  9. Siemens SIPROTEC 5 Operating and installation instructions

Siemens SIPROTEC 5 Operating and installation instructions

Technical Data
Extract from manual C53000-G5040-C002-F, chapter 6
Smart Infrastructure
SIPROTEC 5 V7.90 and higher
Hardware
Cover_TD_C002_enUS.fm Page 1 Monday, June 17, 2019 12:16 PM
i
i
NOTE
For your own safety, observe the warnings and safety instructions contained in this document, if available.
Disclaimer of Liability
Subject to changes and errors. The information given in
this document only contains general descriptions and/or
performance features which may not always specifically
reflect those described, or which may undergo modifica-
tion in the course of further development of the products.
The requested performance features are binding only when
they are expressly agreed upon in the concluded contract.
Document version: C53000-G5040-C002-F.05
Edition: 06.2019
Version of the product described: V7.90 and higher
Copyright
Copyright © Siemens 2019. All rights reserved.
The disclosure, duplication, distribution and editing of this
document, or utilization and communication of the content
are not permitted, unless authorized in writing. All rights,
including rights created by patent grant or registration of a
utility model or a design, are reserved.
Trademarks
SIPROTEC™, DIGSI™, SIGRA™, SIGUARD™, SAFIR™, SICAM™,
and MindSphere™ are trademarks of Siemens AG. Any
unauthorized use is prohibited. All other designations in
this document may represent trademarks whose use by
third parties for their own purposes may violate the propri-
etary rights of the owner.
Preface
Purpose of the Manual
This manual describes the hardware of the SIPROTEC 5 device family and provides general information on the
product structure, the modules and technical data.
Target Audience
Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and main-
tenance of automation, selective protection and control equipment, and operational crew in electrical installa-
tions and power plants.
Scope
This manual applies to the SIPROTEC 5 device family.
Further Documentation
[dwprefhw-221012-01.tif, 3, en_US]
•Device manuals
Each Device manual describes the functions and applications of a specific SIPROTEC 5 device. The printed
manual and the online help for the device have the same informational structure.
•Hardware manual
The Hardware manual describes the hardware building blocks and device combinations of the SIPROTEC 5
device family.
•Operating manual
The Operating manual describes the basic principles and procedures for operating and assembling the
devices of the SIPROTEC 5 range.
SIPROTEC 5, Hardware Description, Manual 3
C53000-G5040-C002-F, Edition 06.2019
•Communication protocol manual
The Communication protocol manual contains a description of the protocols for communication within
the SIPROTEC 5 device family and to higher-level network control centers.
•Product information
The Product information includes general information about device installation, technical data, limiting
values for input and output modules, and conditions when preparing for operation. This document is
provided with each SIPROTEC 5 device.
•Engineering Guide
The Engineering Guide describes the essential steps when engineering with DIGSI 5. In addition, the Engi-
neering Guide shows you how to load a planned configuration to a SIPROTEC 5 device and update the
functionality of the SIPROTEC 5 device.
•DIGSI 5 online help
The DIGSI 5 online help contains a help package for DIGSI 5 and CFC.
The help package for DIGSI 5 includes a description of the basic operation of software, the DIGSI princi-
ples and editors. The help package for CFC includes an introduction to CFC programming, basic examples
of working with CFC, and a reference chapter with all the CFC blocks available for the SIPROTEC 5 range.
•SIPROTEC 5/DIGSI 5 Tutorial
The tutorial on the DVD contains brief information about important product features, more detailed infor-
mation about the individual technical areas, as well as operating sequences with tasks based on practical
