1
FG-ALS Alarm Locating Unit
Installation Instructions
The FG-ALS Alarm Location Unit is designed to be used with two kinds of TTK analogue sense cables: random FG-ECS, FG-ACS
and pre-connected sense cables FG-ECX, FG-ACX. It allows the leak detection and location of liquids.
The appearance of a fault (leak, cable break) is detected in the following way:
 An audible alarm is triggered;
 A luminous diode turns on;
 A dry contact is activated to transfer the alarm information to remote monitoring equipments.
 JBUS/MODBUS protocol is communicated to BMS.
 The display on the front face shows the leak location (in metre).
To stop the audible alarm, press the “reset” button. The diode and the dry contact remain activated as long as the fault is pre-
sent. When the fault disappears, the diode switched off, the relay returns to its original normal status and the content of the
display disappears.
The maintenance of the system is recommended for every six months minimum.
1. Fixing the FG-ALS Alarm Location Unit
The FG-ALS Alarm Location Unit is available in wall mounted version (165 x 85
x 55 mm).
Two of the three cable glands are placed on the FG-ALS Alarm Unit, the last
one can be screwed in the place of plug PG7.
Use the two fixing holes in the lower part of the unit box. Release the higher
part of the box of the lower part which is maintained by two screws. These two
parts could be easily dismounted after mural fixing. Withdraw carefully the
higher part with the PCB (printed circuit board).
FG-ALS Alarm Locating Unit Description
FG-ALS Alarm Locating Unit Installation
2. Connection and Adjustment
2.1 Power Connection FG-ALS Alarm Unit is powered into 230-240 VAC only.
The maximum section of the cable is of 14 AWG for 230-240 VAC. Use PG9 cable gland for the
cable 230 V.
2.2 Connection of the
Dry Relays
The dry relays are free of potential. The maximum section of the cables is of 18 AWG.
Dry Contact for Leak:
The leak contact transfers the information of leak to a PC (or supervisor), allowing automated
equipment control.
Dry Contact for Cable Break:
A specific contact is activated in case of cable break. A power supply failure also activates this
contact.
Relay of Leak and Relay of Cable Break:
Simple relay: COM-NO-NC
Max. commutated Voltage: 125 VAC / 60 VDC
2.3.Serial Interface
Physical Support Opto-isolated, Two-Wire RS485
2.4. Serial Link Parameters 9500 Baud, 8 Data Bits, 1 bit Stop, no Parity
2.5. Supported Protocol Modbus, Functions 3 and 4
2.3. Adjustment of the
Detection Sensitivity
You can adjust the detection sensitivity, using the potentiometer (P1). The adjustment factory
corresponds to the maximum sensitivity (1 turn).
FG-ALS Alarm Locating Unit Installation Instructions v1.5-092014
The FG-ALS Alarm Location Unit
wall mounted version contains:
 1 FG-ALS Alarm Unit: 230VAC/50Hz
 3 PG cable glands: 2 PG7 + 1 PG9
 1 Installation Instructions
2
1. Connection of Sense Cables FG-ECS or FG-ACS
A junction with a length of 3.5 metres of Belden jumper cable on each length of FG-ECS and FG-ACS, allows a simple connection
to the FG-ALS alarm locating unit.
2. Connection of Sense Cables FG-ECX or FG-ACX
Sense Cables Connection
Caution: All connections of the connector blocks must be done with FG-ALS Alarm Locating Unit supply switched off.
Material recommended (*) for a complete installation with FG-ALS Alarm Locating Unit:
FG-ALS Alarm Locating Unit Installation Instructions v1.5-092014
To connect the various cables (leader cable, power supply and relays) at
the corresponding connector block.
Power supply 230VAC/50Hz P : Live
N : Neutral
: Earth
Leak Relay 1: NO
2 : COM
3 : NC
Cable Break Relay 1 : NO
2 : COM
3 : NC
RS485 1: COM
2 : RT+
3 : RT-
FG-ECS or FG-ACS
or FG-ECX or FG-ACX
A : Green wire
B : White wire
C : Black wire
D : Red wire
Potentiometer (in blue colour) P1 for adjusting sensitivity of detection
FG-ALS Wall Mounted Alarm Location Unit
FG-ECS Water Sense Cable Cut to Length in Roll of 400m
FG-ACS Acids Sense Cable Cut to Length in Roll of 400m
FG-ECX15/7/3 Water Sense Cable in 15/7/3m
FG-ACX15/7/3 Acids Sense Cable in 15/7/3m
CFC100 Hold-down Clips and Adhesive (Set of 100)
ES-EC Signal Tags (Set of 40)
To connect the FG-CLC leader cable, refer “FG-SYS installation guide” chapiter 1, sector 3.3 “Connection of FG-CLC leader ca-
ble”.
The FG-CLC leader cable, connected to the FG-ALS alarm unit with a female connector, at its extremity. The beginning of the
sense cable thus corresponds at its extremity with a male connector.
Connect the first sense cable to the leader cable, coming from the FG-ALS alarm unit.
SOU
Leak
FG-
Female connector
Male connector
End termination
Sense cable FG-ECX/ACX
Sense cable FG-ECS/ACS random
Jumper cable
Sense Cable
P N
ON
Leak Relay Cable Break
Relay
Modbus Slave N°
TTK FG-ALS
TTK - FRANCE
RS485
1 2 3 4 5 6 7 8
Potentiometer
3
ABC steps:
A. Carry out and place a clear and precise installation drawing close to the FG-ALS Alarm Location Unit.
B. Make sure that the following documents are at the disposition of the Customer:
 FG-ALS Alarm Location Unit data sheet
 Drawing of the installation
 Installation Instructions
 Certificate of Compliance
C. Inform the Customer, it is recommended to take out maintenance operation twice per annum on the system.
Company ______
Operator name ________
Date__ /__ /__
Commissioning Guide
This brochure with its photos, illustrations and charts were carefully prepared, but may only be taken as examples. TTK cannot guarantee that the information given contains no errors or omissions and will accept no responsibility
related to the usage of its equipment. TTK's only obligations are those set forth in the Standard Terms and Conditions of Sale and will not under any circumstances be held liable for any incidental, indirect or consequential damages
arising from the sale, resale or misuse of this product. The purchasers are the sole judges of the product's adaptability to the use for which it is destined. FROGSYS and TOPSurveillance are trademarks of TTK SAS.
FG-ALS Alarm Locating Unit Installation Instructions v1.5-092014

