manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Controllers
  8. •
  9. Siemens RWD44U User guide

Siemens RWD44U User guide

RWD Controllers
Application Guide
Quick Reference
Document No. 125-3511
March 28, 2005
RWD44U/45U/62U/68U/82U
The RWD Controllers have standard, pre-configured applications. The respective application and setting parameters
are entered via push buttons on the controller or a software tool. See the individual Application Guides (available
online) or the Installation and Commissioning Guide for additional information. Use Tables 1 through 12 to determine
the appropriate controller model and application number.
Example: Select an application that controls two stages of electric heat and two stages of digital cooling, and
includes remote setpoint and an alarm to signal dirty air filters.
1. Select a controller based on the number of outputs and characteristics required. In this example, four digital
outputs are required. Select the RWD44U Controller (see Table 1).
Table 1. Controller Models.
Outputs
Controller Model Analog 0 to 10 Vdc Digital
RWD82U 0 2
RWD62U 2 0
RWD68U 1 1
RWD44U 0 4
RWD45U 1 4
2. Determine the main control loop. Select an application number based on the output characteristics. For the
RWD44U Controller, main control loop 1X (application group 10 through 19) contains the output characteristics
that match this example (see Table 3).
3. Determine the auxiliary control loop. In this example, an auxiliary control loop (X1) is required to readjust the
setpoint remotely (see Table 4).
The controller model and application number needed for this example is RWD44U, Application #11.
Table 2. Legend.
Digital Output (DO)
cooling
RV Reversing valve cooling Analog control loop, DA
Digital Output (DO)
heating
RV Reversing valve heating Analog control loop, RA
Siemens Building Technologies, Inc.
Application Guide Quick Reference RWD Controllers 44U/45U/62U/68U
Document Number 125-3511
March 28, 2005
Table 3. RWD44U Controller Application Numbers.
Main Loop
H = Heating
C = Cooling
Cr = Compressor
RV = Reversing valve
RV
RV
Auxiliary Loop #1x (2H & 2C) #2x (3-stage Cr + RV cool) # 3x (3-stage Cr + RV heat)
#x0 (Standby) #10 #20 #30
#x1 (Remote setpoint) #11 #21 #31
#x2 (Alarm) #12 #22 #32
#x3 (Filter alarm) #13 #23 #33
#x4 (Comp. shift) #14 #24 #34
#x5 (Avg. X1, X2) #15 #25 #35
#x6 (Win/Sum digital) #16 #26 #36
#x7 (Win/Sum analog) #17 #27 #37
#x8 (Sensor select) #18 #28 #38
#x9 (Active input) #19 #29 #39
Table 4. RWD44U Controller Input Configurations – X1, X2, and D1.
Applications 10 Through 39
D1 Options
X1
X2 Filter Alarm Alarm Day/Night Standby
#x0 (Standby) Main Standby ♦♦♦–
#x1 (Remote setpoint) Main Remote setpoint ♦♦♦♦
#x2 (Alarm) Main Alarm ♦– ♦♦
#x3 (Filter alarm) Main Filter alarm – ♦♦♦
#x4(Comp. Shift) Main Compensation ♦♦♦♦
#x5 (Avg. X1, X2) Main Main ♦♦♦♦
#x6 (Win/Sum Digital) Main Win/Sum ♦♦♦♦
#x7 (Win/Sum Analog) Main Win/Sum ♦♦♦♦
#x8 (Sensor select) Main Main ♦♦♦♦
#x9 (Active input) Main Standby
♦♦♦–
Table 5. RWD44U Controller Output Configurations – Digital Outputs Q1, Q2, Q3, and Q4.
Application
Numbers
Q1 Q2 Q3 Q4
