
Model 7706 Multiplexer Module Instructions for use with DAQ6510
077145000 / June 2018
The 7706 includes the following features:
▪Twenty channels of analog input with 300 V,1 A capacity; 60 W, 125 VA maximum
▪Sixteen channels of digital output
▪One event counter/totalizer, which you can use to monitor and control system components and actions,
such as fixtures, limit switches, pass/fail indicators, external voltage sources, loads, door closures, and
revolutions
▪Two analog outputs (±12 V at 5 mA with 16-bit programmability)
▪Two-wire or four-wire resistance measurements (automatically pairs switches for four-wire measurements)
▪Built-in automatic cold junction reference (CJC)
▪Screw terminal connections
The 7706 can be used with the DAQ6510 Data Acquisition and Multimeter System.
If you are using this switching module with the 2700, 2701, or 2750, please see Model 7706
Multiplexer Card User's Manual, Keithley Instruments document PA-719.
Wiring procedure
Use the following procedure to make connections to the 7706 module. Make all connections using correct wire
size (up to 22 AWG).
Connection and wiring procedures in this document are intended for use by qualified
personnel only, as described by the types of product users in the Safety precautions (on
page 40). Do not perform these procedures unless qualified to do so. Failure to recognize and
observe normal safety precautions could result in personal injury or death.
All wiring must be rated for the maximum voltage in the system. For example, if 1000 V is
applied to the front terminals of the instrument, the switching module wiring must be rated
for 1000 V. Failure to recognize and observe normal safety precautions could result in
personal injury or death.
Do not exceed the maximum specifications for the 7706 module. Refer to the specifications
provided in the data sheet. Failure to recognize and observe normal safety precautions could
result in personal injury or death.
The 7706 module provides connections for both hazardous-voltage and low-voltage circuits.
Make sure to install and maintain double insulation between the hazardous-voltage and
low-voltage wiring using supplementary insulation as required. See the "Wire dressing–fully
wired module" figure in this document for more information. Failure to insulate wiring
properly could result in personal injury or death.