Tyco DV-5A User manual

Page 1 of 18 JUNE 2022 TFP1421
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/dv-5a-auto-
si-pre-act-fire-pro-8-dn40-200
DV-5aAutomatic Water Control Valve, Single
Interlock Preaction, Electric Actuation, Fire Protec-
tion Systems 1 1/2 to 8 Inch (DN40 to DN200)
General
Description
The TYCO DV-5aAutomatic Water
Control Valve Single Interlock Preaction
Electric Actuation is a diaphragm type
valve that can be used in single inter-
lock preaction fire protection systems.
When properly trimmed, the double
seat design of the DV-5aValve also
provides actuation of fire alarms upon
system operation.
The diaphragm style design of the
DV-5aValve allows external resetting,
providing for easy resetting of a deluge
system without having to open a valve
handhole cover to manually reposition
a clapper and/or latch mechanism.
Simply re-pressurizing the diaphragm
chamber resets the valve.
The DV-5afeatures internal and exter-
nal coating of the valve to provide
corrosion resistance. The external cor-
rosion resistance of the epoxy coating
permits the use of the DV-5ain cor-
rosive atmospheres associated with
many types of industrial processing
plants and outdoor installations.
The DV-5aSingle Interlock Preac-
tion Electric Actuation Valve is offered
with or without a System Main Control
Valve.
The DV-5aSingle Interlock Preaction
Electric Actuation Valve utilizes auto-
matic sprinklers and a supplemental
detection system, comprised of electric
detection comprised of heat detectors,
smoke detectors, and manual pull sta-
tions. Actuation of the detection system
automatically operates (releases) the
DV-5aValve, allowing water to flow
into the sprinkler piping system and to
be discharged from any sprinklers that
may subsequently open.
Available End Connections and Weights — lb (kg)
End Connection Nominal Valve Size
ANSI Inches
(DN)
Inlet Outlet 1 1/2
(40)
2
(50)
3
(80)
4
(100)
6
(150)
165,1
mm
8
(200)
Thread Thread 26
(11,8)
25
(11, 3) N/A N/A N/A N/A N/A
Groove Groove 25
(11, 3)
25
(11, 3)
60
( 27, 2 )
95
(4 3,1)
177
(80,3)
177
(80,3)
327
(148,3)
Flange Groove N/A N/A 66
(30,0)
106
(4 8,1)
190
(86,2) N/A 346
(157,0 )
Flange Flange N/A N/A 72
(32,7)
116
(52,6)
204
(92,5) N/A 365
(165,6)

TFP1421
Page 2 of 18
Nominal
Valve
Size
ANSI
Inches
(DN)
Flange Drilling Specification
Nominal Dimensions in Inches and (mm)
ANSI B16.1a
(Class 125) ISO 7005-2
(PN16)bJIS B 2210
(10K) AS 2129
(Table E)
A B N A B N A B N A B N
3
(80)
6.00
(152,4)
0.75
(19,0) 46.30
(160,0)
0.75
(19,0) 85.90
(150,0)
0.59
(15,0) 85.75
(146,0)
0.71
(18,0) 4
4
(100)
7.50
(190,5)
0.75
(19,0) 87. 0 9
(180,0)
0.75
(19,0) 86.89
(175,0)
0.60
(15,0) 87. 0 0
178,0)
0.71
(18,0) 8
6
(150)
9.50
(241,3)
0.88
(22,2) 89.45
(240,0)
0.91
(23,0) 89.45
(240,0)
0.75
(19,0) 89.25
(235)
0.87
(22,0) 8
8
(200)
11.75
(298,5)
0.88
(22,2) 811.61
(295,0)
0.91
(23,0) 12 11.42
(290,0)
0.75
(19,0) 12 11.50
(292,0)
0.87
(22,0) 8
NOTES:
a. Same drilling as for
ANSI B16.5 (Class 150) and
ANSI B16.42 (Class 150)
b. Same drilling as for
BS 4504 Section 3.2 (PN16) and
DIN 2532 (PN16)
Item Description Qty.
Nominal Valve Size ANSI Inch (DN)
1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150)e8 (DN200)
P/N P/N P/N P/N P/N P/N
1Valve Body 1N/R N/R N/R N/R N/R N/R
2Diaphragm 1545000020 545000020 545000030 545000040 545000060 545000080
3Diaphragm Cover 1N/R N/R N/R N/R N/R N/R
4 Hex Bolt, Short 2a545100001 545100001 545100002 545100003 545100004 545100003
5Hex Bolt, Long 2545100011 545100011 545100012 545100013 545100014 545100015
6Lift Washer 2bN/A N/A 545100021 545100022 545100023 545100022
7Hex Nut 2545100031 545100031 545100032 545100033 545100034 545100033
8Hoist Ring 2545100041 545100041 545100041 545100041 545100041 545100041
9Flat Washer 2N/A N/A 545100024 545100025 545100026 545100025
NOTES
a. Hex Bolt, Short, Qty. 6 in 6 and 8 inch (DN150 and DN200) assemblies.
b. Lift Washer not used in 1 1/2 and 2 inch (DN40 and DN50) assemblies.
c. N/R = Not Replaceable.
d. Order replacements parts only via Part Numbers given, do not replace Hex Bolt, Hex
Nut, Lift Washer or Hoist Ring with common hardware parts.
e. Also applicable to metric 165,1 mm size.
Dim. A
Bolt Circle
Diameter
Dim. B
Bolt Hole
Diameter
Qty. N
Number of
Bolt Holes
1-1/2 AND 2 INCH
VALVES ONLY
6 AND 8 INCH
VALVES ONLY
79 5
6
3
4
1
75
3
1
1
2
5
9
1
2
3
8
4
7
6
FIGURE 1
DV-5aVALVE ASSEMBLY AND REPLACEMENT PARTS
TABLE A
FLANGE DRILLING SPECIFICATIONS

TFP1421
Page 3 of 18
Port Port Description Port Sizes, NPT Inch per ANSI B1.20.1
1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150)a8 (DN200)
P1 Diaphragm Chamber Supply 1/2 1/2 1/2 1/2 1/2 1/2
P2 Water Supply Pressure & Alarm Test 1/2 1/2 1/2 1/2 1/2 1/2
P3 Alarm Actuation 3/4 3/4 3/4 3/4 3/4 3/4
P4 Automatic Drain Valve 1/2 1/2 1/2 1/2 1/2 1/2
P5 System Drain 3/4 3/4 3/4 3/4 3/4 3/4
P6 Main Drain 3/4 3/4 1 1/4 222
P7 System Air Supply 1/2 1/2 1/2 1/2 1/2 1/2
NOTES
a. Also applicable to metric 165,1 mm.
FIGURE 2A
FIGURE 2C
FIGURE 2B
FIGURE 2D
SYSTEM DRAIN CONDITION
WATER SUPPLY SHUT OFF
DRAIN FROM SYSTEM
SET CONDITION
WATER SUPPLY
SYSTEM OPEN TO ATMOSPHERE
ALARM PORT
WATERFLOW
TO ALARM
WATER SUPPLY
PRESSURE &
ALARM TEST
SYSTEM
DRAIN
OPEN
SYSTEM
DRAIN
OPEN
MAIN
DRAIN
CLOSED
MAIN
DRAIN
OPEN
DIAPHRAGM
CHAMBER
SUPPLY
FROM
UPSTREAM
SIDE OF
SHUT-OFF
VALVE
DIAPHRAGM
CHAMBER
DIAPHRAGM
CHAMBER
OPEN TO
ATMOSPHERE
VALVE
WATERWAY
DIAPHRAGM
SEAT
VALVE
WATERWAY
DIAPHRAGM
CHAMBER
SUPPLY
FROM
UPSTREAM
SIDE OF
SHUT-OFF
VALVE
DIAPHRAGM
AUTOMATICALLY
FLEXES TO
ITS SEATED
POSTION
DIAPHRAGM
CHAMBER
OPEN TO
ATMOSPHERE
DIAPHRAGM
RETRACTS
OPENING
VALVE
WATERWAY
VALVE
WATERWAY
DIAPHRAGM
SEAT
VALVE
WATERWAY
OPERATED CONDITION
WATER SUPPLY SHUT OFF
RESIDUAL DRAIN CONDITION
WATERFLOW FROM WATER SUPPLY
WATERFLOW TO SYSTEM
RESIDUAL DRAIN FROM SYSTEM
SYSTEM
AIR
SUPPLY
AUTOMATIC
DRAIN VALVE
OPEN TO
ATMOSPHERE
AUTOMATIC
DRAIN VALVE
CLOSED
FIGURE 2
DV-5aVALVE OPERATION, PREACTION SYSTEMS