operation and a brief explanation.
•SIPROTEC 5 catalog
The SIPROTEC 5 catalog describes the system features and the devices of SIPROTEC 5.
•Selection guide for SIPROTEC and Reyrolle
The selection guide offers an overview of the device series of the Siemens protection devices, and a
device selection table.
Indication of Conformity
This product complies with the directive of the Council of the European Communities
on harmonization of the laws of the Member States concerning electromagnetic
compatibility (EMC Directive 2014/30/EU), restriction on usage of hazardous
substances in electrical and electronic equipment (RoHS Directive 2011/65/EU), and
electrical equipment for use within specified voltage limits (Low Voltage Directive
2014/35/EU).
This conformity has been proved by tests performed according to the Council Directive
in accordance with the product standard EN 60255-26 (for EMC directive), the standard
EN 50581 (for RoHS directive), and with the product standard EN 60255-27 (for Low
Voltage Directive) by Siemens.
The device is designed and manufactured for application in an industrial environment.
The product conforms with the international standards of IEC 60255 and the German
standard VDE 0435.
Standards
IEEE Std C 37.90
The technical data of the product is approved in accordance with UL.
For more information about the UL database, see ul.com
You can find the product with the UL File Number E194016.
IND. CONT. EQ.
69CA
Preface
4 SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-F, Edition 06.2019
Additional Support
For questions about the system, please contact your Siemens sales partner.
Support
Our Customer Support Center provides a 24-hour service.
Siemens AG
Customer Support Center
Humboldtstrasse 59
90459 Nuremberg
Germany
E-mail: [email protected]
Training Courses
Inquiries regarding individual training courses should be addressed to our Training Center:
Siemens AG Phone: +49 (911) 433-7415
Siemens Power Academy TD Fax: +49 (911) 433-7929
Humboldtstrasse 59 E-mail: [email protected]
90459 Nuremberg Internet: www.siemens.com/poweracademy
Germany
Notes on Safety
This document is not a complete index of all safety measures required for operation of the equipment (module
or device). However, it comprises important information that must be followed for personal safety, as well as
to avoid material damage. Information is highlighted and illustrated as follows according to the degree of
danger:
!
DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
²Comply with all instructions, in order to avoid death or severe injuries.
!
WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
²Comply with all instructions, in order to avoid death or severe injuries.
!
CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
²Comply with all instructions, in order to avoid moderate or minor injuries.
Preface
SIPROTEC 5, Hardware Description, Manual 5
C53000-G5040-C002-F, Edition 06.2019
NOTICE
NOTICE means that property damage can result if the measures specified are not taken.
²Comply with all instructions, in order to avoid property damage.
i
i
NOTE
Important information about the product, product handling or a certain section of the documentation
which must be given particular attention.
Qualified Electrical Engineering Personnel
Only qualified electrical engineering personnel may commission and operate the equipment (module, device)
described in this document. Qualified electrical engineering personnel in the sense of this manual are people
who can demonstrate technical qualifications as electrical technicians. These persons may commission,
isolate, ground and label devices, systems and circuits according to the standards of safety engineering.
Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:
•Proper transport
•Proper storage, setup and installation
•Proper operation and maintenance
When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper
action is not taken, death, severe injury or property damage can result:
