Swegon COLIBRI User manual

11
COLIBRITM Ceiling
Square ceiling diffuser with discs for supply air
COLIBRI Ceiling
Quick facts
►Adjustable discs
►100% flexible spread pattern
►Can be used for vertical air diffusion
►Swirl function
►Also available in the Extract air version
►Designed for modular suspended ceilings (595 x 595 mm)
►Quick Access diffuser face
►Easy to access
►ALS commissioning box with 1 or 2 changes in
dimension between the inlet and outlet.
►Available in a version with low installation height
►Available in alternative colours
►Included in the MagiCAD and CadVent databases
Quick guide
A I R F L O W – S O U N D L E V E L
COLIBRI CR, Supply air l/s
Size 25 dB(A) 30 dB(A) 35 dB(A)
125-400 34 39 46
125-600 33 39 46
160-400 40 48 54
160-600 42 49 54
200-500 64 75 89
200-600 64 75 89
250-600 100 115 135
315-600 110 125 140
400-600 125 140 160
COLIBRI CR, Supply air ALS l/s
Size Size 25 dB(A) 30 dB(A) 35 dB(A)
125-400 100 -125 24 30 37
125-600 100 -125 24 30 37
160-400 125-160 33 40 47
160-600 125-160 33 40 47
200-500 160-200 53 66 79
200-600 160-200 53 66 79
250-600 200-250 87 105 123
315-600 250-315 100 120 140
400-600 315- 400 -140 155
Data specified in the lower table is applicable to 50 Pa total pressure when
the commissioning box ALS is used.

2
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
Technical description
Design
The square supply air diffuser consists of a diffuser back-
ing box and a diffuser face. The diffuser face is equipped
with aerodynamically shaped, adjustable discs. The dif-
fuser face is hung on hinges on one side and secured by
springs on the opposite side. This Quick Access fastening
system makes it simpler and quicker to open and close the
diffuser face for installation, commissioning and cleaning.
air diffuser is also available in a low version for installation
in a ceiling void where low installation height is required.
The air diffuser is then supplied without sleeve coupling.
Materials and surface treatment
The backing box and diffuser face are made of sheet steel.
The connection branch is made of galvanized sheet steel. The
interior and exterior of the air diffuser is painted in our white
standard colour, RAL 9010. The air diffuser is also available in
alternative standard colours: Dusty grey RAL 7037, white alu-
minium RAL 9006, jet black RAL 9005, grey aluminium RAL
9007 and signal white RAL 9003 (NCS 0500).
The discs are made of ABS plastic.
Accessories
Commissioning box:
ALS. Made of galvanized sheet steel. Contains removable
commissioning damper, fixed measurement tappings and
sound absorbing material with reinforced surface layer, to
Fire Resistance Class B-s1,d0 according to EN ISO 11925-2.
The commissioning box is also available in a low version for
installation in a ceiling void where low installation height
is required. The air diffuser is then supplied without sleeve
coupling. The commissioning box is available with 1 or 2
changes in dimension between the inlet and outlet.
Frame:
SAR K. For aesthetic installation of a lowered diffuser.
Adapter:
ADAPTER, for adaptation to various variants and makes
of systemized false ceilings: Ecophon, Gyproc, Dampa etc.
Also used for adaptation to optional sizes of lay-in ceil-
ings, for instance 625 x 625 or 675 x 675. Specification in
separate product sheet for ADAPTER.
Planning
The COLIBRI Ceiling is available with square dimensions of
595 x 595 mm in all connection sizes. This makes COLIBRI
Ceiling very easy to install in 600 x 600 suspended ceiling
modules. Position these directly down in the T-bar frame-
work, and then secure them to the duct system or to the
commissioning box. COLIBRI Ceiling is also available in a
low version for installation in ceiling void where low
installation height is required. See Figure 2.
Installation
To dismantle the face (see Figure 1) prior to installing
the air diffuser, insert a thin object, such as a Quick
Access card or similar card, between the air diffuser face
and backing box to release the springs. Then slide the
card from the centre outward toward the corners. The
inlet spigot of the diffuser backing box can be secured to
the connecting ducting by means of self-tapping screws
or a blind rivets. For flush-mounting in fixed ceiling con-
structions, secure the diffuser by means of screws into
place in the framework through either the sides or top of
the diffuser backing box. The face and backing box in the
version for low installation height must be centred and
jointed together using the locking strip supplied. Secure
the air diffuser in the correct position by means of self-
tapping screws to the underside of commissioning box.
For mounting in modular suspended ceilings, it is advis-
able to select air diffusers with outer dimensions of
595 x 595 mm. Position these directly down in the T-bar
framework, and then secure them to the duct system or
to the commissioning box. If an ALS commissioning box
is used, it must be secured to the building structure by
means of hangers or mounting brackets.
The distance between the air diffuser and the commis-
sioning box can be increased by as much as 500 mm with
an ordinary circular duct without having to lengthen the
measuring tubes and damper adjustment cords.
See Figure 2.
Commissioning
Commissioning must be carried out with the diffuser face
mounted. Pull out the measuring tubes and damper
adjustment cords through the diffuser face discs. Connect
a manometer to the measuring tubes. The desired com-
missioning pressure can be computed by applying the
rated coefficient of performance of the air diffuser. Set
the damper blade in the correct position and tie the
damper adjustment cords in a commissioning knot to
indicate the damper position.
The rated coefficient of performance (K-factor) is specified on
the identification label of the product and the relevant commis-
sioning instructions are also available at www.swegon.com.
Maintenance
The air diffuser can be cleaned, if necessary, using lukewarm
water with dishwashing detergent added. The duct system
can be accessed after opening the diffuser face. If an ALS
commissioning box is used, pull the distributor plate aside and
then grip and twist the damper unit from of its mounting.
Environment
The Declaration of construction materials is available at
www.swegon.com.