TFP1421
Page 4 of 18
Typically, the system designer selects
the detection components for a single
interlock preaction system that will
respond to a fire sooner than the auto-
matic sprinklers. Consequently, the
system will experience a minimal delay
in water delivery over that for a wet pipe
sprinkler system because the system
will have essentially filled with water
before a sprinkler operates. The DV-5a
Single Interlock Preaction Electric
Actuation Valve automatically super-
vises the integrity of the overall system.
Supervision is provided by monitoring a
relatively low air pressure in the system
via a low pressure alarm switch so as
to detect leaks in the system that oth-
erwise would result in unwanted water
discharge should the system operate in
a fire condition.
Supervised single interlock preac-
tion systems are generally used to
protect areas where there is danger
of serious water damage that might
result from damaged automatic sprin-
klers or piping. Typically, such areas
include computer rooms, storage
areas for valuable artifacts, libraries,
and archives.
Single interlock preaction systems are
also effectively used to protect proper-
ties where a pre-alarm of a possible fire
condition may allow time for fire extin-
guishment by alternate suppression
means, prior to a sprinkler discharge.
In the event the fire cannot otherwise
be extinguished, the preaction sprinkler
system will then perform as the primary
fire protection system.
NOTICE
The DV-5aSingle Interlock Preaction
Electric Actuation Valve described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the NATIONAL FIRE PRO-
TECTION ASSOCIATION (NFPA), in
addition to the standards of any other
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
Listing and Approvals are based on
DV-5a Single Interlock Preaction Elec-
tric Actuation Valve being trimmed as
described in Figure 5.
DV-5AValve
Components for the 1 1/2 in. to 8 in.
(DN40 to DN200) DV-5aValve are
shown in Figure 1. The DV-5aValve
is for vertical installations. It is rated
for use at service pressures of 20 to
300 psi (1,4 to 20,7 bar).
The take-out dimensions are shown
in Figure 3, and flanged connec-
tions are available drilled per ANSI,
ISO, AS, and JIS specifications
(see Table A). Threaded inlet and outlet
connections are available in NPT or ISO
7-1. Threaded port connections are
NPT threaded.
Note: PN16 flanges are pressure rated
to 16 bar.
Valve Trim
The maximum pressure rating for the
Single Interlock Preaction Electric
Actuation is dependent on the sepa-
rately ordered solenoid valve per Tech-
nical Data Sheet TFP2180.
When the system pressure is greater
than 175 psi (12,1 bar), provision is
to be made to replace the standard
order 300 psi (20,7 bar) Water Pres-
sure Gauges with separately ordered
600 psi (41,4 bar) Water Pressure
Gauges.
If the addition of an Alarm Control Valve
is desired or required by the local AHJ,
the Alarm Control Valve noted as Item
H in Figure 8 is to be a separately
ordered electronically supervised nor-
mally open valve.
External trim connections are NPT
threaded. EMEA trim is provided with
NPT x ISO 7-1 thread adapters.
Pressure Loss
See Graph A
Detection System
See the Electric Actuation subsection
System Air Pressure Requirements
The supervisory air (nitrogen) pressure
is to be 10 ± 2 psi (0,69 ±0,07 bar). The
use of a higher supervisory pressure
is subject to approval by the author-
ity having jurisdiction, and it should
be understood that the use of a higher
supervisory pressure may increase
water delivery time. The use of a lower
8 Inch (DN200)
6 Inch (DN150)
4 Inch (DN100)
3 Inch (DN80)
2 Inch (DN50)
1-1/2 Inch (DN40)
22-3/8"
(569 mm)
16-3/4"
(425 mm)
13-3/4"
(349 mm)
10-3/16"
(260 mm)
10-3/16"
(260 mm)
27-7/16"
(697 mm)
DIMENSIONS SHOWN
ARE APPLICABLE TO
ALL END CONNECTION
CONFIGURATIONS
AVAILABLE PER
VALVE SIZE
FIGURE 3
DV-5aVALVE
TAKE-OUT DIMENSIONS

TFP1421
Page 5 of 18
supervisory pressure may prevent
clearing the alarm of the Supervisory
Low Pressure Switch (Item T - Figure 8),
which is factory set to alarm at 5 ± 1
psi (0,34 ± 0,07 bar) on decreasing
pressure. The supervisory air supply
pressure of 10 ± 2 psi (0,69 ± 0,07 bar)
can be provided by any of the follow-
ing methods. Refer to the applicable
data sheet for laboratory approval
information.
• Model G16AC812 (self contained)
Automatic Supervisory Air Supply
described in Technical Data Sheet
TFP1620.
• A maximum 200 psi (13,8 bar) plant
air supply in combination with the
Model AMD-1 Air Maintenance
Device described in Technical Data
Sheet TFP1221.
• A maximum 3000 psi (206,9 bar)
nitrogen cylinder in combination with
the Model AMD-3 Nitrogen Mainte-
nance Device described in Technical
Data Sheet TFP1241.
Note: The dew point of the air or nitrogen
supply for a system exposed to freezing
conditions must be maintained below the
lowest ambient temperature to which the
system piping will be exposed. Introduction
of moisture into the system piping can
create ice build-up that could prevent
proper operation of the system.
The Supervisory Low Pressure Switch
(Item T - Figure 8) is factory set at
5 ± 1 psi (0,34 ± 0,07 bar) on decreas-
ing pressure. The Pressure Relief Valve
(Item S - Figure 8) is factory set to fully
open at 25 ± 2 psi (1,72 ± 0,14 bar) and
it begins to crack open at a pressure of
about 18 psi (1,24 bar).
Materials of
Construction
Valve Body
Epoxy coated ductile iron per ASTM
A536-77, Grade 65-45-12
Diaphragm Cover
Epoxy coated ductile iron per ASTM
A536-77, Grade 65-45-12
Diaphragm
Polyester fabric reinforced, TEFLON
coated, EPDM rubber per ASTM D2000
Diaphragm Cover Fasteners
Aluminum zinc coated steel
Common Hardware Trim
•
Common hardware pipe ttings are
galvanized or black as required and
are malleable per ASME B16.3.
•
Common hardware pipe nipples are
galvanized or black as required and
are Schedule 40 per ASTM A53 or
A135.
•
Common hardware compression
ttings are brass per ASTM B16.
•
Common hardware tubing is Type L
copper per ASTM B88.
3 INCH (DN80)
2 INCH (DN50)
4 INCH (DN100)
8 INCH (DN200)
1-1/2 INCH (DN40)
6 INCH (DN150), 165,1 mm
200 400 1000 3000200060010050
50002000 3000 1000070001000600400200
4000
15000
9.0
8.0
4.0
6.0
5.0
7.0
3.0
2.0
1.0
0.7
0.9
0.8
0.5
0.4
0.6
0.3
NOMINAL PRESSURE DROP IN BAR
(1 PSI = 0,06895 BAR)
FLOW RATE IN LITERS PER MINUTE (LPM)
(1 GPM = 3,785 LPM)
NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI)
FLOW RATE IN GALLONS PER MINUTE (GPM)
0,022
0,080
0,030
0,040
0,060
0,050
0,070
0,100
0,090
0,200
0,300
0,400
0,500
0,600
GRAPH A
DV-5aVALVE
NOMINAL PRESSURE LOSS VERSUS FLOW

