1 Safety
MIC-10 meter is designed for performing check tests of protection against electric shock in mains
systems. The meter is used for making measurements and providing results to determine safety of
electrical installations. Therefore, in order to provide conditions for correct operation and the
correctness of the obtained results, the following recommendations must be observed:
•Before you proceed to operate the meter, acquaint yourself thoroughly with the present manual
and observe the safety regulations and specifications determined by the producer.
•Any application that differs from those specified in the present manual may result in a damage to
the device and constitute a source of danger for the user.
•MIC-10 meters must be operated only by appropriately qualified personnel with relevant
certificates authorising the personnel to perform works on electric systems. Operating the meter by
unauthorised personnel may result in damage to the device and constitute a source of danger for
the user.
•During measurements of insulation resistance, dangerous voltage up to 1 kV occurs at the ends of
test leads of the meter.
•Before the measurement of insulation resistance you must be sure that tested object is
disconnected from the power supply
•During the measurement of insulation resistance do not disconnect test leads from the tested
object before the measurement is completed (see par. 3.1); otherwise the capacitance of the
object will not be discharged, creating the risk of electric shock,
•Operation of the meter realised by unauthorised personnel may result in damage to the device and
constitute a source of danger for the user.
•It is unacceptable to operate the following:
⇒A damaged meter which is completely or partially out of order,
⇒A meter with damaged test leads insulation,
⇒A meter stored for an excessive period of time in disadvantageous conditions (e.g. excessive
humidity). If the meter has been transferred from a cool to a warm environment with a high
level of relative humidity, do not start measurements until the meter is warmed up to the
ambient temperature (approximately 30 minutes).
•Displayed BATT symbol indicates insufficient voltage of power supply and the need to charge the
accumulator or replace batteries.
•Symbols ErrX, where Xis a number 1…9, indicate incorrect operation of the meter. If after
restarting the device this situation is repeated - it indicates that the meter is damaged.
•Before measurement, choose a correct measurement function and make sure that test leads are
connected to respective measuring terminals.
•Do not operate a meter with an open or incorrectly closed battery (accumulator) compartment or
power it from other sources than those specified in the present manual.
•Meter inputs are electronically protected against overloads (caused by e.g. connecting the meter
to a live circuit) up to 550V, for voltmeter up to 600V.
•Repairs may be carried out only by an authorised service point.