manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco Fire Product
  6. •
  7. Irrigation System
  8. •
  9. Tyco Fire Product ESFR-22 User manual

Tyco Fire Product ESFR-22 User manual

Model ESFR-22
22.4 K-factor Pendent Sprinklers
Early Suppression, Fast Response
Page 1 of 4 DECEMBER 2015 TFP313
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
1 inch NPT or
ISO 7-R 1
Discharge Coefficient
K=22.4 gpm/psi1/2 (320 lpm/bar1/2)
Temperature Ratings
165° F ( 74°C )
205°F (96°C)
Finish
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Compression Screw . . . . . . . . . . Stainless Steel
Hook ...................... Stainless Steel
Strut. . . . . . . . . . . . . . . . . . . . . . . Stainless Steel
Link Assembly. . . . . . . . . . . . . . . . Solder, Nickel
Button ..............Copper, Stainless Steel
Sealing Assembly . . . . . . . . . . . . Nickel w/PTFE
Applications for the TYCO ESFR Sprin-
klers are expanding beyond currently
recognized installation standards. For
information on research fire tests (e.g.,
with flammable liquids and aerosols)
that may be acceptable to an author-
ity having jurisdiction, contact Tyco Fire
Protection Products (TFPP) Technical
Services.
NOTICE
The Model ESFR-22 Sprinklers described
herein must be installed and maintained
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association
(NFPA), in addition to the standards of
any authorities having jurisdiction (e.g.,
FM Global). Failure to do so may impair
the performance of these devices.
The owner is responsible for maintaining
their fire protection system and devices
in proper operating condition. Contact
the installing contractor or product
manufacturer with any questions.
In all cases, the appropriate NFPA or FM
installation standard, or other applicable
standard, must be referenced to ensure
applicability and to obtain complete
installation guidelines. The general
guidelines in this technical data sheet
are not intended to provide complete
installation criteria.
Sprinkler
Identification
Number (SIN)
TY8226
General
Description
TYCO Model ESFR-22 Pendent Sprin-
klers are Early Suppression, Fast
Response Sprinklers having a nominal
K-factor of 22.4 (Ref. to Figure 1). They
are suppression-mode sprinklers that
are especially advantageous as a
means of eliminating the use of in-rack
sprinklers when protecting high-piled
storage.
The Model ESFR-22 Sprinklers are pri-
marily used for ceiling-only sprinkler
protection of (but not limited to) the
following storage applications:
• most encapsulated or non-encap-
sulated common materials including
cartoned, unexpanded plastics
• uncartoned (exposed) expanded
plastics in accordance with NFPA 13
and FM Global standards
• some storage arrangements of
rubber tires, roll paper, flammable
liquids, and aerosols
For more specific criteria, refer to Table
1 as well as the applicable design
standard.
The Model ESFR-22 can protect a
storage arrangement of 40 ft. (12,2 m)
with a ceiling height of 45 ft. (13,7 m)
without requiring in-rack sprinklers.
In addition, it can be installed with a
maximum deflector-to-ceiling distance
of 18 inches (460 mm).
OBSOLETE
TFP313
Page 2 of 4
Storage Type NFPA FM Global
Open Frame (i.e., no solid shelves)
Single, Double, Multiple-Row, or Portable Rack Storage of
Class I-IV and Group A or B Plastics
Refer to NFPA 13
Chapters 16 and 17
Refer to FM Global
2-0 and 8-9
Solid Pile or Palletized Storage of
Class I-IV and Group A or B Plastics
Refer to NFPA 13
Chapters 14 and 15
Refer to FM Global
2-0 and 8-9
Idle Pallet Storage Refer to NFPA 13
Chapter 12
Refer to FM Global
2-0, 8-9, and 8-24
Rubber Tire Storage Refer to NFPA 13
Chapter 18
Refer to FM Global
2-0 and 8-3
Roll Paper Storage
(Refer to the Standard)
Refer to NFPA 13
Chapter 19 Refer to FM Global 8-21
Flammable/Ignitable Liquid Storage
(Refer to the Standard) Refer to NFPA 30 Refer to FM Global 7-29
Aerosol Storage
(Refer to the Standard) Refer to NFPA 30B Refer to FM Global 7-31
Automotive Components in Portable Racks
(Control mode only; refer to the Standard) N/A N/A
N/A – Not Applicable
1" NPT
-Hook
4
-
7
8
-
5
6
-
-Link Assembly
Sealing
Assembly
Button
Strut
-
2
3
-
1
-
Compression
Screw
Deector
Frame
CENTERLINE
OF THERMAL
SENSING
ELEMENT
WRENCH
FLATS
1-3/4"
(44,5 mm)
DIA.
2
3
3-3/16"
(81,0 mm)
1-5/8"
(41,3 mm)
1-9/16"
(39,9 mm)
4
6
5
7
1
8
FIGURE 1
MODEL ESFR-22 (TY8226) EARLY SUPPRESSION, FAST RESPONSE
PENDENT SPRINKLER 22.4 K-FACTOR
TABLE A
MODEL ESFR-22 PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
OBSOLETE
TFP313
Page 3 of 4
Design
Criteria
The following general guidelines pro-
vided for the TYCO Model ESFR-22
Pendent Sprinklers can be used for a
quick reference.
The National Fire Protection Associa-
tion (NFPA) and FM Global (FM Approv-
als) provide installation standards that
must be used to properly design an