TFP1421
Page 6 of 18
Operation
The TYCO DV-5aValve is a diaphragm
style valve that depends upon water
pressure in the Diaphragm Chamber
(see Figure 2A) to hold the Diaphragm
closed against the water supply
pressure.
When the DV-5aValve is set for service,
the Diaphragm Chamber is pressurized
through the trim connections from the
inlet side of the system’s main control
valve.
Opening the Electric Actuation Trim
trips the Model MRA-1 Manual Reset
Actuator. Tripping the MRA-1 releases
water from the DV-5aDiaphragm
Chamber faster than it can be replen-
ished through a 1/8 in. (3,2 mm) restric-
tion located in the Diaphragm Chamber
Supply Connection. Release of water
through the MRA-1 results in a rapid
pressure drop in the DV-5aDiaphragm
Chamber. The force differential applied
through the Diaphragm to hold the
Diaphragm in the set position is then
reduced below the valve trip point. The
water supply pressure then forces the
Diaphragm open permitting water to
flow into the system piping, as well as
through the Alarm Port to actuate the
system alarms (see Figure 2B).
Upon opening of the DV-5aValve, the
Model MRA-1 Manual Reset Actuator
opens to constantly vent the DV-5aDia-
phragm Chamber to hydraulically latch
the DV-5ain the tripped position until
manually reset.
In standby mode, the integrity of the
system piping is supervised by a low
pressure alarm switch.
See the Electric Actuation section for
additional information.
Electric
Actuation
The Electric Actuation Trim forms a part
of the laboratory approval of the DV-5a
Valves and is necessary for their proper
operation.
The Electric Actuation Trim is required
for electric operation of the DV-5aValve
by a detection system consisting of
electrical devices such as heat sen-
sitive thermostats, smoke detectors,
and/or electric manual pull stations as
shown in Figure 4.
Note: For Single Interlock Preaction
Systems with Electric Actuation,the system
designertypicallyselects electric detection
devices that will operate sooner than the
automatic sprinklers chosen for use on the
sprinkler piping.
Dimensions are provided in Figure 7.
Notes:
The normally closed, de-energized,
Solenoid Valve is separately ordered and
selected based on the required laboratory
approval acceptable to the authority having
jurisdiction. Refer to Technical Data Sheet
TFP2180 for specific laboratory approvals.
Consult with the applicable standards of
the Approval agency regarding installation
criteria pertaining to electric actuation
circuitry.
Due to the functionality of the Model
MRA-1 Manual Reset Actuator, the
release circuit of the releasing panel
need only provide the typical ten
minutes of alarm condition intended
to energize the Solenoid Valve to
open. After the ten minute duration, at
which point should the Solenoid Valve
become de-energized and close (espe-
cially while operating under battery
back-up), the MRA-1 will have already
automatically opened, thereby pre-
venting the DV-5aDiaphragm Chamber
from becoming re-pressurized, and
preventing an inadvertent closing of
the DV-5aduring a fire event.
SYSTEM PIPING WITH AUTOMATIC SPRINKLERS - NORMALLY DRY
DRAIN
SOLENOID
VALVE
(TYPICALLY
24 VOLTS DC)
ELECTRIC DETECTION SYSTEM
(TYPICALLY 24 VOLTS DC)
HEAT DETECTORS, SMOKE DETECTORS,
MANUAL PULL STATIONS, ETC.
DELUGE VALVE
RELEASING PANEL
(AUTOMATIC
CONTROL UNIT
WITH BATTERY
BACK-UP)
POWER
SUPPLY
(TYPICALLY
120 VOLTS AC)
AUTOMATIC
SUPERVISORY
AIR/NITROGEN
SUPPLY
8 TO 12 PSI
SUPERVISORY
LOW PRESSURE
ALARM SWITCH
SYSTEM DRAIN VALVE
(NORMALLY CLOSED)
MAIN
DRAIN VALVE
(NORMALLY
CLOSED)
LOCAL
MANUAL
CONTROL
STATION
MAIN
CONTROL VALVE
(NORMALLY
OPEN)
WATER
SUPPLY
DIAPHRAGM CHAMBER
PRESSURE GAUGE
WATER SUPPLY
PRESSURE
GAUGE
MANUAL RESET
ACTUATOR
RESTRICTION DRAIN
DRAIN
DRAIN
WATERFLOW
PRESSURE
ALARM
SWITCH
DRAIN
DV-5A
VALVE
SYSTEM AIR
PRESSURE
GAUGE
WATER SUPPLY SHUT-OFF
(NORMALLY OPEN)
DIAPHRAGM
CHAMBER SUPPLY
CONTROL VALVE
(NORMALLY OPEN)
DIAPHRAGM CHAMBER
SUPPLY CONNECTION
FIGURE 4
DV-5aVALVE - SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION SCHEMATIC DIAGRAM

TFP1421
Page 7 of 18
Installation
The TYCO DV-5ASingle Interlock Pre-
action Electric Actuation Trim Valve is
to be installed in accordance with this
section.
NOTICE
DV-5A Automatic Water Control Valves
are designed to be used in freshwater
systems. When the supply is from an
alternative source such as brackish
water, saltwater, or contains additives
such as foam, the limited warranty is
reduced to one year from the time of
installation. An increase in frequency of
inspections is required when the valve
is exposed to such supplies and other
corrosive conditions or chemicals that
could impact valve materials or the
operation of the assembly. The system
and all components must be designed
accordingly for the increased demand.
It is required to thoroughly flush the
valve and trim assembly with freshwa-
ter and reset to the set condition after
each operation.
Proper operation of the DV-5aSingle
Interlock Preaction Electric Actua-
tion Valve depends upon their trim
being installed in accordance with the
instructions given in this technical data
sheet. Failure to follow the appropriate
trim diagram may prevent the DV-5a
Valve from functioning properly, as well
as void approvals and the manufactur-
er’s warranties.
The DV-5aValve must be installed in a
readily visible and accessible location.
The DV-5aValve and associated trim
must be maintained at a minimum tem-
perature of 40°F (4°C).
Heat tracing of the DV-5aValve or its
associated trim is not permitted. Heat
tracing can result in the formation of
hardened mineral deposits that are
capable of preventing proper operation.
Always open the system control valves
slowly to avoid a sudden rush of water
entering the system.
The DV-5aValve is to be installed in
accordance with the following criteria:
Step 1. All nipples, fittings, and devices
must be clean and free of scale and
burrs before installation. Use pipe
thread sealant sparingly on male pipe
threads only.
Step 2. The DV-5aSingle Interlock Pre-
action Electric Actuation Valve must be
trimmed in accordance with the trim
illustration shown in Figure 5.
Note:If the addition of an Alarm Control
Valve is desired or required by the local
AHJ, the Alarm Control Valve noted as
Item H in Figure 8 is to be a separately
orderedelectronicallysupervised normally
open valve.
Step 3. Care must be taken to ensure
that check valves, strainers, globe
valves, etc. are installed with the flow
arrows in the proper direction.
Step 4. Drain tubing to the Drip Funnel
must be installed with smooth bends
that will not restrict flow.
Step 5. The Main Drain and Drip Funnel
Drain may be interconnected provided
a check valve is located at least 12 in.
(300 mm) below the Drip Funnel.
Step 6. Suitable provision must be
made for disposal of drain water. Drain-
age water must be directed such that
it will not cause accidental damage to
property or danger to persons.
Step 7. Connect the Diaphragm Supply
Valve to the inlet side of the System
Main Control Valve in order to facilitate
setting of the DV-5aValve (see Figure
8).
Step 8. Unused Pressure Alarm Switch
connections must be plugged.
Step 9. A suitable automatic supervi-
sory air (nitrogen) supply, as described
in the Technical Data section, is to be
installed in accordance with the appli-
cable technical data sheet and set for
10 ± 2 psi (0,69 ± 0,14 bar).
Step 10. A desiccant dryer, when
required for the supervisory air supply,
is to be installed between a drip leg
and the Model AMD-1 Air Mainte-
nance Device or between the Model
G16AC812 Automatic Supervisory Air
Supply and the Preaction Trim.
Step 11. The Supervisory Low Pressure
Switch is to be wired to the supervisory
alarm initiating circuit of an alarm panel.
Step 12. Conduit and electrical con-
nections are to be made in accordance
with the applicable standards of the
approval agency.
Step 13. Before a system hydrostatic
test is performed, the DV-5aDiaphragm
Chamber is to be depressurized, the
Automatic Drain Valve is to be tem-
porarily replaced with a plug, and the
Diaphragm Cover Bolts must be uni-
formly and securely tightened using
a cross-draw sequence.After tight-
ening, double-check to make certain
that all of the Diaphragm Cover Bolts
are securely tightened. See Table B in
the Care and Maintenance section for
torque specifications.