3
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
COLIBRI Ceiling
Figure 3. Installing air diffusers and commissioning box with low
installation height.
Figure 4. Damper removal.
Figure 2. Installation.
Figure 1. Quick Access.

4
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
Sizing
• The sound level, dB(A), values are applicable to rooms
with an equivalent sound absorption area of 10 m2
• Throw l0.2 is measured under isothermal discharge
conditions.
• Recommended max. permissible temperature below
room temperature is 14 K.
• For calculating the width of the air stream, air veloci-
ties in the occupied zone or sound levels in rooms
with other dimensions, please refer to our ProAir web
calculation software available for download at
www.swegon.com.
Sound data – COLIBRI CC – Supply air
– Air diffuser only
Sound power level LW (dB)
Table Kok
Size Mid-frequency (Octave band) Hz
COLIBRI CC 63 125 250 500 1000 2000 4000 8000
125- 400 1 1 2 5 5 -8 -22 -23
125- 600 -3 2 6 8 1 -9 -23 -22
160-400 -4 2 1 3 5 -7 -24 -26
160-600 1 3 5 8 2 -8 -23 -25
200-500 -1 0 1 4 5 -9 -26 -23
200-600 0 1 3 7 3 -10 -25 -27
250-600 -2 1 2 6 4 -9 -24 -23
315- 600 0 3 3 5 4 -10 -24 -21
400-600 7 4 4 5 4 -7 -18 -18
Tol. ± 2 2 2 2 2 2 2 2
Sound attenuation DL (dB)
Table DL
Size Mid-frequency (Octave band) Hz
COLIBRI CC 63 125 250 500 1000 2000 4000 8000
125- 400 20 15 10 53554
125- 600 20 15 10 53554
160-400 19 14 9 4 3 5 5 4
160-600 19 14 9 4 3 5 5 4
200-500 19 14 8 3 3 4 5 5
200-600 19 14 8 3 3 4 5 5
250-600 16 11 5 4 2 3 4 4
315- 600 14 9 4 2 2 2 3 3
400-600 13 8 4 1 0 0 0 0
Tol. ± 2 2 2 2 2 2 2 2
Sound data – COLIBRI CC - Extract air
– Air diffuser only
Sound power level LW(dB)
Table Kok
Size Mid-frequency (Octave band) Hz
COLIBRI CC 63 125 250 500 1000 2000 4000 8000
250-600 0 9 7 5 2 -3 -9 -16
315- 600 0 8 8 5 2 -3 -9 -14
400-600 -2 5 5 5 4 -4 -12 -16
Tol. ± 2 2 2 2 2 2 2 2
Sound attenuation DL (dB)
Table DL
Size Mid-frequency (Octave band) Hz
COLIBRI CC 63 125 250 500 1000 2000 4000 8000
250-600 16 11 5 4 2 3 4 4
315- 600 14 9 4 2 2 2 3 3
400-600 13 8 4 1 0 0 0 0
Tol. ± 2 2 2 2 2 2 2 2

