Error codes
In case of an actuator malfunction or communication error with the Smart Thermostat, an
error code is shown on the display of the SSA911.01TH.
Error codes cannot be acknowledged on the SSA911.01TH. The error code is shown on the
display for as long as the error is active and will disappear once normal status has been
reached.
Error notifications are also sent to the Smart Thermostat and shown on the Smart
Thermostat display. E53 is at first only shown on SSA911.01TH and not immediately shown
on the Smart Thermostat. It will take some time to appear on the Smart Thermostat.
Code Error Cause Measures
Automatic
adaptation failed
ƔThe actuator did not correctly adapt to the valve
or could not detect the end positions of the valve
ƔThe actuator is not connected to a radiator valve
ƔCheck the valve type and stroke
compatibility with the SSA911.01TH and
repeat the adaptation
ƔCheck the mechanical valve connection,
adjust, and repeat the adaption
ƔEnsure that the valve is working correctly
and that the valve stem is not stuck and
repeat the adaptation
Mechanical valve
actuator error
ƔThe movement of the actuator was too short to
detect the end positions of the valve
ƔMotor movement failure
ƔThe actuator is not connected to a radiator valve
ƔThe stroke and/or end positions of the valve are
not compatible with the SSA911.01TH
No controller
found –pairing
failed
ƔNo RDS110.R or RCR114.1 is available to
connect
ƔThe Smart Thermostat is out of range
ƔRF chip failure
ƔCheck and adjust the settings on Smart
Thermostat and re-start the pairing
process
ƔDecrease the distance between the
SSA911.01TH and the Smart
Thermostat and re-start the pairing
process
Connection to
Smart Thermostat
lost
ƔThe current connection to the Smart Thermostat
is not available anymore (RF chip failure)
ƔThe paired RDS110.R or RCR114.1 is not
available anymore (e.g. loss of power)
ƔThe Smart Thermostat is out of range
ƔCheck the power supply and availability
of the Smart Thermostat
ƔDecrease the distance between the
SSA911.01TH and the Smart
Thermostat
No new pairing process is required
to resolve E53. The SSA911.01TH
will automatically re-
Smart Thermostat once the
network is available again.