TFP1421
Page 8 of 18
Notes:
1. Port Connections P1 through P7 are described in Figure 2.
2. External Trim Connections C1 through C5 are described in Figure 8.
3. When ordering pre-assembled "DV-5AValve with Galvanized Trim" or pre-assembled "DV-5AValve with Galvanized Trim and Buttery Valve", Items A1
through A9 are provided, as applicably related to valve size, and Item A6 is provided as P/N 52-287-1-124 described in Technical Data Sheet TFP2180.
4. When ordering DV-5A Trim separately from the DV-5AValve, Items A1 through A9 are separately ordered, as applicably related to valve size. Water
Pressure Gauges for EMEA valve trim are also separately ordered.
Assemble in order
from A to L
C6
C7
C3
C5
C4
C2
C1
P1
P2
P3
P6
P7 P4
P5
1-1/2" (DN40) AND 2" (DN50)
VALVES ONLY
A1
A4
A3
A4
A5
A6
A2
A2
A7
A9
A8
E
D
C
A
B
G
H
F
L
J
K
FIGURE 5
DV-5aVALVES WITH SINGLE INTERLOCK PREACTION
ELECTRIC ACTUATION TRIM
SEMI-ASSEMBLED

TFP1421
Page 9 of 18
Notes:
1. Port Connections P1 through
P7 are described in Figure 2.
2. External Trim Connections C1
through C5 are
described in Figure 8.
3. When ordering pre-assembled
"DV-5A Valve with Galvanized
Trim" or pre-assembled "DV-
5A Valve with Galvanized Trim
and Buttery Valve", Items
A1 through A9 are provided,
as applicably related to valve
size, and Item A7 is provided
as P/N 52-287-1-124 described
in Technical Data Sheet
TFP2180.
4. When ordering DV-5A Trim
separately from the DV-5A
Valve, Items A1 through A9
are separately ordered, as ap-
plicably related to valve size.
Water Pressure Gauges for
EMEA valve trim are also
separately ordered.
ITEM QTY DESCRIPTION CH 1 1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150)b8 IN. (DN200)
1 2 1/4” GAUGE TEST VALVE 460051003 460051003 460051003 460051003 460051003 460051003
2 1 MRA-1 MANUAL RESET ACTUATOR 545001000 545001000 545001000 545001000 545001000 545001000
3 1 MC-2 MANUAL CONTROL STATION 545002000 545002000 545002000 545002000 545002000 545002000
4 1 AD-3 AUTOMATIC DRAIN VALVE 547932004 547932004 547932004 547932004 547932004 547932004
5 1 PRIMING SUPPLY RESTRICTION 545100051 545100051 545100051 545100051 545100051 545100051
6 1 1/4” PRESSURE RELIEF VALVE, 25 PSI 923431019 923431019 923431019 923431019 923431019 923431019
7 2 1/2” BALL VALVE 460501004 460501004 460501004 460501004 460501004 460501004
8 1 1/2” GLOBE VALVE 460471005 460471005 460471005 460471005 460471005 460471005
9 1 1/2” SPRING LOADED CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003
10 1 1/2” SWING CHECK VALVE 460491007 460491007 460491007 460491007 460491007 460491007
11 11/2” Y-STRAINER 523531006 523531006 523531006 523531006 523531006 523531006
12 1 3/4” ANGLE VALVE 460481010 460481010 460481010 460481010 460481010 460481010
13 1ANGLE VALVE 460481010 460481010 460481011 460481012 460481012 460481012
14 1DRIP FUNNEL BRACKET CONNECTOR 922111005 92211100 5 9221110 0 5 9 2 21110 05 922111005 92 21110 05
15 1 DRIP FUNNEL BRACKET 922111003 92211100 3 9 221110 0 3 9 2 21110 03 922111003 92 21110 03
16 1DRIP FUNNEL 923431007 923431007 923431007 923431007 923431007 923431007
17 2 COMP. FITTING 90° 1/2” MNPT x 1/2” OD TUBE ✓——————
18 1 COMP. FITTING 90° 1/2” FNPT x 1/2” OD TUBE ✓— — — — — —
19 2 FLARE FITTING 90° 1/2” NPT x 1/2” TUBE 545100062 545100062 545100062 545100062 545100062 545100062
20 2 FLARE FITTING 3/4” NPT x 3/4” TUBE 545100063 545100063 545100063 545100063 545100063 545100063
21 2PIPE PLUG ✓1/4” 1/4” 1/4” 1/4” 1/4” 1/4”
22 1PIPE PLUG ✓1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
C1
C6
C7
C5
C3
C4
C2
P1
P6
P7
P2
P3
P4
P5
1-1/2" (DN40) AND 2" (DN50)
VALVES ONLY
A4
A3
A4
A5
A1
A2
A6
A2
A7 A9
A8
2
9
17
13
33
55
54 20
12 3
29
39
14
11
37
27
37
7
24
37
20
49
24
31 35
121
25
48
19
38
7
37
27
19
43
5
45
56
16
15
4
29
18
53
50
32
10
30
34
1
36
21
36
36
8
41
36
22
39
26 51
27
28
52 27
42
46
36
47
17
57
40
58
59
56
31
6
32
23
44
FIGURE 6 (1 OF 2)
DV-5aVALVES — SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION TRIM
EXPLODED VIEW

TFP1421
Page 10 of 18
ITEM QTY DESCRIPTION CH 1 1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150)b8 IN. (DN200)
23 1PIPE PLUG ✓3/4” 3/4” 3/4” 3/4” 3/4” 3/4”
24 2UNION ✓1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
25 1STREET ELBOW ✓1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90°
26 1ELBOW ✓1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45°
27 4ELBOW ✓1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90°
28 1CROSS ✓1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
29 2TEE ✓1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
30 1REDUCING TEE ✓1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2”
31 2REDUCING TEE ✓1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4”
32 2REDUCING TEE ✓3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4”
33 1REDUCING TEE ✓3/4” x 3/4” x 3/4” 3/4” x 3/4” x 3/4”
1 1/4” x 1 1/4” x 3/4”
2” x 2” x 3/4” 2” x 2” x 3/4” 2” x 2” x 3/4”
34 1PIPE NIPPLE ✓1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE
35 1PIPE NIPPLE ✓1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2”
36 4PIPE NIPPLE ✓1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE
37 4PIPE NIPPLE ✓1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2”
38 1PIPE NIPPLE ✓1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2”
39 2PIPE NIPPLE ✓1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2”
40 1PIPE NIPPLE ✓1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2”
41 1PIPE NIPPLE ✓1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5”
42 1PIPE NIPPLE ✓1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2”
43 1PIPE NIPPLE ✓3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2”
44 1PIPE NIPPLE ✓3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2”
45 1TUBING, MRA-1 DRAIN 545100065 545100065 545100066 535002140 535002160 535002180
46 1TUBING, MC-2 DRAIN 535000220 535000220 535000230 535000240 535000260 535000280
47 1TUBING, SOLENOID DRAIN 535001020 535001020 535000630 535000640 535000660 535000680
48 1 TUBING ASSY, ALARM TEST INTERCONNECT 535000320 535000320 535000330 535000340 535000360 535000380
49 1 TUBING ASSY, SYSTEM DRAIN 535000420 535000420 535000430 535000440 535000460 535000480
50 1PIPE NIPPLE ✓1/2” x 3 1/2” 1/2” x 3 1/2” 1/2” x 4 1/2” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 6 3/4”
51 1PIPE NIPPLE ✓1/2” x 5” 1/2” x 5” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 6 1/2”
52 1PIPE NIPPLE ✓1/2” x 5” 1/2” x 5” 1/2” x 4 1/2” 1/2” x 5” 1/2” x 7 1/2” 1/2” x 9 1/2”
53 1PIPE NIPPLE ✓3/4” x 5” 3/4” x 5” 3/4” x 6” 3/4” x 7” 3/4” x 9” 3/4” x 11 1/2”
54 1PIPE NIPPLE ✓3/4” x 4 1/2” 3/4” x 4 1/2” 1 1/4” x 3 1/4” 2” x 3” 2” x 3” 2” x 3”
55 1PIPE NIPPLE ✓3/4” x 6 1/2” 3/4” x 6 1/2” 1 1/4” x 5 1/2” 2” x 5” 2” x 6” 2” x 8”
56
2WATER PRESSURE GAUGE, 300 PSI / 2000 kPa
(AMER/APAC) 923431005 923431005 923431005 923431005 923431005 923431005
2WATER PRESSURE GAUGE, 20 bar / 2000 kPa
(EMEA) 025500013 025500013 025500013 025500013 025500013 025500013
57 1AIR PRESSURE GAUGE, 80 PSI / 550 kPa
RETARDED TO 250PSI / 1750 kPa 923431012 923431012 923431012 923431012 923431012 923431012
58 1LABEL 545003005 545003005 545003005 545003005 545003005 545003005
59 1 LABEL WIRE — — — — — —
A1 1DV-5
A
VALVE SEE ORDERING PROCEDURE, SEPARATE DV-5A VALVES WITHOUT TRIM, FOR PART NUMBERS
A2
2WATERFLOW PRESSURE ALARM SWITCH,
PS10-2 (AMER/APAC) 25710 25710 25710 25710 25710 25710
2WATERFLOW PRESSURE ALARM SWITCH,
PS10-1 (EMEA) 0260 0260 0260 0260 0260 0260
A3 1 BUTTERFLY VALVE, G x G 51024A 51021A — — — —
1 BFV-300 BUTTERFLY VALVE, G x G — — 59300G030WS 59300G040WS 59300G060WS 59300G080WS
A4 2FIGURE 577 RIGID GROOVED COUPLING 57715ACP 57720ACP — — — —
1FIGURE 577 RIGID GROOVED COUPLING — — 57730ACP 57740ACP 57760ACP 57780ACP
A5 1 GROOVE x THREADED OUTLET WELDED TEE 545004000 545004001 — — — —
A6 1SOLENOID VALVE NORMALLY CLOSED REFER TO TFP2180
A7 1INVERTED FLARE SHUT-OFF VALVEa545100100 545100100 545100099 545100100 545100100 545100100
A8 1 FLARE FITTING 90° 1/2” NPT x 1/2” TUBE 545100062 545100062 545100062 545100062 545100062 545100062
A9 1TUBING ASSY, DIAPHRAGM CHAMBER SUPPLY 540000015 540000020 540000030 540000040 540000060 540000080
NOTES
a. Not VdS Approved.
b. Also applicable to metric 165,1mm size.
CH - Common Hardware - See Materials of Construction section for specications.
FIGURE 6 (2 OF 2)
DV-5aVALVES — SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION TRIM
EXPLODED VIEW