•The equipment must be grounded at the grounding terminal before any connections are made.
•All circuit components connected to the power supply may be subject to dangerous voltage.
•Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).
•Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.
•The limiting values stated in the document must not be exceeded. This must also be considered during
testing and commissioning.
Used Symbols on Device
No. Symbol Description
1 Direct current, IEC 60417-5031
2 Alternating current, IEC 60417-5032
3 Direct and alternating current, IEC 60417-5033
4 Earth (ground) terminal, IEC 60417-5017
5 Protective conductor terminal, IEC 60417-5019
Preface
6 SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-F, Edition 06.2019
No. Symbol Description
6 Caution, risk of electric shock
7 Caution, risk of danger, ISO 7000-0434
8 Protective Insulation, IEC 60417-5172, Safety Class II devices
9 Guideline 2002/96/EC for electrical and electronic devices
10 Guideline for the Eurasian Market
Preface
SIPROTEC 5, Hardware Description, Manual 7
C53000-G5040-C002-F, Edition 06.2019
Open Source Software
The product contains, among other things, Open Source Software developed by third parties. The Open
Source Software used in the product and the license agreements concerning this software can be found in the
Readme_OSS. These Open Source Software files are protected by copyright. Your compliance with those
license conditions will entitle you to use the Open Source Software as foreseen in the relevant license. In the
event of conflicts between Siemens license conditions and the Open Source Software license conditions, the
Open Source Software conditions shall prevail with respect to the Open Source Software portions of the soft-
ware. The Open Source Software is licensed royalty-free. Insofar as the applicable Open Source Software
License Conditions provide for it you can order the source code of the Open Source Software from your
Siemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years
since purchase of the Product. We are liable for the Product including the Open Source Software contained in
it pursuant to the license conditions applicable to the Product. Any liability for the Open Source Software
beyond the program flow intended for the Product is explicitly excluded. Furthermore any liability for defects
resulting from modifications to the Open Source Software by you or third parties is excluded. We do not
provide any technical support for the Product if it has been modified.
When using DIGSI 5 in online mode, you are provided with the option to go to the main menu Show open
source software information and read and display the Readme_OSS file containing the original license text
and copyright information.
To do this, the following steps are necessary:
•Switch to online mode.
•Select the device.
•Select Online in the menu bar.
•Click Show open source software information.
i
i
NOTE
To read the Readme_OSS file, a PDF viewer must be installed on the computer.
In order to operate SIPROTEC 5 devices, a valid DIGSI 5 license is required.
SIPROTEC 5, Hardware Description, Manual 9
C53000-G5040-C002-F, Edition 06.2019
Technical Data
6.1 Analog Inputs 206
6.2 Supply Voltage 209
6.3 Binary Inputs 211
6.4 Relay Outputs 213
6.5 Light-Emitting Diodes in the On-Site Operation Panel 216
6.6 Communication Interfaces 217
6.7 Electrical Tests 220
6.8 Mechanical Tests 223
6.9 Environmental Conditions 224
6.10 Operating Conditions 226
6.11 Reference Conditions and Influencing Variables 227
6.12 Approvals 228
6.13 Design Data 229
6.14 Assembly Dimensions 232
6.15 Modular Device Name Plate 253
6.16 Name Plate of Non-Modular Devices (7xx81, 7xx82) 254
6.17 Name Plate, UL Approval, Base Module and 1/3 Base Module 255
6.18 Name Plate, UL Approval, Expansion Module 256
6.19 Battery 257
6.20 SDHC Memory Card 258
6.21 Display Resolution 259
6
SIPROTEC 5, Hardware Description, Manual 205
C53000-G5040-C002-F, Edition 06.2019
Analog Inputs
Current Inputs
All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