10 through 19 Heating Stage 2 (H2) Heating Stage 1 (H1) Cooling Stage 1 (C1) Cooling Stage 2 (C2)
20 through 29
30 through 39 Reversing Valve (RV) Compressor Stage 1 (Cr1) Compressor Stage 2 (Cr2) Compressor Stage 3 (Cr3)
Page 2 Siemens Building Technologies, Inc.
RWD44U/45U/62U/68U/82U Controllers Application Guide Quick Reference
Document Number 125-3511
March 28, 2005
Table 6. RWD45U Controller Application Numbers.
Main LoopH = Heating
C = Cooling
Cr = Compressor
RV = Reversing valve
Eco = Economy
RV
RV
Auxiliary Loop #1x (2H2C + Eco Cool) #2x (3-stage Cr + RV cool + Eco Cool) # 3x (3-stage Cr + RV heat + Eco Cool)
#x0 (Standby) #10 #20 #30
#x1 (Remote setpoint) #11 #21 #31
#x2 (Alarm) #12 #22 #32
#x3 (Filter alarm) #13 #23 #33
#x4 (Comp. shift) #14 #24 #34
#x5 (Avg. X1, X2) #15 #25 #35
#x6 (Win/Sum Digital) N/A N/A N/A
#x7 (Win/Sum Analog) N/A N/A N/A
#x8 (Sensor select) #18 #28 #38
#x9 (Active input) #19 #29 #39
Main LoopH = Heating
C = Cooling
Cr = Compressor
RV = Reversing valve
Eco = Economy
RV
RV
Auxiliary Loop #4x (2H2C + Eco Heat) #5x (3-stage Cr + RV cool + Eco Heat) #6x (3-stage Cr + RV heat + Eco Heat)
#x0 (Standby) #40 #50 #60
#x1 (Remote setpoint) #41 #51 #61
#x2 (Alarm) #42 #52 #62
#x3 (Filter alarm) #43 #53 #63
#x4 (Comp. shift) #44 #54 #64
#x5 (Avg. X1, X2) #45 #55 #65
#x6 (Win/Sum Digital) N/A N/A N/A
#x7 (Win/Sum Analog) N/A N/A N/A
#x8 (Sensor select) #48 #58 #68
#x9 (Active input) #49 #59 #69
Main LoopH = Heating
C = Cooling
Cr = Compressor
RV = Reversing valve
Ind = Independent
RV
RV
Auxiliary Loop #7x (2H2C + Ind Y) #8x (3-stage Cr + RV cool + Ind Y) #9x (3-stage Cr + RV heat + Ind Y)
#x0 (Standby) #70 #80 #90
#x1 (Remote setpoint) #71 #81 #91
#x2 (Alarm) #72 #82 #92
#x3 (Filter alarm) #73 #83 #93
#x4 (Comp. shift) #74 #84 #94
#x5 (Avg. X1, X2) #75 #85 #95
#x6 (Win/Sum Digital) #76 #86 #96
#x7 (Win/Sum Analog) #77 #87 #97
#x8 (Sensor select) #78 #88 #98
#x9 (Active input) #79 #89 #99
NOTE: The dotted lines indicate that the applications can be configured for either reverse or direct acting.
Siemens Building Technologies, Inc. Page 3
Application Guide Quick Reference RWD Controllers 44U/45U/62U/68U
Document Number 125-3511
March 28, 2005
Table 7. RWD45U Controller Input Configurations – X1, X2, X3 and D1.
Applications 10 Through 69
D1 Options
X1
X2
X3 Filter
Alarm
Alarm Day/Night Standby
#x0 (Standby) Main Standby Eco ♦♦♦–
#x1 (Remote
setpoint)
Main Remote setpoint Eco ♦♦♦♦
#x2 (Alarm) Main Alarm Eco ♦– ♦♦
#x3 (Filter alarm) Main Filter alarm Eco – ♦♦♦
#14, 24, 34 (Comp.
Shift) *
Main Comp. + Eco
(cool)
Standby ♦♦♦–
#44, 54, 64 (Comp.
Shift)
Main Comp. Eco
(heat)
♦♦♦♦
#x5 (Avg. X1, X2) Main Main Eco ♦♦♦♦
#x6 (Win/Sum
Digital)
N/A N/A N/A – – – –
#x7 (Win/Sum
Analog)
N/A N/A N/A – – – –
#x8 (Sensor select) Main Main Eco ♦♦♦♦
#x9 (Active input) Main Standby Eco ♦♦♦–
* For Applications 14, 24, and 34, the X2 sensor (outside air temperature) is used for both economizer and compensation shift.
Applications 70 Through 99
D1 Options
X1
X2
X3 Filter
Alarm
Alarm Day/Night Standby
#x0 (Standby) Main Standby Ind ♦♦♦–
#x1 (Remote
setpoint)
Main Remote setpoint Ind ♦♦♦♦
#x2 (Alarm) Main Alarm Ind ♦– ♦♦
#x3 (Filter alarm) Main Filter alarm Ind – ♦♦♦