Other TTK Security System manuals

TTK FG-SYS User manual

TTK

TTK FG-SYS User manual

TTK FG-NET User manual

TTK

TTK FG-NET User manual

Popular Security System manuals by other brands

Compur Monitors Statox 501 operating instructions

Compur Monitors

Compur Monitors Statox 501 operating instructions

Mercury Security SR10k user guide

Mercury Security

Mercury Security SR10k user guide

Automatic Systems ClearLock 645 Technical manual

Automatic Systems

Automatic Systems ClearLock 645 Technical manual

Gazer CKR4400 user manual

Gazer

Gazer CKR4400 user manual

Radionics 7112 owner's manual

Radionics

Radionics 7112 owner's manual

Risco Agility 3 Installer manual

Risco

Risco Agility 3 Installer manual

M-system 48NDT instruction manual

M-system

M-system 48NDT instruction manual

Hali-Brite HBM 150/2 L-801A Installation and maintenance manual

Hali-Brite

Hali-Brite HBM 150/2 L-801A Installation and maintenance manual

URIPHON wireless2M Instructions for use

URIPHON

URIPHON wireless2M Instructions for use

Visonic PowerMax10 user guide

Visonic

Visonic PowerMax10 user guide

Honeywell ADEMCO Vista-12C Installation and setup guide

Honeywell

Honeywell ADEMCO Vista-12C Installation and setup guide

Ness 5000 Series installation manual

Ness

Ness 5000 Series installation manual

PowerTech PT-1090 user manual

PowerTech

PowerTech PT-1090 user manual

VADDIO 999-60210-000 Complete manual

VADDIO

VADDIO 999-60210-000 Complete manual

Toyota TVSS IIIB installation instructions

Toyota

Toyota TVSS IIIB installation instructions

Lynx MiniVib manual

Lynx

Lynx MiniVib manual

Sensonic BITE ALARM Operation manual

Sensonic

Sensonic BITE ALARM Operation manual

Evido EAD-B1000 Quick installation guide

Evido

Evido EAD-B1000 Quick installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.