
In order to readily perform the System
Inspection Procedure described in the
Care and Maintenance section, it is
recommended that a System Shut-Off
Valve be installed above the Model
CV-2 Swing Check Valve, as shown in
Figure 1. The System Shut-Off Valve
should be a listed or approved (as ap-
propriate) indicating valve with a su-
pervisory switch to monitor the nor-
mally open position.
System Air Pressure Requirements
Graph B shows the minimum Elec-
tric/Pneumatic Double Interlock Pre-
action System air pressure require-
ments as a function of the water supply
pressure. Use of an automatic air or
nitrogen device is recommended and
may be required by the Authority Hav-
ing Jurisdiction.
NOTE
The dew point of the air or nitrogen
must be maintained below the lowest
ambient temperature to which the
Double Interlock Preaction System
piping will be exposed, or as required
by the Authority Having Jurisdiction.
Introduction of moisture into the sys-
tem piping that is exposed to freezing
temperatures can create ice build up
which could prevent proper operation
of the system.
Friction Loss
The nominal pressure losses versus
flow rate for the 2-1/2 inch (DN65)
combination of the Model DV-3 Deluge
Valve, Grooved End Elbow, and Model
CV-2 Swing Check Valve are shown in
Graphs A-1 and A-2.
The approximate friction losses, based
on the Hazen and Williams formula
and expressed in equivalent length of
Schedule 40 pipe, with C = 100 is 13.7
feet and with C = 120 is 19.2 feet. The
equivalent length of pipe has been cal-
culated on the basis of the flow rates
typically used with a 2-1/2 inch (DN65)
system.
Electric/Pneumatic Double Inter-
lock Preaction Trim
The DV-3 Electric/Pneumatic Double
Interlock Trim is illustrated in Figure 3.
The nipples utilized in the trim arrange-
ment are Schedule 40 steel per ASTM
A53 or A135 and they are threaded per
ANSI Standard B1.20.1. Fittings are
either malleable iron per ANSI B16.3
or cast iron per ANSI B16.4.
NOTE
Do not increase the length of the nipple
between the Solenoid Valve and the
Dry Pilot Actuator or the nipple above
the Dry Pilot Actuator. Increasing
either of these two nipple lengths may
impair operation of the system.
Operation
As indicated in the General Descrip-
tion section, two independent events
resulting in opening of both the Dry
Pilot Actuator and the Solenoid Valve
must occur to actuate the Model DV-3
Electric/Pneumatic Double Interlock
Preaction System.
When the Double Interlock Preaction
System is set for service, the dia-
phragm chamber of the Model DV-3
Deluge Valve is pressurized through
the diaphragm chamber supply con-
nection. The Model DV-3 Deluge Valve
is a differential type valve which de-
pends upon the water pressure in the
diaphragm chamber to hold the center
valve assembly closed against the
water supply pressure. The Model
DV-3 Deluge Valve has a nominal trip
ratio of 2.5 to 1, i.e., the valve operates
when pressure in the diaphragm
chamber is reduced to approximately
two-fifths of the water supply pressure.
The Model DV-3 Automatic Resetting
Deluge Valve is described in TFP1350.
Opening of both the Dry Pilot Actuator
and the Solenoid Valve (16 & 17 - Fig.
3), or operating the Manual Control
Station (4 - Fig. 3) will release water
from the DV-3 diaphragm chamber
faster than it can be replenished
through the 1/8 inch (3,2 mm) diameter
orifice of the Priming Supply Restric-
tion (9 - Fig. 3). A rapid pressure drop
then results in the diaphragm chamber
and the differential between the dia-
phragm chamber and the force differ-
ential holding the center valve assem-
bly down is eliminated. The water
supply pressure then forces the center
valve assembly open, permitting a flow
of water to the Double Interlock Preac-
tion System piping. Water flowing into
the system also flows to the Waterflow
Pressure Alarm Switch (Fig. 3), which
actuates the system alarm signal.
Also, water flowing into the system is
directed to the Model C-1 Pressure
Relief Valve (20 - Fig. C) which, upon
operation, constantly vents the DV-3
diaphragm chamber so as to maintain
the DV-3 Valve in the open (operated)
position.