#x4 (Comp. Shift) Main Comp. Ind ♦♦♦♦
#x5 (Avg. X1, X2) Main Main Ind ♦♦♦♦
#x6 (Win/Sum
Digital)
Main Win/Sum digital Ind ♦♦♦♦
#x7 (Win/Sum
Analog)
Main Win/Sum analog Ind ♦♦♦♦
#x8 (Sensor select) Main Main Ind ♦♦♦♦
#x9 (Active input) Main Standby Ind ♦♦♦–
Page 4 Siemens Building Technologies, Inc.
RWD44U/45U/62U/68U/82U Controllers Application Guide Quick Reference
Document Number 125-3511
March 28, 2005
Table 8. RWD 45U Controller Output Configurations – Digital Outputs Q1, Q2, Q3, Q4, and Y1.
Application
Numbers
Q1 Q2 Q3 Q4 Y1
10 through 19 Eco Cool
40 through 49 Eco Heat
70 through 79
Heating Stage 2 (H2) Heating Stage 1 (H1) Cooling Stage 1 (C1) Cooling Stage 2 (C2)
Ind
Application
Numbers
Q1 Q2 Q3 Q4 Y1
20 through 29 Reversing Valve (RV)
Cool
30 through 39 Reversing Valve (RV)
Heat
Eco Cool
50 through 59 Reversing Valve (RV)
Cool
60 through 69 Reversing Valve (RV)
Heat
Eco Heat
80 through 89 Reversing Valve (RV)
Cool
90 through 99 Reversing Valve (RV)
Heat
Compressor Stage 1
(Cr1)
Compressor Stage 2
(Cr2)
Compressor Stage 3
(Cr3)
Ind
Table 9. RWD62U Controller Application Numbers.
Main Loop
H = Heating
C = Cooling
SP = Setpoint
(First digit =
Main control loop
Second digit = Auxiliary
control loop) SP
SP
SP SP
SP
SP
Auxiliary Loop #1 ×
H Sequence
#2 ×
H + H
Sequences
# 3 ×
H + C Sequences
#4 ×
C Sequence
#5 ×
C + C
Sequences
#x0 (No auxiliary) #10 #20 #30 #40 #50
#x1 (Remote setpoint) #11 #21 #31 #41 #51
#x2 (Absolute limiter) #12 #22 #32 #42 #52
#x3 (Relative limiter) #13 #23 #33 #43 #53
#x4 (Comp. shift) #14 #24 #34 #44 #54
#x5 (Cascade) #15 #25 #35 #45 #55
#x6 (Win/Sum Digital) #16 #26 #36 – –
#x7 (Win/Sum Analog) #17 #27 #37 – –
#x8 (Maximum priority) – – #38 #48 #58
#x9 Main loop (Active input) #19 #29 #39 #49 #59
NOTES:
1. The heating sequence output is set to Direct Acting (default). This is typically used for normally open valves.
Output can be set to reverse acting by changing the MIN and MAX value.
2. The cooling sequence output is set to Direct Acting (default). This is typically used for normally closed valves.
Output can be set to reverse acting by changing the MIN and MAX value.
Siemens Building Technologies, Inc. Page 5
Application Guide Quick Reference RWD Controllers 44U/45U/62U/68U
Document Number 125-3511
March 28, 2005
Table 10. RWD68U Controller Application Numbers.
H = Heating,
C = Cooling,
(1st digit = Main Control
Loop,
2nd digit = Auxiliary
Control Loop)
Main
Loop
Auxiliary Loop #1x
H
Sequence
#2x
H + H
Dependent
#3x
H + H
Independent
#4x
Digital H +
Analog C
#5x
Analog H +
Digital C
#6x
C + C or
D + D
Dependent
#7x
C + C
Independent
#8x
C
Sequence
#x0 No auxiliary #10 #20 #30 #40 #50 #60 #70 #80
#x1 Remote setpoint #11 #21 #31 #41 #51 #61 #71 #81
#x2 Absolute limiter #12 #22 #32 #42 #52 #62 #72 #82
#x3 Relative limiter #13 #23 #33 #43 #53 #63 #73 #83
#x4 Compensation shift #14 #24 #34 #44 #54 #64 #74 #84
#x5 Cascade - #25 #35 #45 #55 #65 #75 -
#x6 Win/Sum digital #16 - #36 #46 #56 - - -
#x7 Win/Sum analog #17 - #37 #47 #57 - - -
#x8 Max. priority - - - #48 - #68 #78 -
#x9 Main loop (active
input)
#19 #29 #39 #49 #59 #69 #79 #89
NOTES:
