soap nearby in case battery
electrolyte contacts skin, clothing, or eyes.
10.3 Wear complete eye protection and clothing protection. Avoid
touching eyes while working near a storage battery.
10.4 If battery electrolyte contacts skin or clothing, wash immediately
with soap and water. If electrolyte enters eye, immediately flood
the eye with running cold water for at least 10 minutes and get
medical attention immediately.
10.5 NEVER smoke or allow a spark or flame in vicinity of battery or
engine.
Ne jamais fumer près de la batterie ou du moteur et éviter toute
étincelle ou flamme nue à proximité de ces derniers.
10.6 Be extra cautious to reduce risk of dropping a metal tool onto
battery. It might spark or short circuit battery or other electrical
part that may cause explosion. Using insulated tools reduces this
risk, but will not eliminate it.
10.7 Remove personal metal items such as rings, bracelets, necklaces,
and watches when working with a storage battery. A storage
battery can produce a short circuit current high enough to weld a
ring or the like to metal, causing a severe burn.
10.8 Use charger for charging 6 and 12 cell LEAD-ACID batteries
only. It is not intended to supply power to a low voltage electrical
system other than in a starter-motor application. Do not use
battery charger for charging dry-cell batteries that are commonly
used with home appliances. These batteries may burst and cause
injuries to persons and damage to property.
Utiliser le chargeur pour charger une batterie au plomb
uniquement. Ce chargeur n’est pas conçu pour alimenter
un réseau électrique très basse tension ni pour charger des piles
sèches. Le fait d’utiliser le chargeur pour charger des piles sèches
pourrait entraîner l’éclatement des piles et causer des blessures ou
des dommages.
10.9 NEVER charge a frozen battery.
11. PREPARING BATTERY FOR CHARGE
11.1 Be sure area around battery is well ventilated while battery is
being charged.
11.2 Ensure battery terminals are clean and properly tightened. Be
careful to keep corrosion from coming in contact with eyes.
11.3 Add distilled water in each cell until battery acid reaches level
specified by battery manufacturer. Do not overfill. For a battery
without removable cell caps, such as valve regulated lead acid
batteries, carefully follow manufacturer’s recharging instructions.
11.4 Study all battery manufacturer specific precautions such as
removing or not removing cell caps while charging and
recommended rate of charge.
12. CHARGER LOCATION
12.1 Locate the charger as far away from the battery as DC cables
permit.
12.2 Never place charger directly above or below battery being
charged; gases from battery will corrode and damage charger.
12.3 Never allow battery acid to drip on charger when reading
electrolyte specific gravity or filling battery.
12.4 Do not operate charger in a closed-in area or restrict ventilation
in any way.
12.5 Do not set anything on top of the charger.
13. GROUNDING AND AC POWER CORD CONNECTION
INSTRUCTIONS – Charger should be grounded to reduce risk
of electric shock. Charger is equipped with an electric cord having
an equipment-grounding conductor and a grounding plug. The
plug must be plugged into an outlet that is properly installed and
grounded in accordance with all local codes and ordinances.
14. DANGER – Never alter AC cord or plug provided – if it will not fit
outlet, have proper outlet installed by a qualified electrician.
Improper connection can result in a risk of an electric shock.
© Stored Energy Systems, LLC 2018 101332 Rev F Date Issued: 10/9/19
IMPORTANT SAFETY INSTRUCTIONS
INSTRUCTIONS IMPORTANTES CONCERNANT LA SÉCURITÉ
Other Sens Batteries Charger manuals

Sens
Sens Q012-012 User manual

Sens
Sens TD Series Operating manual

Sens
Sens EnerGenius NRG24-20 User manual

Sens
Sens EnerGenius NRG22-20 User manual

Sens
Sens MicroGenius S2 User manual

Sens
Sens NRG12-10 User manual

Sens
Sens EnerGenius IQ2 User manual

Sens
Sens MicroGenius S4 User manual

Sens
Sens MicroGenius 2 User manual

Sens
Sens DCT Series Operating manual

Sens
Sens MicroGenius S2 User manual

Sens
Sens F3 SERIES Manual

Sens
Sens F3 SERIES Manual

Sens
Sens EnerGenius DC COMPACT User manual

Sens
Sens EnerGenius NRG24-10 User manual

Sens
Sens MicroGenius 2 User manual

Sens
Sens EnerGenius DC Wallbox User manual

Sens
Sens EnerGenius NRG12-20 User manual

Sens
Sens FC Operating manual