manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. System Sensor
  6. •
  7. Security Sensor
  8. •
  9. System Sensor B110LP User manual

System Sensor B110LP User manual

D150-05-00 1 I56-594-03R
B110LP Plug-in Detector Base
For use with the following smoke detectors:
IN US: 1151, 2151
IN CANADA: 1151A, 2151A
IN EUROPE: 1151E, 2151E
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which pro-
vides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this
manual are available at no charge from System Sensor. (For
installation in Canada, please refer to CAN/ULC-S524,
Standard for the Installation of Fire Alarm Systems and CEC
Part 1, Sec. 32.)
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: The detector used with this base must be
tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.
Specifications
Base Diameter: 6.2 inches (157 mm)
Base Height: 0.95 inches (24 mm)
Weight: 0.3 lb. (137 g)
Mounting: 4-inch square box with or without plaster ring. Min. depth–1.5 inches
3-1/2-inch octagon box. Min. depth–1.5 inches
Operating Temperature Range: 0° to 49°C (32° to 120°F)
Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing
Electrical Ratings - includes base and detector
System Voltage: 12/24 VDC
Maximum Ripple Voltage: 4 Volts peak-to-peak
Start-up Capacitance: 0.02 µF Maximum
Standby Ratings: 8.5 VDC Minimum
35 VDC Maximum
120 µA Maximum
Alarm Ratings: 4.2 VDC Minimum at 10 mA
6.6 VDC Maximum at 100 mA
(Alarm current must be limited to 100 mA (130 mA for models 1151 and 2151) by the
control panel. If it is used, the RA400Z Remote Annunciator operates within the specified
detector alarm currents.)
Reset Voltage: 2.5 VDC Minimum
Reset Time: 0.3 Seconds Minimum
Start-up Time: 34.0 Seconds Maximum
General Description
The Model B110LP detector base is designed for use with
System Sensor models 2151 photoelectronic and 1151 ion-
ization detector heads. This two-wire base is equipped with
screw terminals for the connection of power, ground, and
an optional remote annunciator.
Mounting
The detector base mounts directly to 3-1/2 inch and 4-inch
octagon boxes and 4-inch square boxes, with or without
plaster rings. To mount the base, remove the decorative
ring by rotating it in either direction to unhook the snaps
before separating the ring from the base. Use the screws
supplied with the junction box to attach the base to the box
through the appropriate slots in the base (see Figure 1).
Position the decorative ring around the base and rotate it in
either direction until the ring snaps into place.
D150-05-00 2 I56-594-03R
Installation Guidelines
Allowable loop resistance is an important specification for
control panels as well as for smoke detectors and their
bases. The alarm system cannot be expected to operate cor-
rectly if system components have incompatible allowable
loop resistances.Therefore, before beginning installation,
refer to the control panel manufacturer’s loop resistance
specification to ensure that it is listed as compatible with
the System Sensor base and smoke detector being installed.
System Sensor smoke detectors and mounting bases are
marked with a compatibility identifier as the last digit of a
five-digit code stamped on the back of the product.
Connect detectors only to compatible control units as indi-
cated in System Sensor’s compatibility chart. This chart
consists of a current list of UL-listed control unit/detector
combinations and is available from System Sensor upon
request.
All wiring must be installed in compliance with the
National Electrical Code and all applicable local codes and
any special requirements of the authority having jurisdic-
tion, using the proper wire size. The conductors used to
connect smoke detectors to control panels and accessory
devices should be color-coded to reduce the likelihood of
wiring errors. Improper connections can prevent a system
from responding properly in the event of a fire.
For signal wiring (the wiring between interconnected
detectors), it is recommended that the wire be no smaller
than AWG 18. However, the screws and clamping plate in
the base can accommodate wire sizes up to AWG 12. The
use of twisted pair wiring for the power (+ and -) loop is
recommended to minimize the effects of electrical interfer-
ence.
NOTE: To ensure that electrical connections are super-
vised, do NOT loop wires under terminals 2, 3, and
5 - break the wire at each terminal.
To make electrical connections, strip approximately 3/8" (1
cm) insulation from the end of each wire. Slide the wires
under the clamp plate and tighten the terminal screw.
Check the zone wiring before installing the smoke detector
head. The built-in shorting spring makes it convenient to
do this. After the detector base is wired and attached to the
electrical box, position the shorting spring against terminal
3. Use the slot in the retaining clip to hold the spring
against the terminal, as shown in Figure 1. This shorts the
negative-in and negative-out leads so that loop wiring can
be tested for continuity.
The shorting spring in the base will disengage automatical-
ly when the detector head is removed from the base. DO
NOT remove the shorting spring since it reengages as the
detector head is turned into the base, completing the cir-
cuit.
Tamper-resistance Feature
NOTE: DO NOT use the tamper-resistance feature if the
System Sensor XR2 Removal Tool will be used to
remove detectors from the base.
This detector base can be made tamper resistant so that the
detector cannot be detached without the use of a tool. To
make the base tamper-resistant, break off the smaller tab at
the scribed line on the tamper-resistance tab, on the detec-