1. The analog heating sequence output is set to Direct Acting (default). This is typically used for normally open valves.
Output can be set to reverse acting by changing the MIN and MAX value.
2. The analog cooling sequence output is set to Direct Acting (default). This is typically used for normally closed valves.
Output can be set to reverse acting by changing the MIN and MAX value.
Table 11. RWD82U Controller Application Numbers.
H = Heating
C = Cooling
3P = 3-position
(1st digit = Main Control
Loop, 2nd digit =
Auxiliary Control Loop)
Main
Loop
Auxiliary Loop #1x
H + H
Dependent
#2x
H + H
Independent
#3x
H
3-Position
#4x
H + C
#5x
C + C
Dependent
#6x
C + C
Independent
#7x
C
3-Position
#x0 No auxiliary #10 #20 #30 #40 #50 #60 #70
#x1 Remote Setpoint #11 #21 #31 #41 #51 #61 #71
#x2 Absolute limiter #12 #22 #32 #42 #52 #62 #72
#x3 Relative limiter #13 #23 #33 #43 #53 #63 #73
#x4 Compensation shift #14 #24 #34 #44 #54 #64 #74
#x5 Cascade – – #35 – – – #75
#x6 Win/Sum digital – #26 #36 #46 – – –
#x7 Win/Sum analog – #27 #37 #47 – – –
#x8 Max. priority – – – – – – #78
#x9 Main loop (active
input)
#19 #29 #39 #49 #59 #69 #79
NOTES:
1. The heating sequence output is set to Direct Acting (default). This is typically used for normally open valves.
Output can be set to reverse acting by changing the MIN and MAX value.
2. The cooling sequence output is set to Direct Acting (default). This is typically used for normally closed valves.
Output can be set to reverse acting by changing the MIN and MAX value.
Page 6 Siemens Building Technologies, Inc.
RWD44U/45U/62U/68U/82U Controllers Application Guide Quick Reference
Document Number 125-3511
March 28, 2005
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as
design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners.
© 2005 Siemens Building Technologies, Inc.
Siemens Building Technologies, Inc.
1000 Deerfield Parkway
Your feedback is important to us. If you have
comments about this document, please send them to
Table 12. RWD62U/68U/82U PS 3 Auxiliary Function Parameter Set-up.
Auxiliary Number:
Parameter Description #x1
REM
#x2
LIM
#x3
LIM
#x4
COMP
#x5
CAS
#x6
WIN/SUM
#x7
WIN/SUM
XDZ Dead zone or offset (refer to the above explanation) x
MAX Value to start Limiter cooling x x
MIN Value to start Limiter heating x x
XP-h P-band in Limiter heating x x
XP-c P-band in Limiter cooling x x
TN-h Integrating time heating x x x
TN-c Integrating time cooling x x x
COMP start point heating/reverse acting x
COMP end point heating/reverse acting x
Adjustment in heating/reverse acting x
COMP start point cooling/direct acting x
COMP end point cooling/direct acting x
Adjustment in cooling/direct acting x
MAX Maximum of virtual setpoint x
MIN Minimum of virtual setpoint x
XPh1 First heating/reverse acting P-band in Cascade x
XPc1 First cooling/direct acting P-band in Cascade x
WIN As X2 < WIN, Y1 is reverse acting x
SUM As X2 > SUM, Y1 is direct acting x
T Time elapsed to allow next winter/summer
changeover (Y1 only)
x x
There are no auxiliary function parameters for Applications #x8 and #x9.
Buffalo Grove, IL 60089-4513
U.S.A.
[email protected] Page 7 of 7
Document No. 125-3505
Country of Origin: US

