turck IMX12-CCM05 Series User manual

Your Global Automation Partner
Instructions for Use
IMX12-CCM05…
Cabinet Guard

Contents
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 2
Contents
1 About these instructions ...................................................................................................................3
1.1 Target groups ...................................................................................................................3
1.2 Explanation of symbols used.........................................................................................3
1.3 Other documents.............................................................................................................3
1.4 Feedback about these instructions ..............................................................................3
2 Notes on the product .........................................................................................................................4
2.1 Product identification .....................................................................................................4
2.2 Scope of delivery..............................................................................................................4
2.3 Turck service .....................................................................................................................4
3 For your safety.....................................................................................................................................5
3.1 Intended use .....................................................................................................................5
3.2 Obvious misuse ................................................................................................................5
3.3 General safety instructions ............................................................................................5
3.4 Notes on Ex protection ...................................................................................................5
4 Product description ............................................................................................................................6
4.1 Device overview...............................................................................................................6
4.1.1 Indication elements.........................................................................................................................7
4.2 Properties and features ..................................................................................................7
4.3 Operating principle .........................................................................................................7
4.4 Functions and operating modes...................................................................................7
5 Installing ...............................................................................................................................................8
6 Connection ...........................................................................................................................................9
6.1 Connecting devices with screw terminals...................................................................9
6.2 Connecting devices with spring-loaded terminals ................................................ 10
6.3 Wiring diagram.............................................................................................................. 10
7 Commissioning................................................................................................................................. 11
8 Operation........................................................................................................................................... 12
8.1 LEDs ................................................................................................................................. 12
8.2 Reading process values via the HART interface...................................................... 12
9 Setting................................................................................................................................................ 13
9.1 Setting the device values via the HART interface................................................... 13
10 Troubleshooting............................................................................................................................... 14
11 Maintenance ..................................................................................................................................... 15
12 Repair ................................................................................................................................................. 15
12.1 Returning devices ......................................................................................................... 15
13 Decommissioning ............................................................................................................................ 15
14 Disposal.............................................................................................................................................. 15
15 Technical data................................................................................................................................... 16
16 Appendix: Approvals and markings............................................................................................. 17
17 Turck subsidiaries — contact information.................................................................................. 18

About these instructions
Feedback about these instructions
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 3
1 About these instructions
These instructions for use describe the structure, functions and the use of the product and will
help you to operate the product as intended. Read these instructions carefully before using the
product. This is to avoid possible damage to persons, property or the device. Retain the instruc-
tions for future use during the service life of the product. If the product is passed on, pass on
these instructions as well.
1.1 Target groups
These instructions are aimed at qualified personnel with knowledge of explosion protection
(e.g. EN 60079-14 etc.) and must be carefully read by anyone mounting, commissioning, oper-
ating, maintaining, dismantling or disposing of the device.
1.2 Explanation of symbols used
The following symbols are used in these instructions:
DANGER
DANGER indicates a dangerous situation with high risk of death or severe injury if
not avoided.
WARNING
WARNING indicates a dangerous situation with medium risk of death or severe in-
jury if not avoided.
CAUTION
CAUTION indicates a dangerous situation of medium risk which may result in minor
or moderate injury if not avoided.
NOTICE
NOTICE indicates a situation which may lead to property damage if not avoided.
NOTE
NOTE indicates tips, recommendations and useful information on specific actions
and facts. The notes simplify your work and help you to avoid additional work.
uCALL TO ACTION
This symbol denotes actions that the user must carry out.
aRESULTS OF ACTION
This symbol denotes relevant results of actions.
1.3 Other documents
Besides this document, the following material can be found on the Internet at www.turck.com:
nData sheet
nQuick Start Guide
nApprovals
nDeclarations of Conformity (current version)
1.4 Feedback about these instructions
We make every effort to ensure that these instructions are as informative and as clear as
possible. If you have any suggestions for improving the design or if some information is missing
in the document, please send your suggestions to [email protected].

Notes on the product
Turck service
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 4
2 Notes on the product
2.1 Product identification
These instructions apply to the following cabinet guards:
nIMX12-CCM05-MTI-1I2T-HC/L
nIMX12-CCM05-MTI-1I2T-HC/L/CC
2.2 Scope of delivery
The scope of delivery includes:
nCabinet guard
nQuick Start Guide
nAdhesive foil (Target) for attaching reflective surfaces
2.3 Turck service
Turck supports you with your projects, from initial analysis to the commissioning of your applic-
ation. The Turck product database under www.turck.com contains software tools for program-
ming, configuration or commissioning, data sheets and CAD files in numerous export formats.
The contact details of Turck subsidiaries worldwide can be found on p. [}18].