TFP1421
Page 11 of 18
Nominal
Valve
Size
ANSI
Inches
(DN)
Inches
(mm)
A B C D E F G H J
1 1/2
(40)
2.8
(71)
9.7
(246)
10.4
(264)
15.7
(399)
16.2
(411)
7.3
(185)
10.2
(259)
8.02
(204)
1.2
(31)
2
(50)
2.8
(71)
9.7
(246)
10.4
(264)
15.7
(399)
16.2
(411)
7.3
(185)
10.2
(259)
8.09
(205)
2.9
(74)
3
(80)
3.0
(76)
10.9
(277)
12.0
(305)
16.3
(414)
18.5
(470)
5.8
(147)
13.8
(351)
3.79
(96)
3.6
(91)
4
(100)
3.0
(76)
12.2
(310)
13.1
(333)
16.5
(419)
21.0
(533)
5.1
(130)
16.8
(427)
4.54
(115 )
4.3
(109)
63
(150)
4.5
(114)
13.6
(345)
15.0
(381)
18.4
(467)
24.8
(630)
3.4
(86)
22.4
(569)
5.83
(148)
5.7
(145)
8
(200)
5.3
(135)
16.3
(414)
17. 2
(437)
19.5
(495)
29.2
(742)
2.9
(74)
27. 5
(699)
5.24
(133)
6.7
(170)
NOTES:
1.
Dimensions based on drain valves being open.
2.
Dimensions do not provide installation clearance.
3. Also applicable to metric 165,1 mm size.
HF
E
DCB
J
A
G
FIGURE 7
DV-5aVALVE
SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION TRIM
NOMINAL DIMENSIONS

TFP1421
Page 12 of 18
Valve Setting
Procedure
Perform Steps 1 through 16 when ini-
tially setting the TYCO DV-5aElectric
Actuation Valve, after an operational
test of the fire protection system, or
after system operation due to a fire.
See Figure 8.
Step 1. Close the System Main Control
Valve (B).
Step 2. Close the Diaphragm Supply
Valve (P).
Step 3. Close the Supervisory Air
Supply Valve (S).
Step 4. Open the Main Drain Valve (D),
System Drain Valve (E), and all auxil-
iary drains in the system. Close the
auxiliary drain valves and the System
Drain Valve (E) after water ceases to
discharge. Leave the Main Drain Valve
(D) open.
At this time make certain that the
Pressure Gauge Valves and the Alarm
Control Valve (H), as applicable, are
open.
Step 5. Depress the plunger of the
Automatic Drain Valve (F) to verify that
it is open.
Step 6. Clean the Diaphragm Supply
Strainer (Q) by removing the clean-
out plug and strainer basket. The Dia-
phragm Supply Strainer (Q) may be
flushed out by momentarily opening
the Diaphragm Supply Valve (P).
Step 7. Replace any operated sprin-
klers on the system piping, as
applicable.
Step 8. Reset the automatic actuation
system. Reset the electric detection
system in accordance with the manu-
facturer’s instructions to de-energize
the solenoid valve.
Step 9. Operate (open) the Manual
Control Station (M) and then open
the Diaphragm Supply Valve (P). After
unaerated water ceases to discharge
from the Manual Control Station (M)
drain tube, slowly close the operating
lever by pushing it up. Do not close the
hinged cover at this time.
Step 10. After allowing water to flow
out of the Manual Reset Actuator (N)
drain tube until aerated water ceases
to discharge, reset the Manual Reset
Actuator (N) by pressing the Reset
Knob and hold until water stops flowing
from its drain tube and the pressure
builds and reaches approximately 15
psi (1,0 bar) on the Diaphragm Gauge
(K). Pressure will then build up in the
DV-5aDiaphragm Chamber.
Step 11. Verify the ability for the DV-5a
Diaphragm to hold pressure as follows:
•
With the diaphragm chamber
pressurized per Step 10, tempo-
rarily close the Diaphragm Supply
Valve (P), and then observe the
Diaphragm Gauge (K) for a drop in
pressure.
•
If a drop in pressure is noted, the
DV-5aDiaphragm is to be replaced
and/or any leaks must be corrected
before proceeding to the next step.
•
If the Diaphragm Gauge (K)
indicates no drop in pressure,
re-open the Diaphragm Supply
Valve (P) and proceed to the next
step.
Step 12. Open the Supervisory Air
Supply Valve (S) to reestablish super-
visory system air pressure at nominally
10 psi (0,68 bar).
Step 13. Partially open the System
Main Control Valve (B). Slowly close the
Main Drain Valve (D) as soon as water
discharges from the Main Drain Valve
(D). Observe the Automatic Drain Valve
(F) for leaks. If there are leaks, deter-
mine/correct the cause of the leakage
problem before proceeding.
NOTICE
When the System Main Control Valve
(B) is partially opened, the pressure on
the DV-5aDiaphragm Chamber may
increase. This increase in pressure is
normal, and if the pressure is greater
than 300 psi (20,7 bar), the pressure
is to be relieved by partially and tem-
porarily opening the Manual Control
Station (M); however, do not allow
the pressure as indicated on the Dia-
phragm Gauge (K) to drop below the
supply pressure shown on the Water
Supply Gauge (J), since this action may
result in tripping of the DV-5aValve.
Step 14. Close the hinged cover of the
Manual Control Station (M) and insert a
new break rod in the small hole through
the top of the enclosing box.
Step 15. Fully open the System Main
Control Valve (B).
Step 16. After setting a fire protec-
tion system, notify the proper authori-
ties and advise those responsible for
monitoring proprietary and/or central
station alarms.