5
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
COLIBRI Ceiling
Sound data – COLIBRI CC + ALS – Supply air
– One step
Sound power level LW (dB)
Table Kok
Size Mid-frequency (Octave band) Hz
COLIBRI CC
+ ALS, One
step
63
125
250
500
1000
2000
4000
8000
125- 400 410 9 5 2 -8 -15 -18
125- 600 410 9 5 2 -8 -15 -18
160-400 4 7 7 5 4 -8 -17 -17
160-600 4 7 7 5 4 -8 -17 -17
200-500 2 6 6 4 3 -6 -13 -14
200-600 2 6 6 4 3 -6 -13 -14
250-600 0 7 5 5 3 -7 -16 -16
315- 600 5 5 3 6 4 -10 -21 -19
400-600 3 8 4 4 5 -7 -22 -22
Tol. ± 2 2 2 2 2 2 2 2
Sound data – COLIBRI CC + ALS – Supply air
– Two steps
Sound power level LW(dB)
Table Kok
Size Mid-frequency (Octave band) Hz
COLIBRI CC
+ ALS,
Two steps
63
125
250
500
1000
2000
4000
8000
160-400 311 9 5 1 -8 -14 -14
160-600 311 9 5 1 -8 -14 -14
200-500 312 9 4 0 -6 -13 -14
200-600 312 9 4 0 -6 -13 -14
250-600 511 7 3 0 -5 -12 -13
315- 600 310 3 5 2 -7 -14 -15
Tol. ± 2 2 2 2 2 2 2 2
Sound attenuation DL (dB)
Table DL
Size Mid-frequency (Octave band) Hz
COLIBRI CC
+ ALS, One
step
63
125
250
500
1000
2000
4000
8000
125- 400 21 16 917 23 16 11 13
125- 600 21 16 917 23 16 11 13
160-400 19 14 10 17 19 12 10 12
160-600 19 14 10 17 19 12 10 12
200-500 16 11 816 18 12 11 11
200-600 16 11 816 18 12 11 11
250-600 13 8 8 16 17 12 12 13
315- 600 11 6 7 19 14 10 10 13
400-600 14 5 8 14 11 10 11 12
Tol. ± 2 2 2 2 2 2 2 2
Sound attenuation DL (dB)
Table DL
Size Mid-frequency (Octave band) Hz
COLIBRI CC
+ ALS,
Two steps
63
125
250
500
1000
2000
4000
8000
160-400 19 14 11 17 24 15 13 15
160-600 19 14 11 17 24 15 13 15
200-500 18 14 10 16 23 15 14 15
200-600 18 14 10 16 23 15 14 15
250-600 15 9 9 20 19 15 16 14
315- 600 13 810 19 16 13 16 16
Tol. ± 2 2 2 2 2 2 2 2
COLIBRI CC + ALS – Extract Air
Sound power level LW(dB)
Table Kok
Size Mid-frequency (Octave band) Hz
COLIBRI CC 63 125 250 500 1000 2000 4000 8000
250-600 314 8 2 0 -4 -10 -15
315- 600 511 6 2 3 -4 -14 -18
400-600 6 8 4 4 4 -4 -14 -18
Tol. ± 2 2 2 2 2 2 2 2
Sound attenuation DL (dB)
Table DL
Size Mid-frequency (Octave band) Hz
COLIBRI CC 63 125 250 500 1000 2000 4000 8000
250-600 16 11 5 4 2 3 4 4
315- 600 14 9 4 2 2 2 3 3
400-600 13 8 4 1 0 0 0 0
Tol. ± 2 2 2 2 2 2 2 2

6
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
p
t
Pap
t
Pa
100200300400 m
3
/h
p
t
Pap
t
Pa
20 30 40 50 100l/s
2
3
4
5
10
20
30
40
50
100
20
25
30
35
40 dB(A)
125
160
200
200
160
1 2 3 4 5
125
m
0,2
l
p
t
Pa
2003004005001000 m
3
/h
40 50 100200300 l/s 400
4
5
10
20
30
40
50
100
200
20
25
30
35
40 dB(A)
250
315
400
p
t
Pa
100200300400500 m
3
/h
20 30 40 50 100 l/s 200
2
3
4
5
10
20
30
40
50
100
20
25
30
35
40 dB(A)
125
160
200
250
315
400
400
315
250
200
160
1 2 3 4 5
125
m
0,2
l
COLIBRI CC 250-600, 315-600 and 400-600 – Extract air
Engineering graphs – COLIBRI CC
Airflow – Pressure drop – Sound level – Throw
• The graphs illustrate data for COLIBRI Ceiling recessed
in the ceiling.
• The graphs must not be used for commissioning.
• The dB(A) values are applicable to rooms with normal
acoustic absorption of 4 dB.
• The dB(C) value is normally 6-9 dB higher than the
dB(A) value.
• Throw for adjusting the swirl. For other adjustments, see
the graphs for diffusers with the ALS commissioning box.
COLIBRI CC, 125-400, 160-400 and 200-500
– Supply air
COLIBRI CC 125-600. 160-600, 200-600, 250-600,
315-600 and 400-600 – Supply air