For your safety
Notes on Ex protection
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 5
3 For your safety
The product is designed according to state-of-the-art technology. However, residual risks still
exist. Observe the following warnings and safety notices to prevent damage to persons and
property. Turck accepts no liability for damage caused by failure to observe these warning and
safety notices.
3.1 Intended use
The IMX12-CCM… cabinet guard monitors temperature, relative air humidity and the door
status in control cabinets. The devices are suitable for operation in Zone 1.
The devices may only be used as described in these instructions. Any other use is not in accord-
ance with the intended use. Turck accepts no liability for any resulting damage.
3.2 Obvious misuse
nThe device is not a safety component and must not be used for the protection of persons
and property.
3.3 General safety instructions
nThe device meets the EMC requirements for industrial areas. When used in residential areas,
take measures to avoid radio interference.
nThe device may only be assembled, installed, operated, parameterized and maintained by
professionally-trained personnel.
nThe device may only be used in accordance with applicable national and international
regulations, standards and laws.
nThe device must only be used in enclosed housing or control cabinets.
3.4 Notes on Ex protection
nWhen operating the device in a hazardous area, the user must have a working knowledge of
explosion protection (IEC/EN 60079-14, etc.).
nObserve national and international regulations for explosion protection.
nOnly use the device in Ex areas when installed in the appropriate protective housing.
nOnly use the device within the permitted operating and ambient conditions (see certifica-
tion data and Ex approval requirements for use in Ex area ).
nCables and terminals with intrinsically safe circuits must be indicated — use light blue for
color-coding. Separate cables and terminals from non-intrinsically safe circuits or isolate
accordingly (IEC/EN 60079-14).
nComplete certification of intrinsic safety.
nNever connect equipment to intrinsically safe circuits if this equipment was previously used
once in non-intrinsically safe circuits.

Product description
Device overview
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 6
4 Product description
The IMX12-CCM05... cabinet guards are available with removable screw or spring-loaded
terminals.
4.1 Device overview
IMX12-CCM
Err
Ch1
Ch2
Pwr
7 8
5 6
1 2
3 4
15 16
13 14
11 12
9 10
Power
Teach-in
Fault
Status
[mm]
IMX12-CCM
Err
Ch1
Ch2
Pwr
7 8
5 6
1 2
3 4
15 16
13 14
11 12
9 10
Power
Teach-in
Fault
Status
[mm]
fig.1: IMX12-CCM05… – front view fig.2: IMX12-CCM05…CC – front view
mm [Inch]
37.5 [1.48]
125.7 [4.95]
120 [4.72]
110 [4.33]
12.5 [0.49]
116.8 [4.60]
fig.3: Dimensions – IMX12-CCM05…
mm [Inch]
37.5 [1.48]
125.7 [4.95]
120 [4.72]
110 [4.33]
12.5 [0.49]
131.8 [5.19]
fig.4: Dimensions – IMX12-CCM05…CC

Product description
Functions and operating modes
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 7
4.1.1 Indication elements
The devices each have a green Power LED (Pwr). A red Error LED and two yellow Status LEDs are
also provided.
4.2 Properties and features
nSensors for monitoring humidity, temperature and distance
nTeach-in to ambient conditions
nDevice variants with screw or spring-loaded terminal connection
nFreely configurable switching outputs (NC/NO contacts)
nInput for potential-free switching contact
4.3 Operating principle
The cabinet guards of the IMX12-CCM… series monitor temperature, humidity and door status
(open/closed) in control cabinets within the set limit parameters. An humidity/temperature
sensor and a distance sensor are used to detect the ambient conditions. Values above or below
the limits are indicated and reported by LEDs and the corresponding switching output. The
switching contacts indicate limit value overshoots and undershoots to the higher field level.
4.4 Functions and operating modes
The devices use integrated sensors to monitor temperature, humidity and the status the con-
trol cabinet door. For this the measured values are automatically compared with the defined
limit values. The device automatically reports limit value overshoots. Two potential-free,
galvanically isolated switching contacts are provided for this.
The devices can be parameterized via a teach-in function and the HART interface. Potential-free
switching contacts, such as REED sensors, can be connected to the device via a digital input.

Installing
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 8
5 Installing
DANGER
Explosive atmosphere
Risk of explosion due to spark ignition!
Operation in zone 1: Mount the device in an enclosure in accordance with IEC/
EN 60079-0 and with a degree of protection of at least IP54.
Operation in zone 1: When mounting the device, ensure that its permissible
operating temperature is not exceeded even in unfavorable ambient conditions.
NOTICE
Reflective surfaces
Malfunction when monitoring the control cabinet door
Cover glass and highly reflective surfaces on the control cabinet door with matt
adhesive foil (supplied with the device).
The device can be mounted on a DIN rail according to EN 60715 (TH35).
Fasten the device vertically and free-standing on a DIN rail.
Observe a minimum clearance of 40 mm between the housing front and control cabinet
door.
fig.5: DIN rail mounting

Connection
Connecting devices with screw terminals
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 9
6 Connection
WARNING
Consequential damage through incorrect connection
Explosion through device damage!
Observe the connection requirements in all cases.
The inputs and outputs as well as the supply voltage can be connected by screw or spring-
loaded terminals, depending on device type. The removable terminal blocks are coded.
6.1 Connecting devices with screw terminals
Only use cables (rigid or flexible) with a cross section of 0.2…2.5 mm².
When using stranded wire: Secure the wire ends with ferrules.
Insert the stripped cable ends into the guides of the cable glands.
Tighten screws. The max. tightening torque is 0.5 Nm.
0.5 Nm
(4.43 LBS-inc)
0.2…2.5 mm2
(24…13 AWG)
1
2
7 mm
fig.6: Connecting devices with screw terminals

Connection
Wiring diagram
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 10
6.2 Connecting devices with spring-loaded terminals
Only use cables (rigid or flexible) with a cross section of 0.2…2.5 mm².
When using stranded wire: secure the wire ends with ferrules.
Prise open the spring-loaded terminals using a screwdriver.
Insert the stripped cable ends into the guides of the spring-loaded terminals.
Remove the screwdriver.
2
1
0.2…2.5 mm2
(24…13 AWG)
7 mm
fig.7: Connecting the power supply via spring-loaded terminals
6.3 Wiring diagram
GN RD 16 –
15 +
E1
YE 12 –
11 +
YE 10 –
9 +
6 –
5 +
A1
A2
E2
≤
30 VDC
≤ 100 mA
[mm]
[% RH]
[°C]
°C
% RH
mm
HART
fig.8: IMX12-CCM05… wiring diagram

Commissioning
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 11
7 Commissioning
The device is operational automatically once the cables are connected and the power supply is
switched on.
NOTE
Turck recommends that the short circuit monitoring is deactivated when the device
is supplied by a DCS/PLC card.

Operation
Reading process values via the HART interface
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 12
8 Operation
In normal operation, the device performs the following processes automatically:
nReading configuration data
nRecording current measured values (temperature, humidity, door gap, contact E2)
nMonitoring measured values for limit value overshoots and undershoots
If an error occurs during normal operation at one of the integrated sensors, the Err LED is red
and the current consumption increases to >20mA.
8.1 LEDs
The devices each have a green Power LED (Pwr). A red (Err) LED and two status LEDs (Ch1 and
Ch2) are also provided.
The LEDs have the following indication functions:
LED Color Meaning
Pwr Green Device is operational
Green flashing (0.5Hz) Teach-in running
Err Red Error at one or multiple sensors
Short red Manual input error
Red flashing (0.5 Hz) Error during teach-in
Ch1 Yellow Limit value at channel 1 overshot or undershot
Off Parameters within the limit values
Ch2 Yellow Limit value at channel 2 overshot or undershot
Off Parameters within the limit values
8.2 Reading process values via the HART interface
The sensor process values can be read via the HART interface. The process values can be read
via the HART variables with HART command 3. The HART variables for the process values can be
taken from the following table:
Process value HART variables Meaning
Temperature PV unit code Unit in °C
PV Temperature value
Relative air humidity SV unit code Unit in %
SV Value for relative air humidity
Distance TV unit code Unit in mm
TV Distance value

Setting
Setting the device values via the HART interface
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 13
9 Setting
The current values for temperature, humidity and door gap at the particular mounting situation
can be recorded with a teach-in operation. The preset additional values to calculate the limit
value as a percentage can be taken from the preset parameters. The lower and upper limit val-
ues for the particular mounting situation can alternatively be set via the HART interface. The
teach-in operation is controlled by the pushbutton on the front. The tuning time for the limit
values is 30…1440min.
Press the pushbutton for 2…6 s.
aThe Pwr LED flashes green.
The following limit values are preset in the device:
Parameter Lower limit value Upper limit value
Temperature -25 °C +70 °C
Humidity 0% 80%
Door gap 4 cm 130 cm
9.1 Setting the device values via the HART interface
The devices can be configured and parameterized with the HART interface. This requires the
following components:
nFDT/DTM for IMX12-CCM… (free download at www.turck.com)
nHART modem
Preset parameters
Parameter Value
Temperature hysteresis 5 K
Humidity hysteresis 5 %
Door gap hysteresis 5 mm
Addition for temperature limit value calculation 20 %
Addition for humidity limit value calculation 10 %
Addition for door gap limit value calculation 5 %
Measurement interval 1 s
Adjustment time for automatic calibration 240 min
Max. number of limit value overshoots before notification
(temperature)
2
Max. number of limit value overshoots before notification
(humidity)
2
Max. number of limit value overshoots before notification
(door gap)
3
Type of switching outputs NO
Hysteresis for temperature/humidity/door gap On
Automatic limit value calculation On
Manual calibration process Possible

Troubleshooting
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 14
10 Troubleshooting
NOTICE
Reflective surfaces
Malfunction when monitoring the control cabinet door
Cover glass and highly reflective surfaces on the control cabinet door with matt
adhesive foil (supplied with the device).
If the device does not function as expected, first check whether ambient interference is present.
If there is no ambient interference present, check the connections of the device for faults.
If there are no faults, there is a device malfunction. In this case, decommission the device and
replace it with a new device of the same type.

Maintenance
Returning devices
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 15
11 Maintenance
Ensure that the plug connections and cables are always in good condition.
The devices are maintenance-free, clean dry if required.
12 Repair
The device must not be repaired by the user. The device must be decommissioned if it is faulty.
Observe our return acceptance conditions when returning the device to Turck.
12.1 Returning devices
Returns to Turck can only be accepted if the device has been equipped with a Decontamination
declaration enclosed. The decontamination declaration can be downloaded from
https://www.turck.de/en/retoure-service-6079.php
and must be completely filled in, and affixed securely and weather-proof to the outside of the
packaging.
13 Decommissioning
Separate connections and the power supply.
Undo the terminal connections on the device.
Remove the device from its rail fixing as shown in the figures.
fig.9: Undo the device with the screwdriver fig.10: Remove the device from the DIN rail
14 Disposal
The devices must be disposed of properly and do not belong in the domestic waste.

Technical data
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 16
15 Technical data
Technical data IMX12-CCM05-MTI-1I2T-HC/L IMX12-CCM05-MTI-1I2T-HC/L/CC
ID 100030579 100030580
Power supply 0…20mA current loop
Operating voltage 10…28 VDC
Power consumption ≤ 0.32 W
Internal sensors
Distance Triangulations sensor 4…130 cm (relative accuracy < ±1.5 mm,
absolute accuracy < ±20 mm)
Humidity Humidity sensor 0…100 % rel. hum. (±2 % RF in the range 10…90 %)
Temperature Temperature sensor -25…+70 °C (±0.2 °C at 0…65 °C)
Digital outputs
Switching output 1 and 2 < ±30V, < 100 mA (ambient temperature < 45 °C)
Digital input
Potential-free contact NO
Operational readiness Green
Switching status Yellow
Error message Red
Electrical connection
Terminals Screw terminals, 2-pin, pluggable,
coded
Spring-loaded terminals, 2-pin,
pluggable, coded
Terminal cross-section 0.2…2.5 mm²
Mechanical properties
Dimensions (W × H × D) 120 × 12.5 × 117 mm 120 × 12.5 × 128 mm
Weight 135 g
Fixing type Mounting on DIN rail (NS25)
Housing material Polycarbonate/ABS
Ambient conditions
Ambient temperature -25…+70 °C
Storage temperature -25…+80 °C
Protection type IP20
Flammability class per UL 94 V-0
Pollution degree II
Operating height max. 2000 m above sea level
Standards
Voltage resistance and insulation EN 50178, EN 61010-1
Vibration test Acc. to EN 60068-2-6
Shock testing Acc. to EN 60068-2-27
Temperature EN 60068-2-1 Ad, EN 60068-2-1 Bd, EN 60068-2-1
Air humidity EN 60068-2-38
EMC Acc. to EN 61000-4-2/-3/-4/-5/-6/-8, acc. to NAMUR NE21
MTBF at 20 °C 358 years
MTBF at 40 °C 154 years

Appendix
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 17
16 Appendix: Approvals and markings
Approvals
IBExU 16 ATEX 1005 É II 2 G Ex ib op is IIC T4 Gb
CML 21UKEX21126
2503
IECEx IBE 16.0007 Ex ib op is IIC T4 Gb
Ambient temperature Tamb: -25…+70 °C

