Some useful DN codes.
For a full list of “DN Codes” please refer to the service manual for the installed equipment or to one of
the” CDL Pocket Handbooks” R32 or R410A.
ITEM DESCRIPTION VALUE DEFAULT
03 Network address When under network control. 0099: Unset
0001 to 0064 available 0099
06 Stratification control Increases effective return air temperature setting in heating mode (0 to 10K) 0000 to 0010
0002; +2
C
Floor type
0000; 0ºC
0d Auto mode Enable or disable Auto mode 0000 = available 0001 = unavailable 0000 except
SMMSe
0E
SHRMi only
Used when multiple indoor units are served via a single FS box
0000 = normal 0001= multiple units 0000
0F
Heat Mode
Enable or disable Heat Mode 0000 = available
0001 = unavailable
0000
10 Indoor unit model Must be set when replacing indoor printed circuit board
way compact cassette (600 x 600)
0050: air to air heat exchanger
11 Indoor unit capacity 0000 will generate a (L09) fault
M M R A V
M M
R A V
0005 =012*
- 0017
=048*
140*
0011 =024*
- - - -
0001 =
150m3/h
0002 =
250m3/h
0003 =
350m3/h
0004 =
500m3/h
0005 =
650m3/h
0006 =
800m3/h
0007 = 1000m3/h
12 System number
DI/SDI indoor and outdoor units are automatically addressed, this
value may be set manually but it must be done via the wired
controller – on an individual basis. Settings are 0001 to 0030
0001: outdoor unit 1
0002: outdoor unit 2 0099
13 Indoor unit number
Indoor units connected to a common outdoor unit (e.g. twinned
indoor units) will have the same system number - settings are 0001
to 0064. Automatically allocated – but may be manually overridden.
0001: indoor unit 1
0002: indoor unit 2 0099
14 Group master/slave Allows selection of master indoor unit within group.
Automatically allocated but may be manually overridden.
0000: single indoor unit 0001: group
master 0002: group slave
0099
16 Indoor Fan Indoor fan speed selection. Binary addition. 0015 = all speeds available
1 = auto; 2 = low; 4 = medium; 8 = high
except high static
1E
Dead band - auto
Changeover sensitivity in automatic mode. (1 to 10 k adjustable)
0000: 0 K 0010: 10 K 0003
1F Max. Setting Cooling mode maximum temperature setting (18 – 29oC) 0018 = 18oC 0020 = 20oC 0029 = 29oC 29 o C
20 Min. Setting Cooling mode minimum temperature setting (18 – 29oC) 0018 = 18oC 0020 = 20oC 0029 = 29oC 18 o C
21 Max. Setting Heating mode maximum temperature setting (18 – 29oC) 0018 = 18oC 0020 = 20oC 0029 = 29oC 29 o C
22 Min. Setting Heating mode minimum temperature setting (18 – 29oC) 0018 = 18oC 0020 = 20oC 0029 = 29oC 18 o C
23 Max. Setting Dry mode maximum temperature setting (18 – 29oC) 0018 = 18oC 0020 = 20oC 0029 = 29oC 29 o C
24 Min. Setting Dry mode minimum temperature setting (18 – 29oC) 0018 = 18oC 0020 = 20oC 0029 = 29oC 18 o C
25 Max. Setting Auto mode maximum temperature setting (18 – 29oC) 0018 = 18oC 0020 = 20oC 0029 = 29oC 29 o C
26 Min. Setting Auto mode minimum temperature setting (18 – 29oC) 0018 = 18oC 0020 = 20oC 0029 = 29oC 18 o C
28
Auto restart
Enable or disable 0000: disabled 0001: enabled
0000
2d Modes available Binary addition of modes available. 0015= all modes
1 = fan; 2 = cool; 4 = dry 8 = heat 0015