•Address setting switch: Set the PROFIBUS DP node address.
Address
X10
0
0
:
Settings2
8
OFF
9
0
:
2
ON
Node Address
0 (Default setting)
1
:
99
100
:
125
X1
0
1
:
9
:
5
•V_SEL switch: The number of outputs (size) occupied by the SI unit is
selected.
Content
Number of valves = 32 outputs
Number of valves = 24 outputs
Number of valves = 16 outputs
Settings1
1
Number of valves = 8 outputs
SI unit output data size
4 byte (Default setting)
3 byte
2 byte
1 byte
2
OFF
OFF
ON
ON
OFF
ON
OFF
ON
•HOLD/CLEAR switch: Sets the output status when the fieldbus has a
communication error or is in idling state.
Content
Clears the output. (Default setting)
Holds the output.
Settings2
4
OFF
ON
Setting of the terminating resistor
Terminating resistor
OFF
(Default setting)
Terminating resistor
ON
Terminating resistor
OFF
•Termination switch: Selects the terminating resistor for the
PROFIBUS DP communication line.
Refer to the SMC website (URL http://www.smcworld.com) to obtain
more detailed information about setting and adjustment.
5
Diagnostic
Commissioning
•Parameter Setting
•Hardware Configuration (GSD file)
•I/O Map
Outline with Dimensions
Refer to the product catalogue or SMC website
(URL http://www.smcworld.com) to obtain more detailed information
about outline dimensions.
Refer to the SMC website (URL http://www.smcworld.com) to obtain
more detailed information about diagnostics.
Refer to the SMC website (URL http://www.smcworld.com) to obtain
more detailed information about these settings.
A unit other than the SI unit has been
detected.
Green ST(M) LED is
flashing.
Either of the following conditions:
•The valve ON/OFF counter has
exceeded the set value.
•The valve is short circuited or
disconnected.
Red ST(M) LED is flashing.
Connection error between units has
occurred.
Red/Green ST(M) LED is
flashing alternately.
The configuration data of the master and
device are not consistent.
Red SF LED is ON and
Red BF LED is flashing.
The SI unit has recognized the
communication speed, but the address
setting of the master is incorrect.
Red BF LED is flashing.
•PROFIBUS DP status
Content
The communication with the master has
been established, or the power supply for
control and inputs is OFF.
LED display
OFF.
The communication with the master has
been established, but a diagnostic error
has occurred.
Red SF LED is ON.
Either of the following conditions:
•The cable between the master and SI
unit is not connected.
•The SI unit cannot recognize the
communication speed.
•The master or the SI unit has failed.
Red BF LED is ON.
The address of the SI unit is set to 0, or
above 126.
Red BF and SF LEDs are
both ON.
Maintenance
•Maintenance should be performed according to the Safety Instructions.
•Perform regular maintenance and inspections.
There is a risk of unexpected malfunction.
•Do not use solvents such as benzene, thinner etc. to clean each unit.
They could damage the surface of the body and erase the markings on
the body.
Use a soft cloth to remove stains.
For heavy stains, use a cloth soaked with diluted neutral detergent and
fully squeezed, then wipe up the stains again with a dry cloth.
Refer to the SMC website (URL http://www.smcworld.com) to obtain
more detailed information about maintenance.
Contacts
AUSTRIA (43) 2262 62280 NETHERLANDS (31) 20 531 8888
BELGIUM (32) 3 355 1464 NORWAY (47) 67 12 90 20
CZECH REP. (420) 541 424 611 POLAND (48) 22 211 9600
DENMARK (45) 7025 2900 PORTUGAL (351) 21 471 1880
FINLAND (358) 207 513513 SLOVAKIA (421) 2 444 56725
FRANCE (33) 1 6476 1000 SLOVENIA (386) 73 885 412
GERMANY (49) 6103 4020 SPAIN (34) 945 184 100
GREECE (30) 210 271 7265 SWEDEN (46) 8 603 1200
HUNGARY (36) 23 511 390 SWITZERLAND (41) 52 396 3131
IRELAND (353) 1 403 9000 UNITED KINGDOM (44) 1908 563888
ITALY (39) 02 92711
URL http://www.smcworld.com (Global) http://www.smceu.com (Europe)
Specifications are subject to change without prior notice from the manufacturer.
© 2010 SMC Corporation All Rights Reserved.
LED Display (Continued)
EX600-TFN23
-10 to 50 oC
(Max. surrounding air temperature rating: 50 oC)
Connected load
-20 to 60 oC
Operating temperature
range
For use in Pollution Degree 2 Environment
(UL508)
Pollution degree
24 VDC 1.5 W (SMC)
Solenoid valve with LED and circuit protection
10 to 57 Hz: constant amplitude 0.75 mm p-p
57 to 150 Hz: constant acceleration 49 m/s2
for 2 hours each in direction X, Y and Z
respectively (De-energized)
Vibration resistance
147 m/s23 times each in directions of X, Y and
Z respectively (De-energized)
Impact resistance
Specification
24 VDC Class2, 2 A
Power
supply 24 VDC Class2, 2 AOutput
Control and input
Storage temperature
range
Refer to the product catalogue or SMC website
(URL http://www.smcworld.com) to obtain more detailed information
about product specifications.