tor mounting bracket (see Figure 3A), before installing the
detector.
SNAP ON
DECORATIVE
RING
SCREWS (NOT
SUPPLIED)
DETECTOR
BASE
BOX (NOT
SUPPLIED)
SHORTING
SPRING
Figure 1. Mounting base to box:
A78-1175-01
D150-05-00 3 I56-594-03R
NOTE: IF A REMOTE ANNUN-
CIATOR IS NOT USED,
POLARITY OF THESE
TERMINALS MAY BE
REVERSED.
2
3
4
1
REMOTE
ANNUNCIATOR
2
3
4
1
REMOTE
ANNUNCIATOR
2-WIRE CONTROL PANEL
E
O
L
CLASS A OPTIONAL WIRING
A78-1175-04
Figure 2. Wiring diagram for a typical 2-wire detector system:
To remove the detector from the base after it has been
made tamper resistant, remove the decorative ring by rotat-
ing it in either direction and pulling it away from the base.
Then, insert a small screwdriver into the notch (see Figure
3B), and press the plastic lever toward the mounting sur-
face before rotating the detector counterclockwise for
removal.
Figure 3A. Activating the tamper-resistance feature:
PLASTIC LEVER
BREAK TAB AT
DOTTED LINE BY
TWISTING TOWARD
CENTER OF BASE.
USE SMALL-BLADED
SCREWDRIVER TO
PUSH PLASTIC LEVER
IN DIRECTION OF
ARROW.
A78-1175-03
Figure 3B. Removing detector head from base:
D150-05-00 4 I56-594-03R
©2001 System Sensor
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector base to be free from
defects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector base. No agent, represen-
tative, dealer, or employee of the Company has the authority to increase
or alter the obligations or limitations of this Warranty. The Company’s
obligation of this Warranty shall be limited to the repair or replacement of
any part of the smoke detector base which is found to be defective in
materials or workmanship under normal use and service during the three
year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: System
Sensor, Repair Department, RA #__________, 3825 Ohio Avenue, St.
Charles, IL 60174. Please include a note describing the malfunction and
suspected cause of failure. The Company shall not be obligated to repair
or replace units which are found to be defective because of damage,
unreasonable use, modifications, or alterations occurring after the date of
manufacture. In no case shall the Company be liable for any consequen-
tial or incidental damages for breach of this or any other Warranty,
expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault. Some states do not allow the exclusion
or limitation of incidental or consequential damages, so the above limita-
tion or exclusion may not apply to you. This Warranty gives you specific
legal rights, and you may also have other rights which vary from state to
state.
The smoke detector used with this base is designed to activate and initi-
ate emergency action, but will do so only when it is used in conjunction
with an authorized fire alarm system. This detector must be installed in
accordance with NFPA standard 72.
Smoke detectors will not work without power. AC or DC powered
smoke detectors will not work if the power supply is cut off.
Smoke detectors will not sense fires which start where smoke does not
reach the detectors. Smoldering fires typically do not generate a lot of
heat which is needed to drive the smoke up to the ceiling where the
smoke detector is usually located. For this reason, there may be large
delays in detecting a smoldering fire with either an ionization type detec-
tor or a photoelectric type detector. Either one of them may alarm only
after flaming has initiated which will generate the heat needed to drive the
smoke to the ceiling.
Smoke from fires in chimneys, in walls, on roofs or on the other side of a
closed door(s) may not reach the smoke detector and alarm it. A detector
cannot detect a fire developing on another level of a building quickly or
at all. For these reasons, detectors shall be located on every level and in
every bedroom within a building.
Smoke detectors have sensing limitations, too. Ionization detectors and
photoelectric detectors are required to pass fire tests of the flaming and
smoldering type. This is to ensure that both can detect a wide range of
types of fires. Ionization detectors offer a broad range of fire sensing capa-
bility but they are somewhat better at detecting fast flaming fires than
slow smoldering fires. Photoelectric detectors sense smoldering fires bet-
ter than flaming fires which have little, if any, visible smoke. Because fires
develop in different ways and are often unpredictable in their growth, nei-
ther type of detector is always best, and a given detector may not always
provide early warning of a specific type of fire.
In general, detectors cannot be expected to provide warnings for fires
resulting from inadequate fire protection practices, violent explosions,
escaping gases which ignite, improper storage of flammable liquids like
cleaning solvents which ignite, other similar safety hazards, arson, smok-
ing in bed, children playing with matches or lighters, etc. Smoke detectors
used in high air velocity conditions may have a delay in alarm due to dilu-
tion of smoke densities created by frequent and rapid air exchanges.
Additionally, high air velocity environments may create increased dust
contamination, demanding more frequent maintenance.
Smoke detectors cannot last forever. Smoke detectors contain electronic
parts. Even though smoke detectors are made to last over 10 years, any
part can fail at any time. Therefore, smoke detectors shall be replaced after
being in service for 10 years. The smoke detector system that this detec-
tor is used in must be tested regularly per NFPA 72. This smoke detector
should be cleaned regularly per NFPA 72 or at least once a year.
The Limitations of Property Protection Smoke Detectors
WARNING

