www.autani.com www.autani.com
10 11
Operation – Without HBS-DC Installed Operation – With HBS-DC Installed
Operation - HBS 300, HBS 200
TheHBS300andHBS200operateby
turninglightsONautomaticallywhen
occupancyisdetectedandOFFwhenthe
spaceisleftvacantandthetimedelay
haselapsed.Thesensorcommunicates
wirelesslytootherwirelessdevices
programmedtothesamegrouptoturn
lightsONorOFF.
Light level function - HBS 300, HBS 200
TheHBSsensor’slightlevelfeature
keepslightingOFFduringdaylighthours,
regardlessofoccupancy.Alightlevel
delay-ofunctionpreventsthesensor
fromrespondingtotemporarychanges
inambientlightlevel.Iftheambientlight
levelisbrighterthanthesettargetvalue,
thesensorwillwaitforoneminutebefore
turninglightsOFF.Ifmotionisdetected
withinthistime,lightswillremainON.
Afternomotionisdetectedforoneminute
andthelightlevelhasbeengreaterthan
thetargetvalue,thelightswillturnOFF
andremainOFFuntilthedaylightlevel
dropsbelowthetargetsetpointand
motionisdetected.
Operation - HBS 300, HBS 200
TheHBS300andHBS200operateby
turninglightsonanddimminglights
inresponsetoscheduledormanual
overridesinitiatedfromtheAutaniEnergy
Manager.
MultipleHBS300andHBS200unitsmay
begroupedtogetherinthemanagerso
thatoccupancytransitionsaresharedby
thegroup,turninglightsONandOFFin
unison.
Light level function - HBS 300, HBS 200
TheHBSsensor’slightlevelfeaturewill
dimthextureautomaticallyifenabledin
theAutaniEnergyManager.
Thelightharvestingfeatureallowseach
lighttomaintainaconstantlevelof
illuminationdirectlyunderthexture.
Thesesettingsmustbeconguredinthe
AutaniEnergyManageriftheHBS-DC
radioisinstalled.
Initial power up - HBS 300, HBS 200
Uponinitialpowerup,theloadwillturn
ONforuptooneminute.Ifnomotion
isdetected,theloadwillswitchOFF.If
motionisdetectedandthetargetlight
levelsettingislessthanthedaylightlevel,
theloadwillstayONfortheselectedtime
delaysetting(perDIPswitchsetting).If
thedaylightlevelatpowerupisgreater
thanthetargetlightlevelsetting,theload
willswitchOFFregardlessofoccupancy.
Surge protection - HBS 300, HBS 200
TheHBSsensorscontainsbuiltinsurge
protection.Thisfeaturewillresetthe
unitautomaticallyafter:powersurges,
poweroutages,andpowershortages.
Surgeprotectionprotectsthesensorifit
ismiswiredaswell.Ifmiswired,shuto
power,correctthewiring,andthesensor
willthenoperatecorrectly.
Initial power up - HBS 300, HBS 200
Uponinitialpowerup,theloadwill<check
withBobBelz/Ibrahimforlogic>
Surge protection - HBS 300, HBS 200
TheHBSsensorscontainsbuiltinsurge
protection.Thisfeaturewillresetthe
unitautomaticallyafter:powersurges,
poweroutages,andpowershortages.
Surgeprotectionprotectsthesensorifit
ismiswiredaswell.Ifmiswired,shuto
power,correctthewiring,andthesensor
willthenoperatecorrectly.
Light level - HBS 300, HBS 200
Thelightlevelfeatureallowslightingto
remainOFFduringdaylight,regardlessof
occupancy.Daytimeoperationisat200
footcandles(factorysetting).Nighttime
operationisat.2footcandles.
See Autani Manager documentation.
Light level teach mode - HBS 300, HBS 200
Thelightlevelteachmodereadsthe
ambientlightlevelinthespaceandselects
thisamountforthelightlevelsetting.
• Turnthelightlevelsettingto
• After10seconds,thevalueofthe
ambientbrightnessissaved.
• Thisvalueisalsoavailableafterapower
failureifthepotentiometerissetto
teachmodeatpowerup.
Aftersetupandcommissioningare
complete,adjustthelightlevelsettingsto
ttheapplicationneeds.
Light level: .2 (night) to 200 (day) footcandles