automatic sprinkler system utilizing
Early Suppression, Fast Response
(ESFR) Sprinklers. The guidelines pro-
vided by NFPA and FM Approvals may
differ. Consequently, the appropri-
ate standard must be used for a given
installation.
In all cases, the appropriate NFPA or
FM Approvals installation standard
must be referenced to ensure applica-
bility and to obtain complete installa-
tion guidelines. The following general
guidelines are not intended to provide
complete installation criteria.
In addition to this technical data sheet,
the following Technical Data Sheets
describe other TYCO ESFR Sprinklers:
• TFP312 – Model ESFR-25 (TY9226)
K=25.2 Pendent Sprinkler
• TFP315 – Model ESFR-17 (TY7226)
K=16.8 Pendent Sprinkler
• TFP316 – Model ESFR-17 (TY7126)
K=16.8 Upright Sprinkler
• TFP318 – Model ESFR-1 (TY6226)
K=14.0 Pendent Sprinkler
System Type
Wet pipe
Roof Construction
Unobstructed or obstructed construc-
tion (e.g., smooth ceiling, bar joists,
beam and girder, etc.). Where the
depths of the solid structural members
(e.g., beams and stem) exceed 12
inches (302 mm), install ESFR Sprin-
klers in each channel formed by the
structural members.
Ceiling Slope
Maximum 2 inch rise for 12 inch run
(16.7%)
Maximum Coverage Area
100 ft2(9,3 m2)
In some cases, the installation stan-
dards permit a greater coverage area.
Minimum Coverage Area
64 ft2(5,8 m2) per NFPA 13 / FM Global
2-0
Maximum Spacing
• 12 feet (3,7 m) for building heights up
to 30 feet (9,1 m)
• 10 feet (3,1 m) for building heights
greater than 30 feet (9,1 m); in some
cases, installation standards permit
a greater spacing
Minimum Spacing
8 feet (2,4 m)
Minimum Clearance to Commodity
36 inches (914 mm)
Deflector-to-Ceiling Distance
NFPA – 6 to 18 inches (152 to 457 mm)
Centerline of Thermal Sensing
Element-to-Ceiling Distance
FM Global – See FM Global 2-0 for
Storage Sprinklers
Operation
The fusible link assembly is com-
prised of two link halves that are joined
together by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
flowing water.
Installation
TYCO Model ESFR-22 Pendent Sprin-
klers must be installed in accordance
with this section.
General Instructions
Damage to the fusible Link Assem-
bly during installation can be avoided
by handling the sprinkler by the frame
arms only (i.e., do not apply pressure
to the fusible Link Assembly), and by
using the appropriate sprinkler wrench.
Failure to do so can lead to an unstable
link assembly and premature activation
of the sprinkler. Damaged sprinklers
must be replaced.
A leak-tight 1 inch NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 20 to 30
ft.-lbs. (26,8 to 40,2 Nm). Higher levels
of torque can distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler.
Note: Install the Model ESFR-22 Pendent
Sprinkler in the pendent position (Ref.
Figure 2).
Step 1. With pipe-thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting. Do not apply pres-
sure to the Link Assembly, and handle
the Model ESFR-22 Pendent Sprinkler
only by the Frame arms.
Step 2. Use only the W-Type 32 Sprin-
kler Wrench (Ref. Figure 2) to install
the Model ESFR-22 Pendent Sprinkler.
Fully engage (seat) the wrench recess
on the sprinkler wrench flats (Ref.
Figure 1) and wrench-tighten.
Step 3. After installation, remove
the Protective Sprinkler Cap and
inspect the Link Assembly of each
Model ESFR-22 Pendent Sprinkler for
damage. In particular, verify that the
Link Assembly and Hook are positioned
as illustrated in Figure 1, and that the
Link Assembly is not bent, creased,
or forced out of normal position in any
way. Replace damaged sprinklers.
WRENCH
FLATS
PROTECTIVE
SPRINKLER
CAP
APPLY WRENCH
RECESS TO ESFR-22
WRENCH FLATS ONLY
FIGURE 2
W-TYPE 32
SPRINKLER WRENCH
OBSOLETE
GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
TFP313
Page 4 of 4
Copyright © 2015 Tyco Fire Products, LP. All rights reserved.
Care and
Maintenance
TYCO Model ESFR-22 Pendent Sprin-
klers must be maintained and serviced
in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any authorities having
jurisdiction. Contact the installing con-
tractor or product manufacturer with
any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies
Specify: Model ESFR-22 (TY8226),
K=22.4, Early Suppression, Fast
Response Pendent Sprinkler with
(specify) temperature rating, Natural
Brass, P/N (specify):
165° F ( 74°C ) ..................58-459-1-165
205°F (96°C)..................58-459-1-205
Special Order
Sprinkler Assemblies with
ISO 7-1 Thread Connections
Specify: Model ESFR-22 (TY8226),
K=22.4, Early Suppression, Fast
Response Pendent Sprinkler with
ISO 7-1 thread connection, (specify)
temperature rating, Natural Brass,
P/N (specify):
165° F ( 74°C ) ..................58-460 -1-165
205°F (96°C)..................58 - 460-1-205
Sprinkler Wrench
Specify: W-Type 32 Sprinkler Wrench,
P/N 56-001-1-459
OBSOLETE