The Double Interlock Preaction Sys-
tem will automatically operate only
when both the Solenoid Valve and the
Dry Pilot Actuator are open at the
same time. Opening of just the Dry
Pilot Actuator (e.g., a lift truck acciden-
tally dislodges a sprinkler) or just en-
ergizing the Solenoid Valve (e.g., an
accidental operation of an electric pull
station) will only cause an alarm, via
the low air pressure alarm switch or the
deluge valve releasing panel, as appli-
cable, to indicate that the system re-
Page 5 of 10
TFP1462
FIGURE 3 — PART 2 of 2
2-1/2 Inch (DN65)
DOUBLE INTERLOCK
PREACTION TRIM
(See Page 4 for Illustration)
1/4" Tubing Connector CH1..
1/2" Plug 2............. CH
46-005-1-0023 1/4" Gauge Test Valve 2..
4 Model MC-1 Manual
Control Station 52-289-2-0011.........
10 Model AD-1 Automatic
Drain Valve 52-793-2-0041...........
29
1/2" Tubing Connector CH3..
13
92-211-1-003
92-343-1-007
22
Drip Funnel Bracket
Drip Funnel
1
1...........
....
26
92-032-1-0023/32"VentFitting .......1
28
8 52-353-1-0051.........1/2" Y-Strainer
7
92-322-1-002
1/2" Spring Loaded
1CheckValve ..........
46-050-1-0041/2" Ball Valve 2.........15
11
3/4" Plug 1............. CH
1/4" Plug 2............. CH
1/2" x 30" Tubing CH3.......
NO.
1
QTY.DESCRIPTION P/N
92-343-1-005
300 psi/ 2000 kPa
2Water Pressure Gauge . .
18
32
92-211-1-005
Drip Funnel Connector 1
..
12
20
92-020-1-009
9 Priming Supply
1Restriction ............
30
31
2
92-343-1-012
250 psi/ 1750 kPa
1Air Pressure Gauge . . . . .
19
16 Model DP-1 Dry Pilot
Actuator 52-280-1-0011..............
21 1/4" Pressure Relief
Valve 92-343-1-0201................
6 1/2" Swing Check Valve 46-049-1-0042.
46-047-1-00414 1/2" Globe Valve 1.......
52-287-1-02424 VDC Solenoid Valve 1..17
Waterflow Pressure
Alarm Switch (PS10-2A) 25711.
Low Air Pressure
Alarm Switch (PS40-1A) 25721.
92-343-1-023
Pressure Operated Relief
1Valve,PORV ..........
1-1/4" Angle Valve
2-1/2" Grooved End 90°
Elbow, Figure 510
2-1/2" Rigid Grooved End
Coupling, Figure 772
1/2" x 1/4" x 1/2" Tee
System Label
..............
39
25
24
23
5
38 1/2" Tee
3.... CH
N/A1..........
51025S
77225ASC
46-048-1-007
CH
1
2
......
....
2......
10
1/4" x 30" Tubing CH2.......27
1/2" x Close Nipple
1/4" x 3" Nipple
1/2" 90° Elbow
............
..............
1/2" x 1/4" Reducing
43
42
35
34
33
1/2" Union
Bushing
2
2
11
7
1
........
.....
.........
CH
CH
CH
CH
CH
36 1/2" 45° Elbow 1......... CH
................
1/2" x 1/4" Reducing37
Elbow CH1
1/2" x 1/2" x 3/4" Tee40 1.... CH
1-1/4" x 1/2" x 1-1/4" Tee41 1.CH
1/2" x 1-1/2" Nipple44 30..... CH
45 1/2" x 2" Nipple 1 CH........
46 1/2" x 2" Nipple 3 CH........
47 1/2" x 3-1/2" Nipple 1 CH.....
48 1/2" x 3-1/2" Nipple 1 CH.....
49 1/2" x 4-1/2" Nipple 3 CH.....
50 1/2" x 7-1/2" Nipple 1 CH.....
51 1/2" x 8-1/2" Nipple 1 CH.....
52 1/2" x 10-1/2" Nipple 1 CH....
53 1/2" x 11-1/2" Nipple 1 CH....
54 1-1/4" x Close Nipple 2 CH....
55 1-1/4" x 3" Nipple 1 CH.......
All Fittings and Nipples are galvanized
(Standard Order).
NOTE: