manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. SMC Networks
  6. •
  7. Recording Equipment
  8. •
  9. SMC Networks EX250 Series User manual

SMC Networks EX250 Series User manual

Fieldbus device
Operation Manual
EX250 Series for CANopen
Su ary of Product ele ents
1
7
5
6
2
4
Mounting and Installation
Tie-rod (2 pcs)
accessory
3
Communication connector
Description Function
Connect with CANopen communication line.
Power supply connector Supplies power to the solenoid valve, the Output block, SI unit and the Input
block.
Input block connector Connects the Input block.
Display LED display shows the SI unit status.
Switch protective cover Set node ID and Baud rate by using the switches under the cover.
1
No.
2
3
5
6
FE Used for grounding.
7
Output block connector
Connects the solenoid valve, Output block and etc.
4
Installation
The SI unit does not have mounting holes, so it cannot be installed alone. ake sure to
connect the solenoid valve. When an input block is not required, connect the end plate
directly to the SI unit.
Setting
End plate SI unit Valve manifold
M3 hexagon screw
Tightening torque: 0.6 Nm
Tie rod
Tightening torque: 0.6 Nm
BUS
PWR
RR
33
XX
PP
11
12 12
AA
BB
Exchange of SI unit
•Remove screws from End Plate and release connection of each unit.
•Replace old SI unit with new one. (Tie rod does not need to be removed.)
•Connect Input Block and End Plate and tighten removed screws by specified
tightening torque. (0.6 Nm)
Assembly and disconnection of unit
Addition of Input Block
•Remove screws from End Plate.
• ount attached tie rod.
•Connect additional Input Block.
•Connect End Plate and tighten removed screws by specified tightening torque. (0.6 Nm)
Caution for maintenance
(1) Be sure to turn-off all power supplies.
(2) Be sure that there is no foreign object in any of units.
(3) Be sure that gasket is lined properly.
(4) Be sure that tightening torque is according to specification.
If these items are not kept, it may lead to the breakage of substrate or intrusion of
liquid or dust into the units.
Troubleshooting
Technical documentation giving detailed troubleshooting information can be found
on the S C website (URL http://www.smcworld.com).
Specifications
Power for CANopen communication: 18 to 30 VDC, 0.1 A or less
Power for input block: 24 VDC ±20%, 1 A or less (Depending on number of connecting
sensors and specifications)
Power for solenoid valve: 24 VDC +10%/-5%, 2 A or less
(Depending on number of solenoid valve station and
specifications)
Connection load: Solenoid valve with protection circuit for 24 VDC and 1.5 W or less surge
voltage. (made by S C)
Operating ambient temp: -10 to 50 oC Storage ambient temp: -20 to 60 oC
Pollution degree: Pollution degree 3 (UL508)
Technical documentation giving detailed specification information can be found on
the S C website (URL http://www.smcworld.com).
Outline Di ensions
Technical documentation giving detailed outline dimensions information can be
found on the S C website (URL http://www.smcworld.com).
Asse bly and disasse bly of the SI unit
NOTE
When conformity to UL is necessary the SI unit must be used with a UL1310
Class2 power supply.
Safety Instructions
Do not operate the product outside of the specifications.
Do not use for flammable or harmful fluids.
Fire, malfunction, or damage to the product can result.
Verify the specifications before use.
Do not disasse ble, odify (including changing the printed circuit board) or repair.
An injury or failure can result.
Do not operate in an at osphere containing fla able or explosive gases.
Fire or an explosion can result.
This product is not designed to be explosion proof.
If using the product in an interlocking circuit:
•Provide a double interlocking system, for example a mechanical system.
•Check the product regularly for proper operation.
Otherwise malfunction can result, causing an accident.
The following instructions ust be followed during aintenance:
•Turn off the power supply.
•Stop the air supply, exhaust the residual pressure and verify that the air is released before performing
maintenance.
Otherwise an injury can result.
Provide grounding to assure the safety and noise resistance of the Fieldbus syste .
Individual grounding should be provided close to the product with a short cable.
Thank you for purchasing an S C EX250 Series Fieldbus device (Hereinafter
referred to as "SI unit" ).
Please read this manual carefully before operating the product and make sure you
understand its capabilities and limitations.
Please keep this manual handy for future reference.
To obtain more detailed information about operating this product,
please refer to the S C website (URL http://www.smcworld.com) or
contact S C directly.
Safety Instructions
These safety instructions are intended to prevent hazardous situations and/or
equipment damage.
These instructions indicate the level of potential hazard with the labels of
"Caution", " Warning" or "Danger". They are all important notes for safety and
must be followed in addition to International standards (ISO/IEC) and other safety
regulations.
Warning
Caution
After aintenance is co plete, perfor appropriate functional inspections.
Stop operation if the equipment does not function properly.
Safety cannot be assured in the case of unexpected malfunction.
CAUTION indicates a hazard with a low level of risk which, if
not avoided, could result in minor or moderate injury.
Caution:
Warning:
Danger:
WARNING indicates a hazard with a medium level of risk
which, if not avoided, could result in death or serious injury.
DANGER indicates a hazard with a high level of risk which, if
not avoided, will result in death or serious injury.
Operator
This operation manual is intended for those who have knowledge of machinery
using pneumatic equipment, and have sufficient knowledge of assembly,
operation and maintenace of such equipment. Only those persons are allowed
to perform assembly, operation and maintenance.
Read and understand this operation manual carefully before assembling,
operating or providing maintenance to the product.
Wiring
Co unication wiring
SW power is supplied to the sensor connected to the input block. There is a voltage drop up
to maximum 1 V inside the SI unit when SW power is supplied. Select a sensor taking this
voltage drop into consideration. If 24 V must be supplied to the sensor, it is necessary to
increase the SW power supply voltage so that the input voltage of the sensor will be 24 V with
the actual load. (Allowable SW power supply range: 19.2 V to 28.8 V)
SI unit Input block
Sensor
23 VDC
24 VDC
Voltage reduction of approx.1V
Bus cable and ter ination resistors
The cables, connectors, and termination resistors used in CANopen networks shall
meet the requirements defined in ISO 11898. In addition, here are given some
guidelines for selecting cables and connectors.
The table below shows some standard values for DC parameters for CANopen
networks with less than 64 nodes.
Switch setting
Before setting of Node-ID by DIP switch, turn “OFF” power supply to the SI unit.
Setting of Node-ID
Set SW7 to 0. (SW7 is not used.)
Set SW8 to 1. (fixed)
Setting of output when stopped state
SW9
0
Output Value shall take the pre-defined condition specified in
Error Value Output Object (6207h,6307h,6327h)
Default: all outputs are cleared.
1 Output Value shall be kept.
Output condition of solenoid valve when stopped state by an error
occurs (Error Control ,Emergency Object) or "Stop Remote Node"
command is received.
Setting of mode
SW10
1
SW mode. Setting of Node-ID is achived via network.
SW1-8 become unavailable. Node-ID can be set up to 127.
Default is 127 (7Fh).
Mode
0HW mode. Setting of Node-ID is achieved by DIP switches SW1-6.
1
0
ON
31 245678910
Node-ID SW1
00
11
20
62 0
63 1
SW2
0
0
1
1
1
SW3
0
0
0
1
1
SW4
0
0
0
1
1
SW5
0
0
0
1
1
SW6
0
0
0
1
1
....
No.
Station
fig.a
No.
4
4
6Side A
Side B
2
2
3
0
Double Single Double Double
1
1357
Open
No.
Station
fig.b
No.
3
4
5Side A
Side B
2
2
3
0
Double Single Double Double
1
1-46
Output No. assign ent
Combinations of output data and valve manifold
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.
© 2011 S C Corporation All Rights Reserved
Akihabara UDX 15F, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021, JAPAN
Phone: +81 3-5207-8249 Fax: +81 3-5298-5362
URL http://www.smcworld.com
∗: Output numbers are assigned to stations from side D to U of manifold in order. (See manual of
each valve manifold for the directions of side D and U).
∗: Standard manifold is wired in double. Output numbers are assigned to side A and B alternatively.
In case of single solenoid valve, output on side B is free. (Refer to fig.a)
∗: ixed (single and double) wiring is available as long as wiring specifications designate it. This
allows output numbers to be specified without having free output. (Refer to fig.b)
∗: Each bit of data sent from master (4 bytes) shows ON/OFF (0: OFF, 1: ON) of solenoid valve.
Starting from LSB of the first byte (Offset0), output numbers are assigned to all the bits in
numeric order.
Input No. assign ent
The inputs of the Input block are assigned from the SI unit side Input block in the order
0,1,2…maximum of 31.
Bit: 7 0
Bit: 7 0
Bit: 7 0
Bit: 7 0
1
0
357
246
9
8
17
16
31
30
29
28
࣬࣬࣬࣬࣬࣬
࣬࣬࣬
࣬࣬࣬
࣬࣬࣬࣬࣬࣬
75
02460 0 46
Output No.
Output No.
Bit No.
Bit No.
Valve maifold
Solenoid on side A
Solenoid on side B
0: Solenoid valve: OFF
1: Solenoid valve: ON
Byte
0 Offset
Byte
1 Offset
Byte
2 Offset
Byte
3 Offset
Side D
(SI unit side)
13571
࣬࣬࣬
1
Side U
Accessories
Technical documentation giving detailed accessories information can be found on
the S C website (URL http://www.smcworld.com).
•Communication connector 12 5 pins plug A-coded
CAN_SHLD
Description Function
Shield
CAN_V+ Power supply + for CANopen
CAN_GND Power supply − for CANopen
CAN_L CAN_L bus line (dominant low)
1
No.
2
3
5
CAN_H CAN_H bus line (dominant high)4
14
5
23
Co unication wiring
Relation Baud rate and Bus length are as follows.
1 800 k
ax. bus cable length (m)
Baud rate (Communication speed) (bit/s) 500 k 250 k 125 k 50 k 20 k 10 k
25 50 100 250 500 1000 2000 5000
Example of connection cable: 12 socket 5 pins cable with shield (according to ISO11898)
SV24 V
Description Function
+24 V for solenoid valve.
SV0 V 0 V for solenoid valve
SW24 V +24 V for input block
FE Function ground
1
No.
2
3
5
SW0 V 0 V for input block4
Power supply wiring
•Power supply connector 12 5pins plug B-coded (reverse key type)
Example of connection cable: EX9-AC050-1 etc.
LED indication
PWR(V) CANPWR
ADDRESS
1
0
EX250
Green Light (blinking)
LED Description
Illuminates when SI unit is in the Operational state.
Green Light
Illuminates when power for CANopen line is supplied.
PWR(V) Green Light
CAN
Illuminates when power for solenoid valves is supplied.
PWR Green Light
Green Light (single flash)
Red Light (single flash)
Red Light (double flash)
Single flash when SI unit is in Stopped state.
SI unit is in the Pre-Operational state.
<60
Bus length [m]
Bus cable specification
0.34…0.6
<70 0.25…0.34
0…40
Length-related resistance
[mΩ/m]
300…600
Cross-section [mm2]
40…300
<40
<26 0.75…0.8
0.5…0.6
600…1000
Termination
resistance [Ω]
124
150…300
150…300
150…300
FE connection
Connect the ground terminal to the ground. Resistance to the ground should be 100 Ω
or less.
For drop cables a wire cross-section of 0.25 to 0.34 mm2would be an appropriate
choice in many cases.
Besides the cable resistance, there should also be considered the real resistance of
the connectors, if calculating the voltage drop. The read resistance of one connector
should be in the range of 2.5 to 10 mΩ.
Green / Red Light (flickering)
Red Light
Double flash when Error Control Event occurs.
Single flash when CAN controller error occurs.
SI unit is in “Bus OFF” state.
Flickering when SI unit is in Configuration mode. (LSS services)
14
5
23

Other manuals for EX250 Series

4

Other SMC Networks Recording Equipment manuals

SMC Networks EX180-SDN4 Series Instruction Manual

SMC Networks

SMC Networks EX180-SDN4 Series Instruction Manual

SMC Networks EX250-SDN1-X102 Instruction Manual

SMC Networks

SMC Networks EX250-SDN1-X102 Instruction Manual

SMC Networks EX260 Series User manual

SMC Networks

SMC Networks EX260 Series User manual

SMC Networks EX120-SDN1-X2 User manual

SMC Networks

SMC Networks EX120-SDN1-X2 User manual

SMC Networks EX260 Series User manual

SMC Networks

SMC Networks EX260 Series User manual

SMC Networks EX600-SEC Series User manual

SMC Networks

SMC Networks EX600-SEC Series User manual

SMC Networks EX260 Series User manual

SMC Networks

SMC Networks EX260 Series User manual

SMC Networks EX600 Series Installation manual

SMC Networks

SMC Networks EX600 Series Installation manual

SMC Networks EX250 Series User manual

SMC Networks

SMC Networks EX250 Series User manual

SMC Networks EX120-SCM1 User manual

SMC Networks

SMC Networks EX120-SCM1 User manual

SMC Networks EX250-SAS Series User manual

SMC Networks

SMC Networks EX250-SAS Series User manual

SMC Networks EX600-AX Installation manual

SMC Networks

SMC Networks EX600-AX Installation manual

SMC Networks EX124U-SDN1-X2 User manual

SMC Networks

SMC Networks EX124U-SDN1-X2 User manual

SMC Networks EX260-SPR1 Instruction Manual

SMC Networks

SMC Networks EX260-SPR1 Instruction Manual

SMC Networks EX250-SDN1 User manual

SMC Networks

SMC Networks EX250-SDN1 User manual

SMC Networks EX500-GDN1 Instruction Manual

SMC Networks

SMC Networks EX500-GDN1 Instruction Manual

SMC Networks EX12-SCM Series User manual

SMC Networks

SMC Networks EX12-SCM Series User manual

SMC Networks EX250 Series User manual

SMC Networks

SMC Networks EX250 Series User manual

SMC Networks EX250-SAS3 Installation manual

SMC Networks

SMC Networks EX250-SAS3 Installation manual

SMC Networks EX250 Series User manual

SMC Networks

SMC Networks EX250 Series User manual

SMC Networks EX260 Series User manual

SMC Networks

SMC Networks EX260 Series User manual

SMC Networks EX9-OET1 User manual

SMC Networks

SMC Networks EX9-OET1 User manual

SMC Networks EX600-SDN2 User manual

SMC Networks

SMC Networks EX600-SDN2 User manual

SMC Networks EX180-SMJ3 Series User manual

SMC Networks

SMC Networks EX180-SMJ3 Series User manual

Popular Recording Equipment manuals by other brands

Tegeler Creme user manual

Tegeler

Tegeler Creme user manual

Studio Technologies 215 Configuration guide

Studio Technologies

Studio Technologies 215 Configuration guide

Sony CXFD-S03CP Service manual

Sony

Sony CXFD-S03CP Service manual

Korg A1 owner's manual

Korg

Korg A1 owner's manual

Reloop Mixage Interface Edition MK2 instruction manual

Reloop

Reloop Mixage Interface Edition MK2 instruction manual

Alesis ADAT-M20 owner's manual

Alesis

Alesis ADAT-M20 owner's manual

Roland S-750 owner's manual

Roland

Roland S-750 owner's manual

Peak PCAN-USB Hub user manual

Peak

Peak PCAN-USB Hub user manual

Interface BlueDAQ BSC4D operating manual

Interface

Interface BlueDAQ BSC4D operating manual

ALM Pamela's Pro Workout Operation manual

ALM

ALM Pamela's Pro Workout Operation manual

Lowell SEQ-8 manual

Lowell

Lowell SEQ-8 manual

Black Lion Audio PBR TT owner's manual

Black Lion Audio

Black Lion Audio PBR TT owner's manual

Marantz DR4160 user guide

Marantz

Marantz DR4160 user guide

Calrec SUMMA installation manual

Calrec

Calrec SUMMA installation manual

eaReckon EARebound user manual

eaReckon

eaReckon EARebound user manual

Tascam SX-1 Release notes

Tascam

Tascam SX-1 Release notes

Ricatech PR85 user manual

Ricatech

Ricatech PR85 user manual

Extron electronics RGB 302 Specifications

Extron electronics

Extron electronics RGB 302 Specifications

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.