16.7 Hz (for rail protection devices only)
Protection-class current trans-
formers
Rated current Irated Measuring range of
the modular devices
Measuring range of the
non-modular devices
5 A
1 A
0 A to 500 A
0 A to 100 A
0 A to 250 A
0 A to 50 A
Instrument transformers 5 A
1 A
0 A to 8 A
0 A to 1.6 A
0 A to 8 A
0 A to 1.6 A
Burden for rated current Approx. 0.1 VA
Thermal rating
(protection and instrument trans-
formers)
20 A continuously
25 A for 3 min
30 A for 2 min
150 A for 10 s
500 A for 1 s
Dynamic load-carrying capacity 1250 A one half wave
Voltage Input
All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
16.7 Hz (for rail devices only)
Input and output modules IO102, IO202, IO208, IO211,
IO214
IO215
Measuring range 0 V to 200 V 0 V to 7.07 V
Burden < 0.1 VA < 0.01 VA
Thermal rating 230 V continuously 20 V continuously
i
i
NOTE
You can find more information on the technical data of the current and voltage transformers in the
SIPROTEC 5 Device manuals in the Technical Data chapter.
Measuring-Transducer Inputs (via Module ANAI-CA-4EL)
Insulation class SELV (Safety Extra Low Voltage) (according to IEC 60255-27)
Connector type 8-pin terminal spring
Differential current input channels 4
Measuring range DC -25.6 mA to +25.6 mA
Fault < 0.5 % of the measuring range
Input impedance 140 Ω
Conversion principle Delta-sigma (16 bit)
Permissible potential difference
between channels
DC 20 V
Galvanic separation from ground/
housing
DC 700 V
Permissible overload DC 100 mA continuously
6.1
Technical Data
6.1 Analog Inputs
206 SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-F, Edition 06.2019
Measured-value repetition 200 ms
Inputs for Optical Sensors for Arc Protection (via Module ARC-CD-3FO)
Connector type AVAGO AFBR-4526Z
Number of transceivers 3
Fiber type Polymer Optical Fiber (POF) 1 mm
Receiver
Maximum -10 dBm ± 2 dBm
Minimum -40 dBm ± 2 dBm
Spectrum 400 nm to 1100 nm
Attenuation In the case of plastic optical fibers, you can expect a path attenuation of
0.2 dB/m. Additional attenuation comes from the plug and sensor head.
Optical budget14 Minimal 25 dB
Analog sampling rate 16 kHz
ADC type 10-bit successive approximation
Transmitter
Type LED
Wavelength λ = 650 nm
Transmitter power Minimum 0 dBm
Maximum 2 dBm
Numerical aperture 0.5 15
Signal rate connection test 1 pulse per second
Pulse duration connection test 11 μs
High-Speed Measuring-Transducer Inputs, Voltage/Current (via IO210, IO212)
i
i
NOTE
Current and voltage must not be connected at the same time to one measuring-transducer input. Instead,
only connect either current or voltage. For EMC reasons, do not connect a line to an unused input (current
or voltage).
Use shielded cables.
Table 6-1 High-Speed Measuring-Transducer Inputs, Voltage
Differential voltage input channels IO210: 416
IO212: 817
Measuring range DC -10 V to +10 V
Fault < 0.5 % of the measuring range
Input impedance 48 kΩ
Max. permissible voltage with
respect to ground on the meas-
uring inputs
300 V
Permissible overload DC 20 V continuously
DC 60 V continuously (IO210 MT3 terminal point C9)
14 All values in combination with sensors approved by Siemens.
15 Numerical aperture (NA = sin θ (launch angle))
16 The IO210 has 4 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
17 The IO212 has 8 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
Technical Data
6.1 Analog Inputs
SIPROTEC 5, Hardware Description, Manual 207
C53000-G5040-C002-F, Edition 06.2019
Table 6-2 High-Speed Measuring-Transducer Inputs, Current
Differential current input channels IO210: 418
IO212: 819
Measuring range DC -20 mA to +20 mA
Fault < 0.5 % of the measuring range
Input impedance, current 12 Ω
Permissible potential difference
between channels
DC 3.5 kV
Galvanic separation with respect to
ground/housing
DC 3.5 kV
Permissible current overload DC 100 mA continuously
Table 6-3 Common Data for the Fast Measuring-Transducer Inputs, Voltage/Current
Conversion principle Delta-sigma (16 bit)
Insulation test voltage between the
channels
DC 3.5 kV
Insulation test voltage with respect
