Afterenteringthecatalognumberinformation,press
the ENTER key. If an invalid catalog number has
beenentered, the TS-MD will respondwith:
and you will be asked to enter another catalog
number.
E. If a valid catalog number has been entered, the
TS-MDwill prompt for the breakerswitch settings. If
the circuit breaker has a long time (continuous
current) capability, theTS-MD will prompt:
or
If the long time delay is settable, the TS-MD will
respondwith:
For all breakers, theTS-MD will prompt:
Enter the instantaneous setting indicated on the
circuit breaker, in amps or in multiples of the pickup
setting.
F. Afterentering the breaker switch settings, you must
select the test you wish to perform. The TS-MD will
prompt for the test to perform:
“L”- Long time or overload test
“I” - Instantaneous test
“C”- Current transformer continuity test
Item: TS-MD Test Set
For use with: Type JMKT and LMKT Trip Units
and Type JM6B, JMKB, LM6B, LMKB, MM6B,
NM6B, and PM6B Circuit Breakers.
Page 1 of 3
SAFETY INSTRUCTIONS
Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A.
Universal Test Kit (TS-MD)
Caution: Remove electrical loads from the circuit breaker to
be tested prior to performing tests. Failure to do so
can produce erroneous results and possible electri-
cal malfunction.
TS-MDPROCEDURES
OPERATING INSTRUCTIONS
A. Remove electrical loads from circuit breaker.
B. Plug the TS-MD test set into a grounded 120 VAC
receptacle and turn it on. You will be greeted by the
identifyingturn-on message:
C. Removeanyexternalaccessoryattachedviaribbon
cables from the breaker’s test port before connect-
ing the TS-MD. Connect the ribbon cable between
the TS-MD and the circuit breaker, making sure of
alignment and polarity. After pressing ENTER, the
TS-MDwill prompt:
D. Type in the catalog number of the circuit breaker.
Siemens Energy & Automation, Inc. TS-MD
Test Set. Press any key to continue.
Enter catalog number
XXX…NOT found.
Press any key to continue.
Enter Long Time Delay in Seconds:
Enter Instantaneous Pickup Setting:
Entertest: L-Long I-Inst. C-CT Cont.?
Hazardous voltage.
Will cause death or serious
injury.
Turn off and lock out all power supplying
the circuit breaker prior to cover(s)
removal or while cover(s) are removed
and when installing any internal or
external accessory.
Replace the cover(s) and shield(s)
before power supplying this device is
turned on.
Enter Continuous Current Setting in %:
Enter Continuous Current Setting in Amps:
Siemens Energy & Automation, Inc.
Bellefontaine, OH 43311 U.S.A.
Universal Test Kit (TS-MD)
Page 2 of 3
G. Afterentering the desired test,you will be prompted
for the phase to be tested. The TS-MD will display:
Enter one of the following letters:
“A” - PhaseAor Left Pole
“B” - Phase B or Center Pole
“C” - Phase C or Right Pole
“N”-Neutral
H. The TS-MD will report the type of test you selected
andgiveyouachancetoabortthetest. Forexample,
if “I” was pressed in step F, theTS-MD will display:
If you press the letter “A” to abort, you will be given
new options. See step K.
I. To proceed, reset the circuit breaker and press
ENTER again to start the test. Press any other key
to STOP the test. Once a test has been started, the
TS-MDwill respond with:
Be careful at this time. Any key press will abort the
test.
J. The test may take anywhere from a fraction of a
secondtominutesto complete, depending on which
procedure was selected. If the test passes, the
TS-MD will display:
Enter Phase to Test:
Instantaneous Test
Press ENTER to continue or A to Abort.
Trip Test. Press Any Key to Abort.
Time Remaining: xx.xxx Sec.
Test Passed. xx.xxx Sec.
Press any key to continue.
If the test fails, the display will show one of the
following messages, depending on the type of
failure:
If the circuit breaker tripped during the test, RESET
thecircuit breaker before continuing.
K. TheTS-MDwillpromptforthenextinstructions. The
display will show:
Enter one of the following numbers:
“1” - Select a new test
“2”- Enter a new catalognumber
“3” - Enter new switch settings
If you enter “1”, you will be sent to step F. Choosing
“2” will send the program back to step C. Entering
“3” sends you back to step E, which will be slightly
different the second time through. On the second
lineafter the prompt for the setting, a number ortext
in brackets may appear, which will indicate the last
setting you entered. If you DON’T wish to change
the setting, just press ENTER. If you DO wish to
change the
setting, type in the new setting and press
ENTER.
L. If you pressed “C” when asked,
you will first be prompted by:
and then asked for the phase to test. A message will
then appear stating the test results.
For example:
Test Failed-- Trip Time Too Short.
xx.xxx Sec. Press any key to continue.
TestAborted-- Exceeded Max. Trip Time.
Press any key to continue.
CT Resistance Test. Phase X
PASSED Press any key to continue.
Current Transformer Test
Press ENTER to Continue or A to Abort.
Entertest: L-Long I-Inst. C-CT Cont.?
Change: 1-Test 2-Catalog 3-Settings:
Hazardousvoltage.
Willcausedeathor serious
injury.
Turn off and lock out all power
supplying the circuit breaker prior to
cover(s) removal or while cover(s)
are removed and when installing
any internal or external accessory.
Replace the covers and shields
before power supplying this device
is turned on.
Siemens Energy & Automation, Inc.
Bellefontaine, OH 43311 U.S.A.
Universal Test Kit (TS-MD)
Page 3 of 3
Pc. No. 411660A00
M. There are additional ERROR messages which may
appear on the display during operation which were
notcovered previously:
The test set has sensed that current is not flowing
properlyin the breaker under testand there is either
on open or short circuit between theTS-MD and the
breakertrip unit.
This message will appear if you enter a type of test
that is not available on the breaker being tested.
Forexample:
Thismessagewillappearif you enter a setting value
that does not exist. For example, a MM6B600EW
has continuous current settings of 20, 30, 40, 50,
60,70,80,90&100percent.Ifyouweretoenterany
value other than those listed, the above
messagewouldappear.
Test Not Running-- Check Test Cable.
Press any key to continue.
XXXXXX is NOT available on a XXXXXXXX.
Press any key to continue.
LongTimeisNOTAvailableona LM6B400XCBW.
Press any key to continue.
XX is NOT a Valid Setting.
Press any key to continue.
Test Exceeds Capability of TS-MD.
Press any key to continue.
This message means that a test requires more
current to run than the TS-MD can produce. The
settings on the breaker should be lowered and the
newsettingsshouldbeentered into the TS-MD(step
K, option 3). Then rerun the desired test.
N. The TS-MD will warn you of possible fault coverage
conflicts. These conflicts may occur if, for example,
the short time and instantaneous pickup settings
overlap or interfere with one another. In this case,
the following sequence of messages will appear:
Thesemessagesindicate that something other than
the desired function may trip the breaker. You then
have the option of continuing with the test or
aborting it.
Hazardousvoltage.
Willcause deathor serious
injury.
Turn off and lock out all power
supplying the circuit breaker prior to
cover(s) removal or while cover(s)
are removed and when installing
any internal or external accessory.
Replace the covers and shields
before power supplying this device
is turned on.
You’ve chosen the Long Time test, but the
following may trip first:
Instantaneous
Press any key to continue.
Do you wish to proceed with the test?
[Y/N]
LONG TIME TRIP OUT
Setting
% of In
20%-100% 24.4 to 55.0 33.3 to 75.0 44.4 to 100 77.8 to 175 133 to 300 222 to 500 278 to 625 300 to 675
2.2 sec. 3 sec. 4 sec. 7 sec. 12 sec. 20 sec. 25 sec. 27 sec.
All values are in seconds.