TFP1421
Page 13 of 18
Note:
Port Connections P1 through P7 are described in Figure 2.
External Trim Connections
C1
C2
C3
C4
C5
C6
C7
Diaphragm Supply Connection
Water Motor Alarm Connection
Supervisory Air Supply Connection
Waterow Pressure Alarm Switch
Connection
Low Air Pressure Alarm Switch
Connection
Main Drain Connection
Drip Funnel Drain Connection
Item Description
A
B
C
D
E
F
G
H
J
K
DV-5aValve
System Main Control Valve
Waterow Pressure Switch
Main Drain Valve
System Drain Valve
Automatic Drain Valve
Alarm Test Valve
Alarm Control Valve (Optional)
Water Supply Gauge
Diaphragm Gauge
Item Description
L
M
N
P
Q
R
S
T
U
V
System Gauge
Manual Control Station
Manual Reset Actuator
Diaphragm Supply Valve
Diaphragm Supply Strainer
Inverted Flare Shut-Off Valve
Supervisory Air Supply Valve
Supervisory Air Pressure Relief Valve
Supervisory Low Pressure Switch
Solenoid Valve
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
C6
C7
C5
C3
C2 C4
C1
A
B
JK
D
E
F
G
M
N
P
Q
U
V
S
L
T
C
H
R
P1
P6
P7
P2
P3
P4
P5
FIGURE 8
DV-5aVALVE - SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION
(See Figure 6 for specific Bills of Materials)

TFP1421
Page 14 of 18
Care and
Maintenance
The following procedures and inspec-
tions must be performed as indicated,
in addition to any specific require-
ments of the NFPA and any applicable
standards recognized by the Approval
agency. Any impairment must be imme-
diately corrected. See Figure 8.
NOTICE
If the water supply needs to be shut off
to the DV-5avalve and trim and cannot
be shut off upstream of the system,
close the System Main Control Valve
(B), the Diaphragm Supply Valve (P),
and the Inverted Flare Shut-Off Valve
(R). This will allow any trim above the
System Main Control Valve (B) to be
taken apart for service if necessary.
The frequency at which the following
procedures and inspections are to be
performed are to be in accordance with
the NFPA and any applicable specific
requirements of the standards recog-
nized by the Approval agency.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down
the affected fire protection systems
must first be obtained from the proper
authorities and all personnel who may
be affected by this action must be
notified.
The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this docu-
ment, as well as with the NFPA and any
applicable standards recognized by the
Approval agency. Contact the install-
ing contractor or product manufacturer
with any questions.
Some procedures in this section result
in the operation of the associated
alarms. Notify the owner and the fire
department, central station, or other
signal station to which the alarms are
connected before performing the tests.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with the
NFPA and any applicable standards
recognized by the Approval agency.
Drop in Water Supply Pressure
Below Normal Range
NOTICE
If the water supply pressure is signif-
icantly reduced below the normally
expected static pressure range (as
could occur in the case of a water main
break or repair), and there is a subse-
quent drop in the diaphragm chamber
water pressure below its normal range
(for example, due to a leak in a piping
connection to or from the diaphragm
chamber or, a leak in the diaphragm
chamber check valve caused by dirt or
debris in the check valve seal area), a
deluge valve such as the DV-5acould
inadvertently trip, if its water supply
pressure is quickly restored.
A drop in the water supply pressure
to below its normal range (as in the
case of an interrupted water supply
condition) constitutes an emergency
impairment.
Should this condition occur, immedi-
ately close the System Main Control
Valve (B) and use the following proce-
dure to reset the system:
Step 1. Prior to the water supply pres-
sure being restored to the closed
System Main Control Valve (B), note the
pressure indicated by the Diaphragm
Gauge (K) and determine if the pres-
sure is within the normally expected
range.
Step 2. If the diaphragm chamber pres-
sure is below the normal range, check
for and correct any source of leakage
from the diaphragm chamber prior to
resetting the system.
Step 3. After the water supply pres-
sure is restored to the System Main
Control Valve (B), reset the DV-5aValve
in accordance with the Valve Setting
Procedure section.
NOTICE
For fire protection systems subject to
an emergency impairment caused by
an interrupted water supply condition,
it is recommended that consideration
be given to installing a low water supply
pressure switch with the appropriate
alarm/indications to monitor the water
supply pressure.
Waterflow Alarm Test Procedure
To test the waterflow alarm, open the
Alarm Test Valve (G), which will allow a
flow of water to the Waterflow Pressure
Switch (C) and/or Water Motor Alarm.
Upon satisfactory completion of the
test, close the Alarm Test Valve (G).
To ensure drainage of the alarm line,
depress the plunger on the Automatic
Drain Valve (F).
Supervisory Low Pressure Alarm
Test Procedure
Proper operation of the Supervisory
Low Pressure Switch (U) must be per-
formed as follows:
Step 1. Open the System Drain Valve
(E) just enough to slowly relieve super-
visory air pressure from the system.
Verify that the Supervisory Low Pres-
sure Switch (U) is operational and that
the low pressure set point is approxi-
mately 5 psi (0,34 bar).
Step 2. Close the System Drain Valve
(E) and allow the system supervisory
pressure of 10 ± 2 psi (0,69 ± 0,14 bar)
to be automatically re-established. The
Supervisory Low Pressure Switch (U)
should return to its normal condition.
Pressure Relief Valve Maintenance
Over pressurization of the system
piping with air will result in the opening
of the Supervisory Air Pressure Relief
Valve (T). If the Supervisory Air Pres-
sure Relief Valve (T) continues to bleed
air after the system pressure has been
reduced to its normal supervisory pres-
sure range of 10 ± 2 psi (0,69 ± 0,14 bar),
most likely debris became lodged in the
seating area. To help clean the seating
area, slowly pull up on the ring at the
top of the Supervisory Air Pressure
Relief Valve (T) to allow a full flow of air
through the Supervisory Air Pressure
Relief Valve (T), and then release the
ring to allow the Supervisory Air Pres-
sure Relief Valve (T) to snap closed.
Repeat the cleaning procedure as
necessary.
Electric Actuation Solenoid Valve
Test Procedure
Proper operation of the Solenoid Valve
(V) for electric actuation must be veri-
fied at as follows:
Step 1. Close the System Main Control
Valve (B).
Step 2. Open the Main Drain Valve (D).
Step 3. Test the deluge releasing panel
in accordance with the manufacturer’s
instructions to energize the solenoid
valve.
Step 4. Verify that there is a flow of
water from the Solenoid Valve drain
connection.
Step 5. Verify that the Diaphragm
Chamber pressure has decreased
to below 25% of the water supply
pressure.