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product CENTRAL ELOC User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELOC User manual

Tyco Fire Product Gem G102 User manual

Tyco Fire Product

Tyco Fire Product Gem G102 User manual

Tyco Fire Product Gem F938 User manual

Tyco Fire Product

Tyco Fire Product Gem F938 User manual

Tyco Fire Product EC-HS User manual

Tyco Fire Product

Tyco Fire Product EC-HS User manual

Tyco Fire Product TY-QRF User manual

Tyco Fire Product

Tyco Fire Product TY-QRF User manual

Tyco Fire Product Star Luminous S176 User manual

Tyco Fire Product

Tyco Fire Product Star Luminous S176 User manual

Tyco Fire Product CENTRAL ESLO User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESLO User manual

Tyco Fire Product Gem F892X User manual

Tyco Fire Product

Tyco Fire Product Gem F892X User manual

Tyco Fire Product CENTRAL ESLO-20 GB User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESLO-20 GB User manual

Tyco Fire Product CENTRAL Attic User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Attic User manual

Tyco Fire Product Gem F916 User manual

Tyco Fire Product

Tyco Fire Product Gem F916 User manual

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product Gem F890 User manual

Tyco Fire Product

Tyco Fire Product Gem F890 User manual

Tyco Fire Product CENTRAL K11 ECOH User manual

Tyco Fire Product

Tyco Fire Product CENTRAL K11 ECOH User manual

Tyco Fire Product CENTRAL TY-B User manual

Tyco Fire Product

Tyco Fire Product CENTRAL TY-B User manual

Tyco Fire Product CENTRAL ESFR-1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-1 User manual

Tyco Fire Product Gem TFP1 User manual

Tyco Fire Product

Tyco Fire Product Gem TFP1 User manual

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product CENTRAL Royal Flush GB4-EC User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Royal Flush GB4-EC User manual

Tyco Fire Product CENTRAL DS-1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL DS-1 User manual

Tyco Fire Product Gem F978 User manual

Tyco Fire Product

Tyco Fire Product Gem F978 User manual

Tyco Fire Product Star SG-R User manual

Tyco Fire Product

Tyco Fire Product Star SG-R User manual

Tyco Fire Product CENTRAL ELO-231 BVQR User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231 BVQR User manual

Tyco Fire Product Star DS-1 Series User manual

Tyco Fire Product

Tyco Fire Product Star DS-1 Series User manual

Popular Irrigation System manuals by other brands

Tyco TY-B Series manual

Tyco

Tyco TY-B Series manual

Toro ZSERIES 570Z brochure

Toro

Toro ZSERIES 570Z brochure

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Reliable F1-300 quick start guide

Reliable

Reliable F1-300 quick start guide

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Reliable F4FR quick start guide

Reliable

Reliable F4FR quick start guide

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Reliable F1FR42 Series manual

Reliable

Reliable F1FR42 Series manual

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

Reliable RFC30 LL manual

Reliable

Reliable RFC30 LL manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.