to ground/housing
DC 3.5 kV
Measured-value repetition 62.5 μs
Insulation class IO210 ELV (Extra Low Voltage) (as per IEC 60255-27)
Insulation class IO212 SELV (as per IEC 60255-27)
i
i
NOTE
You can find more information on the measuring accuracy of the analog inputs in the SIPROTEC 5 Device
manuals in the Technical Data chapter.
Temperature Inputs
Settings Value Note
Insulation class PELV (Protective Extra Low Voltage)
(acc. to IEC 60255-27)
–
Measurement mode •Pt 100 Ω
•Ni 100 Ω
•Ni 120 Ω
3-wire connection, shielded cables
–
Connector type 16-pin, 17-pin terminal spring –
Temperature measuring range -65 °C to +710 °C For PT100
-50 °C to +250 °C For NI100
-50 °C to +250 °C For NI120
18 The IO210 has 4 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
19 The IO212 has 8 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
Technical Data
6.1 Analog Inputs
208 SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-F, Edition 06.2019
Supply Voltage
Integrated Power Supply
For modular devices, the following modules contain a power supply:
PS201 – Power supply of the base module and of the 1st device row
PS203 – Power supply of the 2nd device row
CB202 – Plug-in module assembly with integrated power supply, for example, to accommodate communica-
tion modules
Permissible voltage
ranges
(PS201, PS203, CB202)
DC 19 V to DC 60 V DC 48 V to DC 300 V
AC 80 V to AC 265 V, 50 Hz/60 Hz
Auxiliary rated voltage VH
(PS201, PS203, CB202)
DC 24 V/DC 48 V DC 60 V/DC 110 V/DC 125 V/DC 220 V/
DC 250 V or
AC 100 V/AC 115 V/AC 230 V, 50 Hz/60 Hz
Permissible voltage
ranges (PS101)
Only for non-modular
devices
DC 19 V to DC 60 V DC 48 V to 150 V DC 88 V to DC 300 V
AC 80 V to AC 265 V,
50 Hz/60 Hz
Auxiliary rated voltage VH
(PS101)
Only for non-modular
devices
DC 24 V/DC 48 V DC 60 V/DC 110 V/
DC 125 V
DC 110 V/ DC 125 V/
DC 220 V/DC 250 V
or
AC 100 V/AC 115 V/
AC 230 V, 50 Hz/60 Hz
Superimposed alternating
voltage, peak-to-peak,
IEC 60255-11,
IEC 61000-4-17
≤ 15 % of the DC auxiliary rated voltage (applies only to direct voltage)
Inrush current ≤ 18 A
Recommended external
protection
Miniature circuit breaker 6 A, characteristic C according to IEC 60898
Internal fuse
– DC 24 V to DC 48 V DC 60 V to DC 125 V DC 24 V to DC 48 V
AC 100 V to AC 230 V
PS101
Only for non-modular
devices
4 A inert, AC 250 V,
DC 150 V,
UL recognized
SIBA type 179200 or
Schurter type SPT 5x20
2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
PS201, PS203, CB202 2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
Power consumption (life relay active)
– DC AC 230 V/50 Hz AC 115 V/50 Hz
1/3 base module, non-
modular
Without plug-in modules
7 W 16 VA 12.5 VA
1/3 base module, modular
Without plug-in modules
13 W 33 VA 24 VA
1/6 expansion module 3 W 6 VA 6 VA
1/6 plug-in module
assembly without plug-in
modules (modules CB202)
3.5 W 14 VA 7 VA
6.2
Technical Data
6.2 Supply Voltage
SIPROTEC 5, Hardware Description, Manual 209
C53000-G5040-C002-F, Edition 06.2019
Integrated Power Supply
Plug-in module for base
module or plug-in module
assembly (for example,
communication module)
< 5 W < 6 VA < 6 VA
Stored-energy time for auxiliary voltage outage or
short circuit, modular devices
IEC 61000-4-11
IEC 61000-4-29
For V ≥ DC 24 V ≥ 50 ms
For V ≥ DC 110 V ≥ 50 ms
For V ≥ AC 115 V ≥ 50 ms
Stored-energy time for auxiliary voltage outage or
short circuit, non-modular devices
IEC 61000-4-11
IEC 61000-4-29
For V ≥ DC 24 V ≥ 20 ms
For V ≥ DC 60 V ≥ 50 ms
For V ≥ AC 115 V ≥ 200 ms
Technical Data
6.2 Supply Voltage
210 SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-F, Edition 06.2019
Binary Inputs
Standard Binary Input
Rated voltage range DC 24 V to 250 V
The binary inputs of SIPROTEC 5 are bipolar, with the exception of the
binary inputs on the modules IO230, IO231, and IO233.
Current consumption, excited Approx. DC 0.6 mA to 2.5 mA (independent of the control voltage)
Power consumption, max. 0.6 W
Pickup time Approx. 3 ms
Dropout time20 Capacitive load (supply-line capaci-
tance)
Dropout time
< 5 nF < 4 ms
< 10 nF < 6 ms