TFP1421
Page 15 of 18
Step 6. Reset the electric detection
system in accordance with the manu-
facturer’s instructions to de-energize
the Solenoid Valve (V), and proceed as
follows:
• Water should cease draining from the
Solenoid Valve (V) but remain drain-
ing from the Manual Reset Actuator
(N).
• Press the Reset Knob on the Man-
ual Reset Actuator (N) and hold it a
few seconds until water stops flow-
ing from its drain tube.
• Pressure will then build up in the
DV-5aDiaphragm Chamber.
• After system pressure is restored
in the DV-5aDiaphragm Chamber,
inspect the Solenoid Valve (U) and
Manual Reset Actuator (N) for leaks
at the drain tube. Any leaks must be
corrected before proceeding to the
next step.
Step 7. Partially open the System Main
Control Valve (B). Slowly close the Main
Drain Valve (D) as soon as water dis-
charges from the Main Drain Valve (D).
Observe the Automatic Drain Valve
(F) for leaks. If there are leaks, deter-
mine/correct the cause of the leakage
problem. If there are no leaks, the
DV-5aValve is ready to be placed in
service and the System Main Control
Valve (B) must then be fully opened.
Internal Valve Inspection
Once every five years during the annual
operational test procedure and prior
to the DV-5aValve being reset and
with the DV-5aValve de-pressurized,
the interior of the DV-5aValve must
be cleaned and inspected for wear
and damage. Damaged or worn parts
must be replaced. (Replacement of the
Diaphragm every ten years is recom-
mended, or more frequently if inspec-
tions and/or wear and tear warrant
more frequent replacement.)
NOTICE
The Diaphragm Cover may be removed
between Steps 4 and 5 of the reset-
ting instructions, since at that point the
DV-5aValve should be de-pressurized
as evident by a zero gauge reading on
the Diaphragm Gauge (K) and Water
Supply Gauge (J), as well as no water
discharging from the Automatic Drain
Valve (F).
To perform internal valve inspection
between Steps 4 and 5 of the Valve
Setting Procedure remove the Dia-
phragm cover as follows:
Step 1. Close the Inverted Flare Shut-
Off Valve (R).
Step 2. Remove the Copper Tube
Fitting between the Diaphragm Supply
Valve (P) and the Inverted Flare Shut-
Off Valve (R).
Step 3. Loosen the union securing the
Electric Actuation Trim and remove the
Electric Actuation Trim.
Step 4. Loosen and remove the union
between the Diaphragm Cover and the
MRA-1 Manual Reset Actuator (N) and
remove the MRA-1 Manual Reset Actu-
ator (N) subassembly.
Step 5. Remove the Diaphragm Valve
Cover hardware, then slowly remove
the Diaphragm Cover and perform
internal valve inspection. Clean the
valve interior and replace parts as
necessary.
After cleaning and inspecting valve
interior, and replacing parts as nec-
essary, reinstall the Diaphragm Cover
by completing the following steps to
assure the Diaphragm Cover Fasteners
are uniformly and securely tightened.
Step 1. With reference to Figure 1,
ensure that the Diaphragm is properly
oriented and that the proper hardware
arrangement is utilized when assem-
bling the Diaphragm Covers. The hard-
ware arrangements differ depending on
the size of the DV-5aValve.
Step 2. By first using the Long Hex
Bolts, support of the Diaphragm Cover
will be provided before installing the
Short Hex Bolts. Align Diaphragm in
proper orientation with Valve Body, and
then align Diaphragm Cover in proper
orientation with Valve Body. Hand-
tighten all fasteners.
Step 3. Using crossdraw sequence
to assure uniformity, wrench-tighten
Long Hex Bolts and Short Hex Bolts
to appropriate torque values. Repeat
crossdraw sequence two to three
times at incremental torque valves
until reaching the torque valves found
in Table B.
Step 4. Inspect to assure all Hex Bolts
are securely tightened.
Step 5. Using the union, secure the
MRA-1 Manual Reset Actuator (N) to
the Diaphragm Cover.
Step 6. Using the union, secure the
Electric Actuation Trim.
Step 7. Replace the Copper Tube
Fitting between the Diaphragm Supply
Valve (P) and the Inverted Flare Shut-
Off Valve (R).
Step 8. Ensure that the unions and flare
fittings are securely tightened.
Step 9. With the Diaphragm Supply
Valve (P) closed, fully open the Inverted
Flare Shut-Off Valve (R) stainless steel
screw (approximately 1/2 in.) until resis-
tance is met so as not to break the
internal roll-pin. The internal roll-pin
stops the removal of the Inverted Flare
Shut-Off Valve (R) stainless steel screw.
Step 10. Proceed with Step 5 of the
Valve Setting Procedures section in this
data sheet.
NOTICE
If the water supply contains chemicals
which tend to attack a polyester fab-
ric-reinforced, EPDM rubber or the five
year inspection indicates a build-up of
debris within the DV-5aValve that could
affect its proper operation, then the
frequency of the internal valve inspec-
tion procedure must be appropriately
increased.
With reference to Figure 1, make
certain that the Diaphragm is correctly
oriented; otherwise, the DV-5aValve
cannot be properly set.
Under-tightening the Diaphragm Cover
Bolts can result in internal and external
leakage.
Use only TYCO replacement fasteners
as specified in Figure 1.
Do not apply adhesives, lubricants, or
other substances to the Diaphragm
Valve Body.
Nominal
Valve Sizes
ANSI
Inches
(DN)
Torque
lb-ft
(N∙m)
Nuts Short
Hex
Bolts
1 1/2
(40)
44
(59,7)
35
(47, 5)
2
(50)
44
(59,7)
35
(47, 5)
3
(80)
125
(169,5)
125
(169,5)
4
(100)
150
(203,4)
150
(203,4)
61
(150)
150
(203,4)
150
(203,4)
8
(200)
188
(254,9)
188
(254,9)
NOTES
1. Also applicable to metric 165,1 mm size.
TABLE B
DIAPHRAGM COVER BOLTS
MINIMUM TORQUE

TFP1421
Page 16 of 18
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
The TYCO DV-5aAutomatic Water
Control Valves may be ordered as
follows:
Pre-Assembled Valves
with Trim
DV-5
A
Valves with Galvanized Trim
and Butterfly Valve
Specify: Size (specify), DV-5aAuto-
matic Water Control Valve, G x G con-
nections with assembled galvanized
Americas Single Interlock Preaction
Electric Actuation Trim, complete with
assembled Model BFV-300 Butterfly
Valve, P/N (specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 551011315
2 in. (DN50) .................... 551011320
3 in. (DN80) ....................551011330
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 551011340
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 551011360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 551011380
Notes:
AMERICAS DV-5
A
Valve with Trim and
Butterfly Valve: Americas pressure
switches, P/N 52-287-1-124 solenoid valve,
and psi/kPa water pressure gauges are
provided.
This arrangement is available for EMEA
and APAC upon request. Contact your
local distributor.
AMERICAS
DV-5A Valves with Galvanized Trim
Specify: Size (specify), DV-5aAuto-
matic Water Control Valve, (specify)
end connection with assembled gal-
vanized Americas Single Interlock
Preaction Electric Actuation Trim, P/N
(specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 5 50 011315
2 in. (DN50) ....................550 011320
3 in. (DN80) ....................550 011330
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550 011340
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550 0113 60
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550 011380
Flange x Flange ANSI
3 in. (DN80) ....................550021330
4 in. (DN100)....................550021340
6 in. (DN150)....................550021360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550021380
Flange x Grove ANSI
3 in. (DN80) ....................550031330
4 in. (DN100)....................550031340
6 in. (DN150)....................550031360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550031380
T x T NPT
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 550061315
2 in. (DN50) ....................550061320
Separate DV-5
A
Valves without Trim
See Table A for flange drilling
specifications.
Specify: Size (specify), DV-5aAuto-
matic Water Control Valve, (specify)
end connection, P/N (specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530010015
2 in. (DN50) ....................530010020
3 in. (DN80) ....................530010030
4 in. (DN100)....................530010040
6 in. (DN150)....................530010060
8 in. (DN200) ...................530010080
Flange x Flange ANSI
3 in. (DN80) ....................530020030
4 in. (DN100)....................530020040
6 in. (DN150)....................530020060
8 in. (DN200) ...................530020080
Flange x Grove ANSI
3 in. (DN80) ....................530030030
4 in. (DN100)....................530030040
6 in. (DN150)....................530030060
8 in. (DN200) ...................530030080
T x T NPT
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . .530060015
2 in. (DN50) ....................530060020
Notes:
Valves are typically provided with flange
drilling per ANSI B16.1 (Class 125) or ISO
(7005-2 PN16).
Upon request, valves can be provided with
flange drilling per JIS B 2210 or AS 2129. In
whichcasepartnumbersare notassigned.
DV-5
A
Valve Trim
Specify: Size (specify), finish (specify),
Electric Actuation Trim for DV-5aAuto-
matic Water Control Valves used in
Single Interlock Preaction Fire Protec-
tion System, P/N (specify):
Galvanized
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 540001320
2 in. (DN50) ....................540001320
3 in. (DN80) ....................540001330
4 in. (DN100)....................540001340
6 in. (DN150)....................540001360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 540001380
Black
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 542001320
2 in. (DN50) ....................542001320
3 in. (DN80) ....................542001330
4 in. (DN100)....................542001340
6 in. (DN150)....................542001360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 542001380
Note:
Pressure switches and/or solenoid valves
for electric actuation are separately
ordered.
EMEA
DV-5A Valves with Galvanized Trim
Specify: Size (specify), DV-5aAuto-
matic Water Control Valve, (specify)
end connection with assembled galva-
nized EMEA Single Interlock Preaction
Electric Actuation Trim, P/N (specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 5 50111315
2 in. (DN50) .................... 55 0111320
3 in. (DN80) ....................550111330
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 55011134 0
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 55011136 0
165,1 mm ...................... 55011136 6
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 55011138 0
Flange x Flange ANSI
3 in. (DN80) ....................550121330
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550121340
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550121360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550121380
Flange x Groove ANSI
3 in. (DN80) ....................550131330
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550131340
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550131360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550131380
Flange x Flange ISO
3 in. (DN80) ....................550141330
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550141340
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550141360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550141380
Flange x Groove ISO
3 in. (DN80) ....................550151330
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550151340
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550151360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550151380
T x T ISO
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 550171315
2 in. (DN50) ....................550171320
Notes:
Pressure switches, P/N 52-287-1-124
solenoid valve, bar/psi water pressure
gauges, and NPT to ISO threaded trim
adaptors for external connections are
provided.
Separate DV-5
A
Valves without Trim
See Table A for flange drilling
specifications.
Specify: Size (specify), DV-5aAuto-
matic Water Control Valve, (specify)
end connection, P/N (specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530010015
2 in. (DN50) ....................530010020
3 in. (DN80) ....................530010030
4 in. (DN100)....................530010040
6 in. (DN150)....................530010060
165,1 mm ......................530010066
8 in. (DN200) ...................530010080
Flange x Flange ANSI
3 in. (DN80) ....................530020030
4 in. (DN100)....................530020040
6 in. (DN150)....................530020060
8 in. (DN200) ...................530020080
Flange x Grove ANSI
3 in. (DN80) ....................530030030
4 in. (DN100)....................530030040
6 in. (DN150)....................530030060
8 in. (DN200) ...................530030080
T x T NPT
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . .530060015
2 in. (DN50) ....................530060020