Turck subsidiaries — contact information
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 18
17 Turck subsidiaries — contact information
Germany Hans Turck GmbH & Co. KG
Witzlebenstraße 7, 45472 Mülheim an der Ruhr
www.turck.de
Australia Turck Australia Pty Ltd
Building 4, 19-25 Duerdin Street, Notting Hill, 3168 Victoria
www.turck.com.au
Austria Turck GmbH
Graumanngasse 7/A5-1, A-1150 Wien
www.turck.at
Belgium TURCK MULTIPROX
Lion d'Orweg 12, B-9300 Aalst
www.multiprox.be
Brazil Turck do Brasil Automação Ltda.
Rua Anjo Custódio Nr. 42, Jardim Anália Franco, CEP 03358-040 São Paulo
www.turck.com.br
Canada Turck Canada Inc.
140 Duffield Drive, CDN-Markham, Ontario L6G 1B5
www.turck.ca
China Turck (Tianjin) Sensor Co. Ltd.
18,4th Xinghuazhi Road, Xiqing Economic Development Area, 300381
Tianjin
www.turck.com.cn
Czech Republic TURCK s.r.o.
Na Brne 2065, CZ-500 06 Hradec Králové
www.turck.cz
France TURCK BANNER S.A.S.
11 rue de Courtalin Bat C, Magny Le Hongre, F-77703 MARNE LA VALLEE
Cedex 4
www.turckbanner.fr
Great Britain TURCK BANNER LIMITED
Blenheim House, Hurricane Way, GB-SS11 8YT Wickford, Essex
www.turckbanner.co.uk
Hungary TURCK Hungary kft.
Árpád fejedelem útja 26-28., Óbuda Gate, 2. em., H-1023 Budapest
www.turck.hu
India TURCK India Automation Pvt. Ltd.
401-403 Aurum Avenue, Survey. No 109 /4, Near Cummins Complex,
Baner-Balewadi Link Rd., 411045 Pune - Maharashtra
www.turck.co.in
Italy TURCK BANNER S.R.L.
Via San Domenico 5, IT-20008 Bareggio (MI)
www.turckbanner.it
Japan TURCK Japan Corporation
ISM Akihabara 1F, 1-24-2, Taito, Taito-ku, 110-0016 Tokyo
www.turck.jp

Turck subsidiaries — contact information
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.01 | 2023/03 | 19
Korea Turck Korea Co, Ltd.
B-509 Gwangmyeong Technopark, 60 Haan-ro, Gwangmyeong-si,
14322 Gyeonggi-Do
www.turck.kr
Malaysia Turck Banner Malaysia Sdn Bhd
Unit A-23A-08, Tower A, Pinnacle Petaling Jaya, Jalan Utara C,
46200 Petaling Jaya Selangor
www.turckbanner.my
Mexico Turck Comercial, S. de RL de CV
Blvd. Campestre No. 100, Parque Industrial SERVER, C.P. 25350 Arteaga,
Coahuila
www.turck.com.mx
Netherlands Turck B. V.
Ruiterlaan 7, NL-8019 BN Zwolle
www.turck.nl
Poland TURCK sp.z.o.o.
Wroclawska 115, PL-45-836 Opole
www.turck.pl
Romania Turck Automation Romania SRL
Str. Siriului nr. 6-8, Sector 1, RO-014354 Bucuresti
www.turck.ro
Russian
Federation
TURCK RUS OOO
2-nd Pryadilnaya Street, 1, 105037 Moscow
www.turck.ru
Sweden Turck Sweden Office
Fabriksstråket 9, 433 76 Jonsered
www.turck.se
Singapore TURCK BANNER Singapore Pte. Ltd.
25 International Business Park, #04-75/77 (West Wing) German Centre,
609916 Singapore
www.turckbanner.sg
South Africa Turck Banner (Pty) Ltd
Boeing Road East, Bedfordview, ZA-2007 Johannesburg
www.turckbanner.co.za
Turkey Turck Otomasyon Ticaret Limited Sirketi
Inönü mah. Kayisdagi c., Yesil Konak Evleri No: 178, A Blok D:4,
34755 Kadiköy/ Istanbul
www.turck.com.tr
USA Turck Inc.
3000 Campus Drive, USA-MN 55441 Minneapolis
www.turck.us

Over 30 subsidiaries and
60 representations worldwide!
www.turck.com
100037995 | 2023/03
100037995
This manual suits for next models
2
Table of contents
Other turck Safety Equipment manuals
Popular Safety Equipment manuals by other brands

INGAL
INGAL ArmorBuffa MASH TL3 COMPLIANT product manual

Assa Abloy
Assa Abloy SARGENT 9400 Series installation instructions

Elkron
Elkron wl31 nstallation and Programmation manual

inVue
inVue NB80 quick start guide

U-Line
U-Line S-21985 Assembly instructions

Collingwood Lighting
Collingwood Lighting Salvus installation instructions