7
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
COLIBRI Ceiling
COLIBRI CC + ALS – supply air
Air flow – Pressure drop – Sound level – Throw
• The graphs illustrate data for COLIBRI Ceiling recessed
in the ceiling
• The graphs must not be used for commissioning
• = Minimum airflow required for obtaining sufficient
commissioning pressure
• The dB(A) values are applicable to rooms with normal
acoustic absorption of 4 dB.
• The dB(C) value is normally 6-9 dB higher than the
dB(A) value.
• The version for low installation height generates
approx. 3 dB(A) higher sound level than the value plot-
ted in the graph.
COLIBRI CC 125-400 + ALS 100-125 – One step
p
t
Pap
t
Pa
40 50 100200 m
3
/h
p
t
Pap
t
Pa
10 20 30 40 50 l/s100
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
1 2 3 4 5
m
0,2
l
COLIBRI CC 160-400 + ALS 100-160 – Two steps
p
t
Pap
t
Pa
40 50 100200 m
3
/h
p
t
Pap
t
Pa
10 20 30 40 50 l/s100
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
1 2 3 4 5
m
0,2
l
COLIBRI CC 125-600 + ALS 100-125 – One step COLIBRI CC 160-600 + ALS 100-160 – Two steps
p
t
Pap
t
Pa
40 50 100200 m
3
/h
p
t
Pap
t
Pa
10 20 30 40 50 l/s100
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
1 2 3 4 5
m
0,2
l
p
t
Pap
t
Pa
40 50 100200 m
3
/h
p
t
Pap
t
Pa
10 20 30 40 50 l/s100
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
1 2 3 4 5
m
0,2
l
D

8
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
COLIBRI CC 160-400 + ALS 125-160 – One step COLIBRI CC 200-500 + ALS 125-200 – Two steps
p
t
Pap
t
Pa
40 50 100200 m
3
/h
p
t
Pap
t
Pa
10 20 30 40 50 l/s100
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
1 2 3 4 5
m
0,2
l
p
t
Pap
t
Pa
100 200300400 m
3
/h
p
t
Pap
t
Pa
20 30 40 50 100l/s
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100%
0%
1 2 3 4 5
m
0,2
l
COLIBRI CC 200-600 + ALS 125-200 – Two steps
COLIBRI CC 160-600 + ALS 125-160 – One step
p
t
Pap
t
Pa
40 50 100200 m
3
/h
p
t
Pap
t
Pa
10 20 30 40 50 l/s100
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
1 2 3 4 5
m
0,2
l
p
t
Pap
t
Pa
100 200300400 m
3
/h
p
t
Pap
t
Pa
20 30 40 50 100l/s
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100%
0%
1 2 3 4 5
m
0,2
l
COLIBRI CC 250-600 + ALS 160-250 – Two stepsCOLIBRI CC 200-500 + ALS 160-200 – One step
p
t
Pap
t
Pa
100200 300 400 500 m
3
/h
p
t
Pap
t
Pa
20 30 40 50 100 l/s 200
10
20
30
40
50
100
200
300
400
20
25
30
35
40 dB(A)
100%
0%
1 2 3 4 5
m
0,2
l
p
t
Pap
t
Pa
100200300400500 m
3
/h
p
t
Pap
t
Pa
20 30 40 50 100l/
s2
00
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
1 2 3 4 5
m
0,2
l

9
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
COLIBRI Ceiling
COLIBRI CC 200-600 + ALS 160-200 – One step
p
t
Pap
t
Pa
100200300400500 m
3
/h
p
t
Pap
t
Pa
20 30 40 50 100l/s200
10
20
30
40
50
100
200
300
400
20
25
30
35
40 dB(A)
100
%
0%
1 2 3 4 5
m
0,2
l
COLIBRI CC 250-600 + ALS 200-250 – One step COLIBRI CC 315-600 + ALS 200-315 – Two steps
COLIBRI CC 315-600 + ALS 250-315 – One step
p
t
Pap
t
Pa
200300400500 m
3
/h
p
t
Pap
t
Pa
30 40 50 100200l/s300
10
20
30
40
50
100
200
300
20
25
30
35
40 dB(A)
100
%
0%
2 3 4 5 10
m
0,2
l
p
t
Pap
t
Pa
200 300400500 m
3
/h
p
t
Pap
t
Pa
30 40 50 100200l/s300
10
20
30
40
50
100
200
300
400
20
25
30
35
40 dB(A)
100
%
0%
2 3 4 5 10
m
0,2
l
p
t
Pap
t
Pa
200300400500 m
3
/h
p
t
Pap
t
Pa
30 40 50 100200l/s300
5
10
20
30
40
50
100
200
20
25
30
35
40 dB(A)
100
%
0%
2 3 4 5 10
m
0,2
l
COLIBRI CC 400-600 + ALS 315-400 – One step
ptPa
2003004005001000 m3/h
40 50 100200300 l/s 400
4
5
10
20
30
40
50
100
200
20
25
30
35
40 dB(A)
100%
0%
2 3 4 5 10
m
0,2
l