< 50 nF < 10 ms
< 220 nF < 35 ms
Control voltage for all modules
with binary inputs, except
module IO233
Adapt the binary-input threshold to be set in the device to the control
voltage.
Range 1 for 24 V, 48 V, and 60 V
Control voltage
Vlow ≤ DC 10 V
Vhigh ≥ DC 19 V
Range 2 for 110 V and 125 V
Control voltage
Vlow ≤ DC 44 V
Vhigh ≥ DC 88 V
Range 3 for 220 V and 250 V
Control voltage
Vlow ≤ DC 88 V
Vhigh ≥ DC 176 V
Control voltage for binary inputs of
the IO233 module
Range for 125 V
Control voltage
Vlow ≤ DC 85 V
Vhigh ≥ DC 105 V
Maximum permitted voltage DC 300 V
The binary inputs contain interference suppression capacitors. To ensure EMC immunity, use the terminals
shown in the terminal diagrams/connection diagrams to connect the binary inputs to the common potential.
Special Binary Input with Maximized Robustness against Electrical Disturbances and Failures (IO216)
Rated voltage range DC 220 V
The special binary inputs of the SIPROTEC 5 with maximized robustness
against electrical disturbances and failures are bipolar and available only
on the module IO216.
Input impedance 50 kΩ to 60 kΩ
Rejection pulse charge > 200 µC
Current consumption, excited Approx. DC 1.2 mA to 2.0 mA (additionally to the current consumption
of the input impedance)
Power consumption, max. 1.5 W at DC 242 V
Pickup time Approx. 3 ms
6.3
20 For time-critical applications with low-active signals, consider the specified dropout times. If necessary, provide for active discharge
of the binary input (for example, a resistor in parallel to the binary input or using a change-over contact).
Technical Data
6.3 Binary Inputs
SIPROTEC 5, Hardware Description, Manual 211
C53000-G5040-C002-F, Edition 06.2019
Dropout time21 Capacitive load (supply-line capaci-
tance)
Dropout time
< 5 nF < 3 ms
< 10 nF < 4 ms
< 50 nF < 5 ms
< 220 nF < 10 ms
Control voltage for the module
IO216
Range for 220 V control voltage
Threshold pickup 158 V to 170 V
Threshold dropout 132 V to 154 V
Maximum permitted voltage DC 300 V
The binary inputs contain interference suppression capacitors. To ensure EMC immunity, use the terminals
shown in the terminal diagrams/connection diagrams to connect the binary inputs to the common potential.
21 For time-critical applications with low-active signals, consider the specified dropout times. If necessary, provide for active discharge
of the binary input (for example, a resistor in parallel to the binary input or using a change-over contact).
Technical Data
6.3 Binary Inputs
212 SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-F, Edition 06.2019
Relay Outputs
Standard Relay (Type S)
Making capacity Max. 1000 W (L/R = 40 ms)
Max. 3600 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
Breaking capacity Max. 30 W (L/R = 40 ms)
Max. 360 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
AC and DC contact voltage 250 V
Permissible current per contact (continuous) 5 A
Permissible current per contact (switching on and
holding)
30 A for 1 s (make contact)
Short-time current across closed contact 250 A for 30 ms
Total permissible current for contacts connected to
common potential
5 A
Switching time OOT (Output Operating Time)
Additional delay of the output medium used
Make time: typical: 8 ms; maximum: 10 ms
Break time: typical: 2 ms; maximum: 5 ms
Max. rated data of the output contacts in accordance
with UL certification
DC 24 V, 5 A, General Purpose
DC 48 V, 0.8 A, General Purpose
DC 240 V, 0.1 A, General Purpose
AC 240 V, 5 A, General Purpose
AC 120 V, 1/6 hp
AC 250 V, 1/2 hp
B300
R300
Interference suppression capacitors across the
contacts
4.7 nF, ± 20 %, AC 250 V
Fast Relay (Type F)
Making capacity Max. 1000 W (L/R = 40 ms)
Max. 3600 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
Breaking capacity Max. 30 W (L/R = 40 ms)
Max. 360 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
AC and DC contact voltage 250 V
Permissible current per contact (continuous) 5 A
Permissible current per contact (switching on and
holding)
30 A for 1 s (make contact)
Short-time current across closed contact 250 A for 30 ms
