4.0 Specifications
4.1 Plus Series Specifications
MODEL NUMBER UC1A1A020C6TB
CAPACITY 2000 VA (1.4 kW)
Input Input voltage Single phase, 120 Vac, +10% to -30% (*)
Input frequency 45 to 65 Hz
Input capacity 1920 VA
Input power factor Approximate unity (0.98 to 1.0)
Battery Battery rated voltage 96 Vdc
Battery backup time when fully charged
10 min. at full load (**)
with 0.7 power factor at77°F (25°C)
30 min. at half load (**)
Recharge time Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***)
Type of batteries Sealed lead-acid
Output Output voltage Single-phase, 120 volts
Output voltage regulation Within +/- 3%, steady state
Output frequency 50/60 Hz +/- 0.5% in free-running mode (line sync range +/- 1Hz)
Output voltage waveform Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
Rated load power factor 0.7 lagging (0.6 to 1.0)
Voltage transient characteristic +/- 5% under 100% load step change
Rated output current (rms) 16.7A
Maximum output current (peak) 50.0A
Inverter overload capacity 150% for 60 seconds
Crest factor 3.0
Environment Operating temperature 32 to 104°F (0 to 40°C), optimal at 77°F (25°C)
Storage temperature -4 to 104°F (-20 to 40°C)
Operating humidity 30 to 90%, no condensation
Altitude(****) Less than 3000 ft (1000 m) above sea level
External dimensions (2 KVA 120V) 10.00W x 25.50D x 22.50H (254W x 648D x 572Hmm)
Net weight 129 lb (58.6 kg)
Acoustical noise 45 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac) 85%
Switches Bypass switch Automatic bypass is provided when the run switch is in the off
position, if a fault occurs, or if an overload occurs (transfer time is
approximately 4 mS)
Interfaces IBM (TM) AS/400 Pins 5 through 9
LAN Manager Pins 2 and 3 DB9 male connector
Fault detect and input power loss Pins 1 and 4
RS232 ASCII Pins 1 through 8 DB9 female connector (Pin 9 not used)
Options Software for unattended
computer shutdown Contact Toshiba for details on this option
External battery pack Contact Toshiba for details on this option
(*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the
installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used
for battery backup.
(****) At 6000 ft (2000 m) above sea level, output capacity should be derated by 3%.