10
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
COLIBRI CC + ALS – Extract air
Air flow – Pressure drop – Sound level
• The sound level, dB(A), values are applicable to rooms
with an equivalent sound absorption area of 10 m
2.
• For calculating the width of the air stream, air veloci-
ties in the occupied zone or sound levels in rooms
with other dimensions, please refer to our ProAir web
calculation software available for download at
www.swegon.com.
p
t
Pa
100200300400500 m
3
/h
20 30 40 50 100 l/s 200
10
20
30
40
50
100
200
300
20
25
30
35
40 dB(A)
100%
0%
COLIBRI CC 250-600 + ALS 200-250 COLIBRI CC 315-600 + ALS 250-315
p
t
Pa
200300400500 m
3
/h
30 40 50 100200 l/s 300
5
10
20
30
40
50
100
200
20
25
30
35
40 dB(A)
100%
0%
COLIBRI CC 400-600 + ALS 315-400
p
t
Pa
2003004005001000 m
3
/h
40 50 100200300 l/s 400
4
5
10
20
30
40
50
100
200
20
25
30
35
40 dB(A)
100%
0%

11
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
COLIBRI Ceiling
Sizing
• The sound level, dB(A), values are applicable to rooms
with an equivalent sound absorption area of 10 m2.
• Throw l0.2 is measured under isothermal discharge
conditions.
• Recommended max. permissible temperature below
room temperature is 14 K.
• For calculating the width of the air stream, air veloci-
ties in the occupied zone or sound levels in rooms
with other dimensions, please refer to our ProAir web
calculation software available for download at
www.swegon.com.
Sound data – COLIBRI CR - Supply air – Air
diffusers only
Sound power level LW(dB)
Table Kok
Size Mid-frequency (Octave band) Hz
COLIBRI CR 63 125 250 500 1000 2000 4000 8000
125- 400 -2 1 1 4 5 -7 -22 -23
125- 600 -3 2 5 8 1 -8 -23 -22
160-400 3 1 0 3 6 -6 -22 -25
160-600 -1 1 4 8 1 -7 -22 -24
200-500 -1 2 2 2 6 -6 -22 -25
200-600 7 2 2 6 4 -8 -22 -27
250-600 0 1 2 3 5 -7 -24 -25
315- 600 0 1 2 2 2 -7 -24 -23
400-600 -3 0 1 1 5 -8 -24 -20
Tol. ± 2 2 2 2 2 2 2 2
Sound attenuation DL (dB)
Table DL
Size Mid-frequency (Octave band) Hz
COLIBRI CR 63 125 250 500 1000 2000 4000 8000
125- 400 20 15 10 53554
125- 600 20 15 10 53554
160-400 19 14 9 4 3 5 5 4
160-600 19 14 9 4 3 5 5 4
200-500 19 14 8 3 3 4 5 5
200-600 19 14 8 3 3 4 5 5
250-600 16 11 5 4 2 3 4 4
315- 600 14 9 4 2 2 2 3 3
400-600 13 8 4 1 0 0 0 0
Tol. ± 2 2 2 2 2 2 2 2
Sound data - COLIBRI CR - Extract air – Air
diffusers only
Sound power level LW(dB)
Table Kok
Size Mid-frequency (Octave band) Hz
COLIBRI CR 63 125 250 500 1000 2000 4000 8000
250-600 2 8 5 4 3 -2 -10 -17
315- 600 0 8 7 4 3 -3 -10 -18
400-600 2 4 4 3 3 -4 -11 -17
Tol. ± 2 2 2 2 2 2 2 2
Sound attenuation DL (dB)
Table DL
Size Mid-frequency (Octave band) Hz
COLIBRI CR 63 125 250 500 1000 2000 4000 8000
250-600 16 11 5 4 2 3 4 4
315- 600 14 9 4 2 2 2 3 3
400-600 13 8 4 1 0 0 0 0
Tol. ± 2 2 2 2 2 2 2 2