Other Siemens Test Equipment manuals

Siemens T110 User manual

Siemens

Siemens T110 User manual

Siemens 3VW9011-0AT40 User manual

Siemens

Siemens 3VW9011-0AT40 User manual

Siemens FDUD293 User manual

Siemens

Siemens FDUD293 User manual

Siemens Milltronics MWL Weight Lifter User manual

Siemens

Siemens Milltronics MWL Weight Lifter User manual

Siemens TD500 User manual

Siemens

Siemens TD500 User manual

Siemens SENTRON 3WL User manual

Siemens

Siemens SENTRON 3WL User manual

Siemens Cerberus NW8005 User manual

Siemens

Siemens Cerberus NW8005 User manual

Siemens ELTPHB User manual

Siemens

Siemens ELTPHB User manual

Siemens Powers 832-177 Service manual

Siemens

Siemens Powers 832-177 Service manual

Siemens EPSP18V User manual

Siemens

Siemens EPSP18V User manual

Siemens FDUL221 User manual

Siemens

Siemens FDUL221 User manual

Siemens KF8806 User manual

Siemens

Siemens KF8806 User manual

Siemens 3RK1904-2AB02 Reference guide

Siemens

Siemens 3RK1904-2AB02 Reference guide

Siemens PTS-4 Guide

Siemens

Siemens PTS-4 Guide

Siemens RE7T Solo461 User manual

Siemens

Siemens RE7T Solo461 User manual

Siemens TD400 User manual

Siemens

Siemens TD400 User manual

Siemens BT 200 User manual

Siemens

Siemens BT 200 User manual

Siemens WLTS User guide

Siemens

Siemens WLTS User guide

Siemens WAC 11 User manual

Siemens

Siemens WAC 11 User manual

Siemens 985-047 User manual

Siemens

Siemens 985-047 User manual

Popular Test Equipment manuals by other brands

Futech TEMPPOINTER1 manual

Futech

Futech TEMPPOINTER1 manual

SmartSafe iSmartEV ED500 user manual

SmartSafe

SmartSafe iSmartEV ED500 user manual

Druck UPS-III-IS instruction manual

Druck

Druck UPS-III-IS instruction manual

Alps Electric FlexPitch Operator's manual

Alps Electric

Alps Electric FlexPitch Operator's manual

R&S CMW-KM5 Series user manual

R&S

R&S CMW-KM5 Series user manual

Transmille 1000 Series Operation manual

Transmille

Transmille 1000 Series Operation manual

PMK SKID eco manual

PMK

PMK SKID eco manual

Horiba Scientific 6561S-10C instruction manual

Horiba Scientific

Horiba Scientific 6561S-10C instruction manual

iDeaSat NSF H5 user manual

iDeaSat

iDeaSat NSF H5 user manual

Fluke 718 30G manual

Fluke

Fluke 718 30G manual

Rossmax ThermoCal instruction manual

Rossmax

Rossmax ThermoCal instruction manual

PT W89729 owner's manual

PT

PT W89729 owner's manual

PIE 535 operating instructions

PIE

PIE 535 operating instructions

Fluke 714 instruction sheet

Fluke

Fluke 714 instruction sheet

MAHA SA 2 Euro Operation & maintenance manual

MAHA

MAHA SA 2 Euro Operation & maintenance manual

Tektronix MSO70000 Series Service manual

Tektronix

Tektronix MSO70000 Series Service manual

Bedfont NOBreath quick start guide

Bedfont

Bedfont NOBreath quick start guide

Anritsu MP2110A BERTWave Operation manual

Anritsu

Anritsu MP2110A BERTWave Operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.