Other manuals for RWD44U

1

This manual suits for next models

5

Other Siemens Controllers manuals

Siemens Synco 700 Series Operator's manual

Siemens

Siemens Synco 700 Series Operator's manual

Siemens SIRIUS M200D User manual

Siemens

Siemens SIRIUS M200D User manual

Siemens SKD32 Series User manual

Siemens

Siemens SKD32 Series User manual

Siemens RWD32S User manual

Siemens

Siemens RWD32S User manual

Siemens RXB39.1 User manual

Siemens

Siemens RXB39.1 User manual

Siemens Stratos Outstation Guide

Siemens

Siemens Stratos Outstation Guide

Siemens 3RA2220 User manual

Siemens

Siemens 3RA2220 User manual

Siemens GEB 4 Series User manual

Siemens

Siemens GEB 4 Series User manual

Siemens Stratos Outstation User manual

Siemens

Siemens Stratos Outstation User manual

Siemens SIMATIC S7-1200 User manual

Siemens

Siemens SIMATIC S7-1200 User manual

Siemens RCM-1 Service manual

Siemens

Siemens RCM-1 Service manual

Siemens OpenAir GBB Series Installation guide

Siemens

Siemens OpenAir GBB Series Installation guide

Siemens WS 720 A User manual

Siemens

Siemens WS 720 A User manual

Siemens ST950ELV User manual

Siemens

Siemens ST950ELV User manual

Siemens SKP Series Owner's manual

Siemens

Siemens SKP Series Owner's manual

Siemens SINAMICS G120 User manual

Siemens

Siemens SINAMICS G120 User manual

Siemens 5WG1 536-1DB51 User manual

Siemens

Siemens 5WG1 536-1DB51 User manual

Siemens SIMATIC NET MOBIC T8 User manual

Siemens

Siemens SIMATIC NET MOBIC T8 User manual

Siemens SSC61.5U User manual

Siemens

Siemens SSC61.5U User manual

Siemens RWD62U Owner's manual

Siemens

Siemens RWD62U Owner's manual

Siemens SIRIUS 3RW44 User guide

Siemens

Siemens SIRIUS 3RW44 User guide

Siemens SQL36E65 User manual

Siemens

Siemens SQL36E65 User manual

Siemens RVL482 User manual

Siemens

Siemens RVL482 User manual

Siemens Sirius 3RW44 V.6.2 User manual

Siemens

Siemens Sirius 3RW44 V.6.2 User manual

Popular Controllers manuals by other brands

Allen-Bradley Micro800 installation instructions

Allen-Bradley

Allen-Bradley Micro800 installation instructions

RKC INSTRUMENT THW-3 Series quick start guide

RKC INSTRUMENT

RKC INSTRUMENT THW-3 Series quick start guide

DPS NetGuardian 864 quick start guide

DPS

DPS NetGuardian 864 quick start guide

Hitron FASTRAX II instruction manual

Hitron

Hitron FASTRAX II instruction manual

Omega Engineering CN9400 user guide

Omega Engineering

Omega Engineering CN9400 user guide

Top Gun APOLLO user manual

Top Gun

Top Gun APOLLO user manual

Endress+Hauser Liquiline CM442 operating instructions

Endress+Hauser

Endress+Hauser Liquiline CM442 operating instructions

ABB ACQ810-04 Hardware manual

ABB

ABB ACQ810-04 Hardware manual

Hama 00054682 quick guide

Hama

Hama 00054682 quick guide

JLL 2000 Series user manual

JLL

JLL 2000 Series user manual

DAYLIFF PVm015 Installation & operating manual

DAYLIFF

DAYLIFF PVm015 Installation & operating manual

Omron C200H-MC221 - Operation manual

Omron

Omron C200H-MC221 - Operation manual

Johnson Controls VA-77 Series Product bulletin

Johnson Controls

Johnson Controls VA-77 Series Product bulletin

ABL eMS home user manual

ABL

ABL eMS home user manual

Welker IR-1 Installation, operation & maintenance manual

Welker

Welker IR-1 Installation, operation & maintenance manual

Sonos 200 Convertible Technical specifications

Sonos

Sonos 200 Convertible Technical specifications

Digitrax UT4 Series instruction manual

Digitrax

Digitrax UT4 Series instruction manual

Danfoss AK-CC 550A user guide

Danfoss

Danfoss AK-CC 550A user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.