12
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
Sound attenuation DL (dB)
Table DL
Size Mid-frequency (Octave band) Hz
COLIBRI CR
+ ALS,
Two steps
63
125
250
500
1000
2000
4000
8000
160-400 19 14 11 17 24 15 13 15
160-600 19 14 11 17 24 15 13 15
200-500 18 14 10 16 23 15 14 15
200-600 18 14 10 16 23 15 14 15
250-600 15 9 9 20 19 15 16 14
315- 600 13 810 19 16 13 16 16
Tol. ± 2 2 2 2 2 2 2 2
Sound data – COLIBRI CR + ALS – Supply air
– Two steps
Sound power level LW(dB)
Table Kok
Size Mid-frequency (Octave band) Hz
COLIBRI CR
+ ALS,
Two steps
63
125
250
500
1000
2000
4000
8000
160-400 111 9 5 1 -8 -14 -15
160-600 111 9 5 1 -8 -14 -15
200-500 311 10 3 0 -5 -12 -14
200-600 311 10 3 0 -5 -12 -14
250-600 412 8 1 0 -4 -11 -13
315- 600 611 6 1 3 -4 -12 -15
Tol. ± 2 2 2 2 2 2 2 2
Sound attenuation DL (dB)
Table DL
Size Mid-frequency (Octave band) Hz
COLIBRI CR
+ ALS,
One step
63
125
250
500
1000
2000
4000
8000
125- 400 21 16 917 23 16 11 13
125- 600 21 16 917 23 16 11 13
160-400 19 14 10 17 19 12 10 12
160-600 19 14 10 17 19 12 10 12
200-500 16 11 816 18 12 11 11
200-600 16 11 816 18 12 11 11
250-600 13 8 8 16 17 12 12 13
315- 600 11 6 7 19 14 10 10 13
400-600 14 5 8 14 11 10 11 12
Tol. ± 2 2 2 2 2 2 2 2
Sound data – COLIBRI CR + ALS- Supply air
– One step
Sound power level LW(dB)
Table Kok
Size Mid-frequency (Octave band) Hz
COLIBRI CR
+ ALS,
One step
63
125
250
500
1000
2000
4000
8000
125- 400 510 9 5 3 -8 -15 -19
125- 600 510 9 5 3 -8 -15 -19
160-400 4 7 7 4 4 -8 -17 -17
160-600 4 7 7 4 4 -8 -17 -17
200-500 1 7 7 3 3 -5 -13 -14
200-600 1 7 7 3 3 -5 -13 -14
250-600 0 9 6 3 3 -5 -13 -14
315- 600 3 7 4 3 3 -7 -19 -19
400-600 1 6 2 0 5 -9 -24 -23
Tol. ± 2 2 2 2 2 2 2 2
COLIBRI CR + ALS – Extract air
Sound power level LW(dB)
Table Kok
Size Mid-frequency (Octave band) Hz
COLIBRI CR 63 125 250 500 1000 2000 4000 8000
250-600 013 8 1 0 -4 -10 -16
315- 600 412 6 1 3 -4 -13 -18
400-600 5 9 4 2 3 -4 -13 -20
Tol. ± 2 2 2 2 2 2 2 2
Sound attenuation DL (dB)
Table DL
Size Mid-frequency (Octave band) Hz
COLIBRI CR 63 125 250 500 1000 2000 4000 8000
250-600 13 8 8 16 17 12 12 13
315- 600 11 6 7 19 14 10 10 13
400-600 14 5 8 14 11 10 11 12
Tol. ± 2 2 2 2 2 2 2 2

13
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
COLIBRI Ceiling
p
t
Pap
t
Pa
100200300400 m
3
/h
p
t
Pap
t
Pa
20 30 40 50 100 l/s
2
3
4
5
10
20
30
40
50
100
20
25
30
35
40 dB(A)
125
160
200
200
160
1 2 3 4 5
125
m
0,2
l
COLIBRI CR 125-600, 160-600 and 200-600 – Supply air
p
t
Pa
100200300400500 m
3
/h
20 30 40 50 100 l/s 200
2
3
4
5
10
20
30
40
50
100
20
25
30
35
40 dB(A)
125
160
200
200
160
1 2 3 4 5
125
m
0,2
l
COLIBRI CR 250-600, 315-600 and 400-600 – Extract air
p
t
Pa
2003004005001000 m
3
/h
50 100200300400 l/s 500
4
5
10
20
30
40
50
100
200
20
25
30
35
40 dB(A)
250
315
400
COLIBRI CR 250-600, 315-600 and 400-600 – Supply air
p
t
Pa
2003004005001000 m
3
/h
40 50 100200300 l/s 400
2
3
4
5
10
20
30
40
50
100
20
25
30
35
40 dB(A)
250
315
400
400
315
1 2 3 4 5
250
m
0,2
l
Engineering graphs – COLIBRI CR
Airflow – Pressure drop – Sound level – Throw
• The graphs illustrate data for COLIBRI Ceiling recessed
in the ceiling.
• The graphs are not to be used for commissioning.
• The dB(A) values are applicable to rooms with normal
acoustic absorption of 4 dB.
• The dB(C) value is normally 6-9 dB higher than the
dB(A) value.
• Throw for adjusting swirl. For other adjustments, see the
graphs for diffusers with the ALS commissioning box.
COLIBRI CR 125-400, 160-400 and 200-500 – Supply air