Total permissible current for contacts connected to
common potential
5 A
Switching time OOT (Output Operating Time)
Additional delay of the output medium used
Make time: typical: 4 ms; maximum: 5 ms
Break time: typical: 2 ms; maximum: 5 ms
Rated data of the output contacts in accordance with
UL certification
DC 24 V, 5 A, General Purpose
DC 48 V, 0.8 A, General Purpose
DC 240 V, 0.1 A, General Purpose
AC 120 V, 5 A, General Purpose
AC 250 V, 5 A, General Purpose
AC 250 V, 0.5 hp
B300
R300
6.4
Technical Data
6.4 Relay Outputs
SIPROTEC 5, Hardware Description, Manual 213
C53000-G5040-C002-F, Edition 06.2019
Interference suppression capacitors across the
contacts
4.7 nF, ± 20 %, AC 250 V
Supervision 2-channel activation with cyclic testing (only for make
contact)
High-Speed Relay with Semiconductor Acceleration (Type HS)
Making capacity Max. 2500 W (L/R = 40 ms)
Max. 3600 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
Breaking capacity Max. 2500 W (L/R = 40 ms)
Max. 360 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
Contact voltage AC 200 V, DC 250 V
Permissible current per contact (continuous) 5 A (according to UL certification)
10 A (no UL certification; AWG 14 / 2.5-mm2 (0.0039-
in2) copper conductors necessary)
Permissible current per contact (switching on and
holding)
30 A for 1 s (make contact)
Short-time current across closed contact 250 A for 30 ms
Switching time OOT (Output Operating Time)
Additional delay of the output medium used
Make time, typical: 0.2 ms; maximum: 0.2 ms
Break time, typical: 9 ms; maximum: 9 ms
Rated data of the output contacts in accordance with
UL certification
B150
Q300
Power Relay (for Direct Control of Motor Switches)
Switching power for permanent and periodic operation
250 V/4.0 A
220 V/4.5 A
110 V/5.0 A
60 V/5.0 A
48 V/5.0 A
24 V/5.0 A
1000 W
1000 W
550 W
300 W
240 W
120 W
In order to prevent any damage, the external protec-
tion circuit must switch off the motor in case the rotor
is blocked.
Turn on switching power for 30 s, recovery time until switching on again is 15 minutes.
For short-term switching operations, an impulse/pause ratio of 3 % must be considered.
100 V/9.0 A
60 V/10.0 A
48 V/10.0 A
24 V/10.0 A
1000 W
600 W
480 W
240 W
Continuous and inching operation is not permitted.
In order to prevent any damage, the external protec-
tion circuit must switch off the motor in case the rotor
is blocked.
AC and DC contact voltage 250 V
Permissible continuous current per contact 5 A
Permissible current per contact (switching on and
holding)
30 A for 1 s
Short-time current across closed contact 250 A for 30 ms
Total permissible current for contacts connected to
common potential
5 A
Switching time OOT (Output Operating Time)
Additional delay of the output medium used
≤ 16 ms
Technical Data
6.4 Relay Outputs
214 SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-F, Edition 06.2019
Rated data of the output contacts in accordance with
UL certification
DC 300 V, 4.5 A - 30 s ON, 15 min OFF
DC 250 V, 1 hp motor - 30 s ON, 15 min OFF
DC 110 V, 3/4 hp motor - 30 s ON, 15 min OFF
DC 60 V, 10 A, 1/2 hp motor - 30 s ON, 15 min OFF
DC 48 V, 10 A, 1/3 hp motor - 30 s ON, 15 min OFF
DC 24 V, 10 A, 1/6 hp motor - 30 s ON, 15 min OFF
Interference suppression capacitors across the
contacts
4.7 nF, ± 20 %, AC 250 V
The power relays operate in interlocked mode, that is, only one relay of each switching pair picks up at a time
thereby avoiding a power-supply short circuit.
Technical Data
6.4 Relay Outputs
SIPROTEC 5, Hardware Description, Manual 215
C53000-G5040-C002-F, Edition 06.2019
Light-Emitting Diodes in the On-Site Operation Panel
Base Module
Status Color Quantity
RUN Green 1
ERROR Red 1
Routable (adjustable with DIGSI 5)
Only the defined color can be used
in operation.
2-colored: red or green 16
Expansion Module
Status Color Quantity
Routable Red 16 optional
6.5
Technical Data
6.5 Light-Emitting Diodes in the On-Site Operation Panel
216 SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-F, Edition 06.2019

