BLD-405S BLDC Brushless Driver
5
The potentiometer performs 0~1.0 ratio attenuation processing on the amplitude of the SV digital signal. Generally, the
R-SV is adjusted to 1.0, and the SV input data
Word signals are not attenuated.
5.2 Motor Operate/Stop Control (EN)
By controlling the on/off state of the EN terminal relative to GND, the operation and stop of the motor can be controlled.
When the terminal is connected, the motor runs, and vice versa, the motor stops. When the motor is stopped by using the
run/stop terminal, it will come to a natural stop, and its motion characteristics are related to the load inertia.
5.3 Motor Rotation Direction Control (F/R)
The direction of the motor can be controlled by connecting or disconnecting terminal F/R and terminal GND. When F/R is
not connected to terminal GND, the motor runs clockwise (facing the motor shaft) and vice versa for counterclockwise
rotation.
Attention: To avoid damage to the driver when changing the motor direction, the motor should be stopped before the
direction changing to avoid performing direction operations while the motor is running.
5.4 Braking Stop (BK)
The braking stop of the motor can be controlled by the connection of control terminal BK to terminal GND. When control
terminal BK is disconnected from terminal GND, the motor runs, when it is switched on the motor quickly brakes to a stop,
braking stop is faster than natural stop, the specific stopping time is related to the load inertia of the user's system.
Attention: As the brake stop has a bad impact on both the electrical and the mechanical, a natural stop should be used if
there are no special stopping requirements.
5.5 Motor Speed Signal Output (PG)
The speed pulse output is a 5V pulse output, to obtain the signal a pull-up resistor of 3K ohm ~10K ohm should be
connected to the power supply. The number of output pulses per revolution of the motor is 3 x N, N being the number of
pairs of poles of the motor. For example: 2 pairs of poles, i.e. a four-pole motor, 6 pulses per revolution. When the motor
speed is 500 rpm, the output pulse of the terminal PG is 3000.
5.6 Alarm Output (ALM)
Alarm output of the driver: this terminal is low during an alarm. To obtain a signal, a pull-up resistor of 3K ohm to 10K ohm
should be connected to the power supply. When the alarm is on, this terminal is connected to GND (low level) and the
driver stops itself and is in alarm.
5.7 Driver Failure
When there is over-voltage or over-current inside the drive, the drive will enter a protection state, automatically stop
working, the motor will stop, and the blue light on the drive will go out. To clear the alarm, the enable terminal (that is,
disconnecting EN and GND) or power must be disconnected. If this fault occurs, please check the motor wiring or motor
load.