TFP1421
Page 17 of 18
Flange x Flange ISO
3 in. (DN80) ....................530040030
4 in. (DN100)....................530040040
6 in. (DN150)....................530040060
8 in. (DN200) ...................530040080
Flange x Groove ISO
3 in. (DN80) ....................530050030
4 in. (DN100)....................530050040
6 in. (DN150)....................530050060
8 in. (DN200) ...................530050080
T x T ISO
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530070015
2 in. (DN50) ....................530070020
Notes:
Valves are typically provided with flange
drilling per ANSI B16.1 (Class 125) or ISO
(7005-2 PN16).
Upon request, valves can be provided with
flange drilling per JIS B 2210 or AS 2129. In
whichcasepartnumbersare notassigned.
DV-5
A
Valve Trim
Specify: Size (specify), finish (specify),
Electric Actuation Trim for DV-5aAuto-
matic Water Control Valves used in
Single Interlock Preaction Fire Protec-
tion System, P/N (specify):
Galvanized
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 540101320
2 in. (DN50) ....................540101320
3 in. (DN80) ....................540101330
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 540101340
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 540101360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 540101380
Black
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 542101320
2 in. (DN50) ....................542101320
3 in. (DN80) ....................542101330
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 542101340
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 542101360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 542101380
Note: Pressure switches, solenoid valves
for electric actuation, water pressure
gauges, and BFV-300 Butterfly Valve are
separately ordered. NPT to ISO threaded
adaptors are provided for External Trim
Connections (drains, pressure switches,
water motor alarms, etc.).
APAC
DV-5A Valves with Galvanized Trim
Specify: Size (specify), DV-5aAuto-
matic Water Control Valve, (specify)
end connection with assembled galva-
nized APAC Single Interlock Preaction
Electric Actuation Trim, P/N (specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 5 50 011315
2 in. (DN50) ....................550 011320
3 in. (DN80) ....................550 011330
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550 011340
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550 0113 60
165,1 mm ......................550 01136 6
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550 011380
Flange x Flange ANSI
3 in. (DN80) ....................550021330
4 in. (DN100)....................550021340
6 in. (DN150)....................550021360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550021380
Flange x Groove ANSI
3 in. (DN80) ....................550031330
4 in. (DN100)....................550031340
6 in. (DN150)....................550031360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550031380
T x T NPT
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 550061315
2 in. (DN50) ....................550061320
Flange x Flange ISO
3 in. (DN80) ....................550041330
4 in. (DN100)....................550041340
6 in. (DN150)....................550041360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550041380
Flange x Groove ISO
3 in. (DN80) ....................550051330
4 in. (DN100)....................550051340
6 in. (DN150)....................550051360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550051380
Note: Pressure switches, P/N 52-287-1-124
solenoid valve, and psi/kPa water pressure
gauges are provided.
Separate DV-5
A
Valves without Trim
See Table A for flange drilling
specifications.
Specify: Size (specify), DV-5aAuto-
matic Water Control Valve, (specify)
end connection, P/N (specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530010015
2 in. (DN50) ....................530010020
3 in. (DN80) ....................530010030
4 in. (DN100)....................530010040
6 in. (DN150)....................530010060
165,1 mm ......................530010066
8 in. (DN200) ...................530010080
Flange x Flange ANSI
3 in. (DN80) ....................530020030
4 in. (DN100)....................530020040
6 in. (DN150)....................530020060
8 in. (DN200) ...................530020080
Flange x Grove ANSI
3 in. (DN80) ....................530030030
4 in. (DN100)....................530030040
6 in. (DN150)....................530030060
8 in. (DN200) ...................530030080
T x T NPT
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . .530060015
2 in. (DN50) ....................530060020
Flange x Flange ISO
3 in. (DN80) ....................530040030
4 in. (DN100)....................530040040
6 in. (DN150)....................530040060
8 in. (DN200) ...................530040080
Flange x Groove ISO
3 in. (DN80) ....................530050030
4 in. (DN100)....................530050040
6 in. (DN150)....................530050060
8 in. (DN200) ...................530050080
T x T ISO
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530070015
2 in. (DN50) ....................530070020
Notes:
Valves are typically provided with flange
drilling per ANSI B16.1 (Class 125) or ISO
(7005-2 PN16).
Upon request, valves can be provided with
flange drilling per JIS B 2210 or AS 2129. In
whichcasepartnumbersare notassigned.
DV-5
A
Valve Trim
Specify: Size (specify), finish (specify),
Electric Actuation Trim for DV-5aAuto-
matic Water Control Valves used in
Single Interlock Preaction Fire Protec-
tion System, P/N (specify):
Galvanized
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 540001320
2 in. (DN50) ....................540001320
3 in. (DN80) ....................540001330
4 in. (DN100)....................540001340
6 in. (DN150)....................540001360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 540001380
Black
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 542001320
2 in. (DN50) ....................542001320
3 in. (DN80) ....................542001330
4 in. (DN100)....................542001340
6 in. (DN150)....................542001360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 542001380
Note: Pressure switches and/or solenoid
valves for electric actuation are separately
ordered.
DV-5
A
Valve Trim Accessories
(for separately ordered valve trim)
Specify: Specify Accessory Descrip-
tion), P/N (specify):
Waterflow Pressure Alarm Switch, Potter
PS10-2 (America/APAC) . . . . . . . . . . . . . . 25720
Waterflow Pressure Alarm Switch
PS10-1 (EMEA). . . . . . . . . . . . . . . . . . . . . . . 0260
Supervisory Air Pressure Alarm Switch, Potter
PS40-2 (America/APAC) . . . . . . . . . . . . . . 25710
Supervisory Air Pressure Alarm Switch
PS40-1 (EMEA) . . . . . . . . . . . . . . . . . . . . . . 0262
Model WMA-1 Water Motor Alarm
(America/APAC) . . . . . . . . . . . . . . . . 526301001P
Model WMA-1 Water Motor Alarm
(EMEA) . . . . . . . . . . . . . . . . . . . . . . . 526301021R
Model G16AC812 Automatic Supervisory
Air Supply......................521201001
Model AMD-1 Air Maintenance Device
Supervisory Air Supply . . . . . . . . . . . 523242002
Model AMD-3 Nitrogen Maintenance Device
Supervisory Air Supply . . . . . . . . . . . 523282001
Water Gauges
with bar/psi ....................025500013
600 psi Water Gauge psi/kPa
(service pressure over 300 psi) . . . . . 923431004
Solenoid Valve for
Releasing Service .........Refer to Technical
Data Sheet TFP2180
DV-5
A
Valve Replacement Parts
Specify: (Description) for use with
(specify size) DV-5aAutomatic Water
Control Valve, P/N (See Figure 1)
DV-5
A
Valve Trim Replacement
Parts
Specify: (Description) for use with
DV-5aValve Trim, P/N (See Figure 6)

TFP1421
Page 18 of 18
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a trademark of The Chemours Company FC, LLC
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Other manuals for DV-5A
13
Table of contents
Other Tyco Control Unit manuals
Popular Control Unit manuals by other brands

Extron electronics
Extron electronics Interface IPL T PC1 user guide

Stahl
Stahl 9482/32 Series operating instructions

Crosswater
Crosswater KL0007WC installation instructions

Raytheon Anschütz
Raytheon Anschütz Standard 22 GYRO COMPASS Operator's and service manual

GatesAir
GatesAir Intraplex DA-191B Installation and operation manual

Stahl
Stahl 9469/35 Series operating instructions