- 10 - - 11 -
Technical specifications
Dimensions (H x W x D): 120 x 120 x 68 mm DualTech
120 x 120 x 73 mm Single US
120 x 120 x 68 mm US 360
120 x 120 x 73 mm Dual US
Mains voltage: KNX bus voltage
Settings: via ETS software, remote control or bus
Lighting channels:
light 1 – light 4:
Switching/dimming; switching mode, constant lighting control
Stay-ON time: IQ mode, 1-30 min,
depending on presence and light level
Light measurement: mixed light
Basic brightness: OFF / 10% – 50%
Stay-ON time: Basic brightness ON duration, 1-30 min
HVAC output: depending on presence
Switch-on delay: Room surveillance, 1-30 min
Stay-ON time: 1-120 min
Presence stay-ON time output: 1-255 s
Further outputs: Light level, scene control, sabotage
Detection zones: US 360 / DualTech Single US / Dual US
(detection
at 2.5 m /
mounting
height 2.5 m)
Tangential / presence:
Radial:
max. Ø 6 m (28 m2)
min. Ø 2 m (3 m2)
Reach up to Ø 10 m max. 3 x 10 m / 3 x 20 m (30 / 60 m²)
min. 3 x 2.5 m / 3 x 5 m min. (7.5 /
15 m²)
Mounting height
(mounted to ceiling):
2.5 m – 3.5 m
Application: inside buildings
Sensor technology: DualTech US 360 / Single US / DualTech
PIR (passive infrared),
single pyro sensor,
11 detection zones,
520 switching zones,
Ultrasonic 40 kHz
Ultrasonic 40 kHz
IP rating: IP20
Temperature range: -25°C to +55°C
Remote control
Using the remote control (optional),
functions can be conveniently
activated from the floor.
Service remote control
RC6KNX
EAN no.: 4007841 593018
User remote control
RC7KNX
EAN no.: 4007841 592912
Troubleshooting
Malfunction Cause Remedy
Light does not switch ON nNo BUS voltage
nLight level set too low
nNo movement being detected
nCheck BUS voltage
nSlowly increase twilight
setting until light switches ON
nEnsure unobstructed sensor
vision
nCheck detection zone
Light does not switch OFF nRoom light level too bright
nStay-ON time still effective
n
Interference from unintended
sources of motion, e.g.: ceiling
fan, air-conditioning, ventilation,
open doors and windows
nReduce twilight setting
nWait until stay-ON time
elapses, reduce stay-ON
time if necessary
nM
ask out stationary sources
of interference by reducing
sensitivity
Sensor switches OFF in spite
of persons being present
nStay-ON time too short
nLight-level threshold too low
nIncrease stay-ON time
nChange twilight setting
Sensor does not switch OFF
quickly enough
nStay-ON time too long nReduce stay-ON time
Sensor does not switch ON
when persons are present
despite it being dark
nLux setting too low nSensor deactivated by
switch/button?
nSemi-automatic mode?
nIncrease light-level threshold
Warranty Declaration
As purchaser, you are entitled to your statutory
rights against the vendor. If these rights exist in your
country, they are neither curtailed nor restricted by
our Warranty Declaration. We guarantee that your
STEINEL Professional sensor product will remain
in perfect condition and proper working order for
a period of 5 years. We guarantee that this product
is free from material-, manufacturing- and design
flaws. In addition, we guarantee that all electronic
components and cables function in the proper
manner and that all materials used and their
surfaces are without defects.
Making Claims
If you wish to make a claim, please send your prod-
uct complete and carriage paid with the original
receipt of purchase, which must show the date of
purchase and product designation, either to your
retailer or contact us at STEINEL (UK) Limited,
25 Manasty Road, Axis Park, Orton Southgate,
Peterborough, PE2 6UP, for a returns number.
For this reason, we recommend that you keep your
receipt of purchase in a safe place until the warranty
period expires. STEINEL shall assume no liability for
the costs or risks involved in returning a product.
For information on making claims under the
terms of the warranty, please go to
www.steinel-professional.de/garantie
If you have a warranty claim or would like to ask
any question regarding your product, you are
welcome to call us at any time on our
Service Hotline 01733 366700.
GB