Siemens Ltd.
I-IA-CECP-793
(ThisreplacesSGR-03IO-1113)
OrderNo.A5E33259242000ARevAB
Productdevelopmentisacontinuousprocess.Consequently
the data indicated in this Leaflet is subject to change without
priornotice.Forlatestissuecontactoursalesofces.
SACHINENTERPRISE
Disposal
Siemensproductareenvironmentfriendly,whichpredominantly
consist of recyclable materials.
For disposals we recommend disassembling and separation into
following materials:
METALS:SegregateintoFerrous&NonFerroustypesforrecycling
through authorised dealer.
PLASTICS:Segregateaspermaterialtypeforrecyclingthrough
authoriseddealer.BecauseofthelonglifetimeofSiemens
products the disposal guidelines may be replaced by other national
regulations when taking the product out of service.
The local customer care service is available at any time to answer
disposal-related questions
Permissible Conductor Size: Main Terminals
Termination Data - Contactor 3TS1722-0A..5-8K
Finely Stranded with ring type cable lug 1x35mm²/2x16mm²
Terminalbar(max.width) 12mm
Screw Size M6
Tightening Torque 4-6N-m
B. Installation
1. Permitted mounting positions are indicated in Fig.2
2. The unit is suitable for screw mounting on flat vertical
surfacewithtwoM4screws.Alwaysuseplainandspring
washers.
Note:Installtheunitinhousingifitisexposedtodust,dirt,
contamination or aggressive atmosphere.
E. Overall Dimensions
Dimensions in mm : 50 kVAr (3TS1722-0A .. 5-8K)
C. Maintenance
• Removedustbysuction.
• Replacementofcoilavailableasspare.
Order Code AC Coil Voltage
3TY7463-0AF0 110
3TY7463-0AP0 230
3TY7463-0AR0 415
• Sparecontactkitsavailable.
• ContactSiemensSalesofcefordetails.
• Handletheresistorwirescarefully.
D. Note:
NormallythepowerfactorcontrollerinAPFCpanels,hasthe
provision for adjustment under voltage cut out with respect
to voltage and time. Please ensure that the controllers are
present as per values given in the table below
Coil Voltage Controller settings
Under Voltage Actuating time
110V ≥94V <0.1sec
230V ≥196V <0.1sec
415V ≥353V <0.1sec
Incase,Powerfactorcontrollerdoesnothavetheprovision
ofabovesettings,itisrecommendedtoprovideaseparate
undervoltagemonitorhavingsettingsaspertable,toensure
satisfactory performance of the contactors.
Forfurtherdetailsonsuchanundervoltagemonitor,please
contactnearestSiemensofce
Fig. 2
Fig. 3