Other manuals for SIPROTEC 5

5

Other Siemens Controllers manuals

Siemens SINUMERIK 840D sl User manual

Siemens

Siemens SINUMERIK 840D sl User manual

Siemens SIMATIC S7-200 User manual

Siemens

Siemens SIMATIC S7-200 User manual

Siemens 125-5033 User manual

Siemens

Siemens 125-5033 User manual

Siemens RWD62 User manual

Siemens

Siemens RWD62 User manual

Siemens Climatix S300 HRV User guide

Siemens

Siemens Climatix S300 HRV User guide

Siemens SIMATIC S5 User manual

Siemens

Siemens SIMATIC S5 User manual

Siemens GEB 1 Series User manual

Siemens

Siemens GEB 1 Series User manual

Siemens RMZ791 User manual

Siemens

Siemens RMZ791 User manual

Siemens QPA84 User manual

Siemens

Siemens QPA84 User manual

Siemens 7SR224 User manual

Siemens

Siemens 7SR224 User manual

Siemens OpenAir GCA Series Owner's manual

Siemens

Siemens OpenAir GCA Series Owner's manual

Siemens SINUMERIK 810D Instruction sheet

Siemens

Siemens SINUMERIK 810D Instruction sheet

Siemens 540-716 Service manual

Siemens

Siemens 540-716 Service manual

Siemens SINUMERIK 802C User manual

Siemens

Siemens SINUMERIK 802C User manual

Siemens SIMATIC ET 200SP User manual

Siemens

Siemens SIMATIC ET 200SP User manual

Siemens Simatic S7-400 Technical Document

Siemens

Siemens Simatic S7-400 Technical Document

Siemens RMH760 User manual

Siemens

Siemens RMH760 User manual

Siemens KNX RL 524D23 User manual

Siemens

Siemens KNX RL 524D23 User manual

Siemens Climatix POL822 User manual

Siemens

Siemens Climatix POL822 User manual

Siemens RAJA+ 3TE7 DOL Guide

Siemens

Siemens RAJA+ 3TE7 DOL Guide

Siemens GIB 1 Series User manual

Siemens

Siemens GIB 1 Series User manual

Siemens SIRIUS 3RA2120 Series User manual

Siemens

Siemens SIRIUS 3RA2120 Series User manual

Siemens MVI421 Series User manual

Siemens

Siemens MVI421 Series User manual

Siemens SIMATIC S7-1200 CP 1243-8 IRC User guide

Siemens

Siemens SIMATIC S7-1200 CP 1243-8 IRC User guide

Popular Controllers manuals by other brands

schmersal AZM 161 I Series operating instructions

schmersal

schmersal AZM 161 I Series operating instructions

GF EA25 instruction manual

GF

GF EA25 instruction manual

SCHIEBEL ACTUSMART CM Series operating instructions

SCHIEBEL

SCHIEBEL ACTUSMART CM Series operating instructions

Mitsubishi Electric MELSEC iQ-R Series user manual

Mitsubishi Electric

Mitsubishi Electric MELSEC iQ-R Series user manual

heat-timer SQ-Elite-8T Installation and operation manual

heat-timer

heat-timer SQ-Elite-8T Installation and operation manual

Mitsubishi Electric MELSERVO J5 Series user manual

Mitsubishi Electric

Mitsubishi Electric MELSERVO J5 Series user manual

Lexicon DC-1 Release notice

Lexicon

Lexicon DC-1 Release notice

Johnson Controls TEC3000 Series quick start guide

Johnson Controls

Johnson Controls TEC3000 Series quick start guide

Samson TROVIS 5400 Series Mounting and operating instructions

Samson

Samson TROVIS 5400 Series Mounting and operating instructions

PXM PX227 user manual

PXM

PXM PX227 user manual

Tyco iSTAR eX Installation and configuration guide

Tyco

Tyco iSTAR eX Installation and configuration guide

Lumens VS-K20 user manual

Lumens

Lumens VS-K20 user manual

Vestamatic MC P4 LoVo Installation and operating instructions

Vestamatic

Vestamatic MC P4 LoVo Installation and operating instructions

Newport ESP302 Startup manual

Newport

Newport ESP302 Startup manual

AviteQ Vibtronic SC-2 Series operating manual

AviteQ

AviteQ Vibtronic SC-2 Series operating manual

SOMFY Animeo IB+ quick start guide

SOMFY

SOMFY Animeo IB+ quick start guide

Worldsemi WS2821 manual

Worldsemi

Worldsemi WS2821 manual

Omron R88D-GT series user manual

Omron

Omron R88D-GT series user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.