14
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
COLIBRI CR + ALS – Supply air
Airflow – Pressure drop – Sound level – Throw
• The graphs illustrate data for COLIBRI Ceiling recessed
in the ceiling.
• The graphs are not meant to be used in conjunction
with commissioning.
• ∇ = Min. airflow required for obtaining sufficient com-
missioning pressure.
• The dB(A) values are applicable to rooms with normal
acoustic absorption of 4 dB.
• The dB(C) value is normally 6-9 dB higher than the
dB(A) value.
• The version for low installation height generates approx.
3 dB(A) higher sound level than the value plotted in the
graph.
COLIBRI CR 125-400 + ALS 100-125 – One step
ptPaptPa
40 50 100200 m3/h
ptPaptPa
10 20 30 40 50 l/s100
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
2 3 4 5 10
m
0,2
l
COLIBRI CR 160-400 + ALS 100-160 – Two steps
ptPaptPa
40 50 100200 m3/h
ptPaptPa
10 20 30 40 50 l/s100
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
2 3 4 5 10
m
0,2
l

15
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
COLIBRI Ceiling
p
t
Pa
40 50 100200 m
3
/h
10 20 30 40 50 l/s 100
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100%
0%
2 3 4 5 10
m
0,2
l
COLIBRI CR 125-600 + ALS 100-125 – One step
p
t
Pap
t
Pa
40 50 100200 m
3
/h
p
t
Pap
t
Pa
10 20 30 40 50 l/s100
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
2 3 4 5 10
m
0,2
l
COLIBRI CR 160-600 + ALS 100-160 – Two steps
COLIBRI CR 160-400 + ALS 125-160 – One step COLIBRI CR 200-500 + ALS 125-200 – Two steps
p
t
Pap
t
Pa
40 50 100200 m
3
/h
p
t
Pap
t
Pa
10 20 30 40 50 l/s100
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
2 3 4 5 10
ml
p
t
Pap
t
Pa
100 200300400 m
3
/h
p
t
Pap
t
Pa
20 30 40 50 100l/s
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
2 3 4 5 10
m
0,2
l

16
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
COLIBRI CR 160-600 + ALS 125-160 – One step
p
t
Pap
t
Pa
40 50 100200 m
3
/h
p
t
Pap
t
Pa
10 20 30 40 50 l/s100
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100%
0%
2 3 4 5 10
m
0,2
l
COLIBRI CR 200-600 + ALS 125-200 – Two steps
p
t
Pap
t
Pa
100 200300400 m
3
/h
p
t
Pap
t
Pa
20 30 40 50 100l/s
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100%
0%
2 3 4 5 10
m
0,2
l
COLIBRI CR 200-500 + ALS 160-200 – One step COLIBRI CR 250-600 + ALS 160-250 – Two steps
p
t
Pap
t
Pa
100200300400500 m
3
/h
p
t
Pap
t
Pa
20 30 40 50 100l/
s2
00
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
3 4 5 10 20
m
0,2
l
p
t
Pap
t
Pa
100 200 300400500 m
3
/h
p
t
Pap
t
Pa
30 40 50 100200l/s
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
2 3 4 5 10
m
0,2
l

17
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
COLIBRI Ceiling
COLIBRI CR 200-600 + ALS 160-200 One step
p
t
Pap
t
Pa
100200300400500 m
3
/h
p
t
Pap
t
Pa
20 30 40 50 100l/
s2
00
10
20
30
40
50
100
200
300
400
500
20
25
30
35
40 dB(A)
100
%
0%
3 4 5 10 20
m
0,2
l
COLIBRI CR 250-600 + ALS 200-250 One step COLIBRI CR 315-600 + ALS 200-315 Two steps
p
t
Pap
t
Pa
200 300400500 m
3
/h
p
t
Pap
t
Pa
30 40 50 100200l/s300
10
20
30
40
50
100
200
300
400
20
25
30
35
40 dB(A)
100
%
0%
3 4 5 10 20
m
0,2
l
p
t
Pap
t
Pa
200300400500 m
3
/h
p
t
Pap
t
Pa
30 40 50 100200l/s300
10
20
30
40
50
100
200
300
400
20
25
30
35
40 dB(A)
100
%
0%
3 4 5 10 20
m
0,2
l

