SP7-20, SP7-21 and SP7-22 Smart Positioner
Safe operation of these products can only be guaranteed if they are properly installed,
commissioned, used and maintained by qualified personnel (see SP7-20, SP7-21 and SP7-22
Installation manual IM-P706-03) in compliance with the operating instructions. General installation
and safety instructions for pipeline and plant construction, as well as the proper use of tools
and safety equipment must also be complied with.
Explosion Proof Warning
Please ensure the unit is being used and installed in conformity with local, regional, and national
explosion proof regulations.
-Refer to “8. Approvals”
-Explosion proof type of cables and gaskets should be used, when explosive gases are present
at the installation site.
-Power should be turned off completely when opening the product’s cover. When opening the
cover, ensure that there is no power remaining in any electrical parts nearby.
-Flameproof enclosure type positioner has 2 ports for power connection. Explosion proof type
wires and packing should be used. A blanking plug is required for any port that is not being used.
-For external ground terminal, ring terminal with surface area of more than 5.5 mm2 should
be used.
-There is risk of explosion due to static electricity charge. Static electricity charge may develop
when cleaning the product with a dry cloth. It is imperative to avoid static electricity charge
in the hazardous environment. A damp cloth must be used, when cleaning the surface of the
product.
-To meet explosion-proof marking information and ingress protection of IP66, use certified
Ex-cable glands and Ex-plugs.
-The cable entry must be equipped with a cable entry device, which must be an Ex cable
entry device approved by the explosion-proof inspection agency (For NEPSI - according to
the requirements of GB3836.1-2010 and GB3836.2-2010) and meet the requirements of the
product explosion-proof mark, and the installation of the cable entry device Use must follow
its instructions.
-The positioner is designed for use at an ambient temperature range of -40 °C up to 85 °C at
maximum.
-If the positioner is used at an ambient temperature above 60 °C or below -20 °C, cable glands and
cables approved for a service temperature corresponding to the maximum ambient temperature
increased by 10 K or corresponding to the minimum ambient temperature shall be used.
-The dimensions of the flameproof joints are in parts other than the relevant minimum or
maximum values of IEC 60079-1:2014. For information on the dimensions of the flameproof
joints contact the manufacturer.
-Fasteners with a minimum property class of 10.12, A2-70 or A2-80 must be used for the closing
of the flameproof enclosure.
1. Safety information