Other System Sensor Security Sensor manuals

System Sensor 2351TEM User manual

System Sensor

System Sensor 2351TEM User manual

System Sensor 1424 User manual

System Sensor

System Sensor 1424 User manual

System Sensor WFD Series User manual

System Sensor

System Sensor WFD Series User manual

System Sensor 4451HTA User manual

System Sensor

System Sensor 4451HTA User manual

System Sensor ECO1002 User manual

System Sensor

System Sensor ECO1002 User manual

System Sensor WFD20A User manual

System Sensor

System Sensor WFD20A User manual

System Sensor ECO1005ABL User manual

System Sensor

System Sensor ECO1005ABL User manual

System Sensor B501A User manual

System Sensor

System Sensor B501A User manual

System Sensor 9440X FAAST User manual

System Sensor

System Sensor 9440X FAAST User manual

System Sensor B210LPA User manual

System Sensor

System Sensor B210LPA User manual

System Sensor 2300TB User manual

System Sensor

System Sensor 2300TB User manual

System Sensor B224BI-WH User manual

System Sensor

System Sensor B224BI-WH User manual

System Sensor B112LP User manual

System Sensor

System Sensor B112LP User manual

System Sensor WFD Series User manual

System Sensor

System Sensor WFD Series User manual

System Sensor B501AP User manual

System Sensor

System Sensor B501AP User manual

System Sensor 5151 User manual

System Sensor

System Sensor 5151 User manual

System Sensor JTWB-BCD-5151EIS User manual

System Sensor

System Sensor JTWB-BCD-5151EIS User manual

System Sensor B114LPBT User manual

System Sensor

System Sensor B114LPBT User manual

System Sensor InnovAir DH100ACDCI User manual

System Sensor

System Sensor InnovAir DH100ACDCI User manual

System Sensor L-Series User manual

System Sensor

System Sensor L-Series User manual

System Sensor B110RLP User manual

System Sensor

System Sensor B110RLP User manual

System Sensor B501-WHITE User manual

System Sensor

System Sensor B501-WHITE User manual

System Sensor Innovair SSK451 User manual

System Sensor

System Sensor Innovair SSK451 User manual

System Sensor WFD20EXP User manual

System Sensor

System Sensor WFD20EXP User manual

Popular Security Sensor manuals by other brands

Guide 532 Instructions of use

Guide

Guide 532 Instructions of use

Rielta FOTON-SH2-RK installation guide

Rielta

Rielta FOTON-SH2-RK installation guide

Optex VX Shield series installation instructions

Optex

Optex VX Shield series installation instructions

EDWARDS SYSTEMS TECHNOLOGY EST3 Operation manual

EDWARDS SYSTEMS TECHNOLOGY

EDWARDS SYSTEMS TECHNOLOGY EST3 Operation manual

Milesight EM300 Series user guide

Milesight

Milesight EM300 Series user guide

DoCash Golf user manual

DoCash

DoCash Golf user manual

Besantek BST-CBF01 instruction manual

Besantek

Besantek BST-CBF01 instruction manual

Stahl INTRINSPAK 9001 Series Product information

Stahl

Stahl INTRINSPAK 9001 Series Product information

Interlogix PB501 Installation sheet

Interlogix

Interlogix PB501 Installation sheet

THORLABS SPDMA Operation manual

THORLABS

THORLABS SPDMA Operation manual

Airthings Wave Plus operating manual

Airthings

Airthings Wave Plus operating manual

Endress+Hauser USR30 technical information

Endress+Hauser

Endress+Hauser USR30 technical information

Kyla KSEN-231 Easy start guide

Kyla

Kyla KSEN-231 Easy start guide

AVS Electronics ONE PA manual

AVS Electronics

AVS Electronics ONE PA manual

Reer PI M12 NF operating instructions

Reer

Reer PI M12 NF operating instructions

Eldat RFD01 operating instructions

Eldat

Eldat RFD01 operating instructions

NookBox IRD-23 installation guide

NookBox

NookBox IRD-23 installation guide

Niko 350-20060 manual

Niko

Niko 350-20060 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.