18
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
COLIBRI CR 315-600 + ALS 250-315 One step
p
t
Pap
t
Pa
200300400500 m
3
/h
p
t
Pap
t
Pa
30 40 50 100200l/s300
5
10
20
30
40
50
100
200
20
25
30
35
40 dB(A)
100
%
0%
3 4 5 10 20
m
0,2
l
COLIBRI CR 400-600 + ALS 315-400 One step
p
t
Pa
2003004005001000 m
3
/h
40 50 100200300 l/s 400
4
5
10
20
30
40
50
100
200
20
25
30
35
40 dB(A)
100%
0%
3 4 5 10 20
m
0,2
l

19
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
COLIBRI Ceiling
p
t
Pa
100200300400500 m
3
/h
20 30 40 50 100 l/s 200
5
10
20
30
40
50
100
200
20
25
30
35
40 dB(A)
100%
0%
p
t
Pa
2003004005001000 m
3
/h
40 50 100200 l/s 300
10
20
30
40
50
100
200
300
20
25
30
35
40 dB(A)
100%
0%
p
t
Pa
2003004005001000 m
3
/h
40 50 100200300 l/s 400
5
10
20
30
40
50
100
200
20
25
30
35
40 dB(A)
100%
0%
COLIBRI CR 250-600 + ALS 200-250 COLIBRI CR 315-600 + ALS 250-315
COLIBRI CR 400-600 + ALS 315-400
COLIBRI CR + ALS – Extract air
Air flow – Pressure drop – Sound level
• The sound level, dB(A), values are applicable to rooms
with an equivalent sound absorption area of 10 m
2.
• For calculating the width of the air stream, air veloci-
ties in the occupied zone or sound levels in rooms
with other dimensions, please refer to our ProAir web
calculation software available for download at
www.swegon.com.

20
COLIBRI Ceiling
We reserve the right to alter specifications. 201200713 www.swegon.com
Dimensions and weights
COLIBRI Ceiling
Size AØd I M Weight, kg
125-400 395 124 375 70 1,5
125-600 595 124 575 70 3,5
160-400 395 159 375 70 1,5
160-600 595 159 575 70 3,5
200-500 495 199 475 70 2,5
200-600 595 199 575 70 3,5
250-600 595 249 575 70 3,5
315-600 595 314 575 50 3,5
400-600 595 399 575 50 3,5
Dimensions of opening l x l
Number of discs
Size COLIBRI CC COLIBRI CR
125-400 47 49
125-600 47 49
160-400 47 49
160-600 47 49
200-500 90 100
200-600 90 100
250-600 130 169
315-600 130 169
400-600 130 169
Figure 5. COLIBRI Ceiling.
COLIBRI Ceiling with ALS, 1-step
Size ABCØD Ød E1 E2 F1 F2 G1 G2 H K Weight, kg
125-400 395 282 217 99 125 255 212 113 70 175 132 270 80 3,5
125-600 595 282 217 99 125 255 212 113 70 175 132 270 80 5,5
160-400 395 342 252 124 160 279 236 113 70 188 145 315 80 4,2
160-600 595 342 252 124 160 279 236 113 70 188 145 315 80 6,2
200-500 495 404 288 159 200 314 271 113 70 205 162 375 100 6,0
200-600 595 404 288 159 200 314 271 113 70 205 162 375 100 7,0
250-600 595 504 332 199 250 354 311 113 70 225 182 465 115 8,7
315-600 595 622 388 249 315 395 352 93 50 230 187 575 140 11,8
400-600 595 767 488 314 400 455 –93 –262 –712 175 15,0
COLIBRI Ceiling with ALS, 2-steps
Size ABCØD Ød E1 E2 F1 F2 G1 G2 H K Weight, kg
160-400 395 342 252 99 160 255 212 113 70 175 132 315 80 3,5
160-600 595 342 252 99 160 255 212 113 70 175 132 315 80 5,5
200-500 495 404 288 124 200 279 236 113 70 188 145 355 80 3,2
200-600 595 404 288 124 200 279 236 113 70 188 145 355 80 4,2
250-600 595 504 332 159 250 314 271 113 70 205 162 450 100 7,0
315-600 595 622 388 199 315 334 291 93 50 205 162 550 115 8,7
CL = Center line
Table of contents
Other Swegon Accessories manuals

Swegon
Swegon WCD2 Pacific User manual

Swegon
Swegon ELQZ-2-504 series User manual

Swegon
Swegon WCD2 PARAGON User manual

Swegon
Swegon GOLD series User manual

Swegon
Swegon COOL DXS User manual

Swegon
Swegon DETECT SMEa Guide

Swegon
Swegon CDKa User manual

Swegon
Swegon CASA Smart Sensor User manual

Swegon
Swegon Cooler Series User manual

Swegon
Swegon CASA Smart Sensor SRH User manual