Tyco DV-5A User manual

DV-5A Automatic Water Control Valve
Preaction Type A Systems (EN12845 Compliance)
DN40 to DN200
Page 1 of 20 SEPTEMBER 2022 TFP1485
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycore/tfp1485
General
Description
The TYCO DV-5aAutomatic Water
Control Valves are diaphragm type
valves that can be used in Preac-
tion Type A Fire Protection Systems
(EN12845). When properly trimmed, the
double seat design of the DV-5aValve
also provides actuation of re alarms
upon system operation.
Preaction Type A Fire Protection
Systems are characterized in normal
operation as being a single interlock
system wherein upon electric fire
detection the system piping is ooded
before sprinkler operation. Flooding of
the system converts the normally dry
pipe system into a water lled system
ready for sprinkler operation. The Pre-
action Type A Fire Protection Systems
are further characterized when being in
a fault detection, as in a loss of primary
and back-up battery electric power, as
converting to a dry pipe system. In dry
system mode, opening of a sprinkler
results in loss of system air pressure
and opening the DV-5aValve.
The diaphragm style design of the
DV-5aValve allows external resetting,
providing for easy resetting of the Pre-
acton Type A System without having to
open a valve handhole cover to manu-
ally reposition a clapper and/or latch
mechanism. Simply re-pressurizing the
diaphragm chamber resets the valve.
The DV-5afeatures internal and exter-
nal coating of the valve to provide
corrosion resistance. The external cor-
rosion resistance of the epoxy coating
permits the use of the DV-5ain cor-
rosive atmospheres associated with
many types of industrial processing
plants and outdoor installations.
The DV-5aValves are offered with the
DV-5aValve and separately ordered
semi-assembled trim shown in Figure
5, or, for ease of installation, with the
DV-5aValve completely trimmed.
Preaction Type A Systems utilize auto-
matic sprinklers and a supplemental
detection system. The supplemental
detection system is typically comprised
of 24 VDC heat detectors, smoke
detectors, and manual pull stations.
Actuation of the detection system auto-
Available End Connections and Weights — lb/(kg)
End Connection Nominal Valve Size
ANSI Inches
(DN)
Inlet Outlet 1-1/2
(40)
2
(50)
3
(80)
4
(100)
6
(150)
165,1
mm
8
(200)
Thread Thread 26
(11, 8)
25
(11, 3) N/A N/A N/A N/A N/A
Groove Groove 25
(11, 3)
25
(11, 3)
60
( 27, 2 )
95
(4 3,1)
177
(80,3)
177
(80,3)
327
(148,3)
Flange Groove N/A N/A 66
(30,0)
106
(4 8,1)
190
(86,2) N/A 346
(157,0)
Flange Flange N/A N/A 72
(32,7)
116
(52,6)
204
(92,5) N/A 365
(165,6)

TFP1485
Page 2 of 20
Nominal
Valve
Size
ANSI
Inches
(DN)
Flange Drilling Specification
Nominal Dimensions in Inches and (mm)
ANSI B16.11a
(Class 125) ISO 7005-2
(PN16)3bJIS B 2210
(10K) AS 2129
(Table E)
A B N A B N A B N A B N
3
(80)
6.00
(152,4)
0.75
(19,0) 46.30
(160,0)
0.75
(19,0) 85.90
(150,0)
0.59
(15,0) 8
5.75
(146,0) 0.71
(18,0) 4
4
(100)
7.50
(190,5)
0.75
(19,0) 87. 0 9
(180,0)
0.75
(19,0) 86.89
(175,0)
0.60
(15,0) 87. 0 0
178,0)
0.71
(18,0) 8
6
(150)
9.50
(241,3)
0.88
(22,2) 89.45
(240,0)
0.91
(23,0) 89.45
(240,0)
0.75
(19,0) 89.25
(235)
0.87
(22,0) 8
8
(200)
11.75
(298,5)
0.88
(22,2) 811.61
(295,0)
0.91
(23,0) 12 11.42
(290,0)
0.75
(19,0) 12 11. 50
(292,0)
0.87
(22,0) 8
NOTES:
a. Same drilling as for
ANSI B16.5 (Class 150) and
ANSI B16.42 (Class 150)
b. Same drilling as for
BS 4504 Section 3.2 (PN16) and
DIN 2532 (PN16)
Item Description Qty.
Nominal Valve Size ANSI Inch (DN)
1-1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150)e8 (DN200)
P/N P/N P/N P/N P/N P/N
1Valve Body 1N/R N/R N/R N/R N/R N/R
2Diaphragm 1545000020 545000020 545000030 545000040 545000060 545000080
3Diaphragm Cover 1N/R N/R N/R N/R N/R N/R
4 Hex Bolt, Short 2a545100001 545100001 545100002 545100003 545100004 545100003
5Hex Bolt, Long 2545100011 545100011 545100012 545100013 545100014 545100015
6Lift Washer 2bN/A N/A 545100021 545100022 545100023 545100022
7Hex Nut 2545100031 545100031 545100032 545100033 545100034 545100033
8Hoist Ring 2545100041 545100041 545100041 545100041 545100041 545100041
9Flat Washer 2N/A N/A 545100024 545100025 545100026 545100025
NOTES
a. Hex Bolt, Short, Qty. 6 in 6 and 8 inch (DN150 and DN200) assemblies.
b. Lift Washer not used in 1-1/2 and 2 inch (DN40 and DN50) assemblies.
c. N/R = Not Replaceable.
d. Order replacements parts only via Part Numbers given, do not replace Hex Bolt, Hex
Nut, Lift Washer or Hoist Ring with common hardware parts.
e. Also applicable to metric 165,1 mm size.
Dim. A
Bolt Circle
Diameter
Dim. B
Bolt Hole
Diameter
Qty. N
Number of
Bolt Holes
1-1/2 AND 2 INCH
VALVES ONLY
6 AND 8 INCH
VALVES ONLY
79 5
6
3
4
1
75
3
1
1
2
5
9
1
2
3
8
4
7
6
FIGURE 1
DV-5AVALVE ASSEMBLY AND REPLACEMENT PARTS
TABLE A
FLANGE DRILLING SPECIFICATIONS

TFP1485
Page 3 of 20
Port Port Description Port Sizes, NPT Inch per ANSI B1.20.1
1-1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150)a8 (DN200)
P1 Diaphragm Chamber Supply 1/2 1/2 1/2 1/2 1/2 1/2
P2 Water Supply Pressure & Alarm Test 1/2 1/2 1/2 1/2 1/2 1/2
P3 Alarm Actuation 3/4 3/4 3/4 3/4 3/4 3/4
P4 Automatic Drain Valve 1/2 1/2 1/2 1/2 1/2 1/2
P5 System Drain 3/4 3/4 3/4 3/4 3/4 3/4
P6 Main Drain 3/4 3/4 1-1/4 2 2 2
P7 System Air Supply 1/2 1/2 1/2 1/2 1/2 1/2
NOTES:
a. Also applicable to metric 165,1 mm size.
FIGURE 2A
FIGURE 2C
FIGURE 2B
FIGURE 2D
SYSTEM DRAIN CONDITION
WATER SUPPLY SHUT OFF
DRAIN FROM SYSTEM
SET CONDITION
WATER SUPPLY
SYSTEM OPEN TO ATMOSPHERE
ALARM PORT
WATERFLOW
TO ALARM
WATER SUPPLY
PRESSURE &
ALARM TEST
SYSTEM
DRAIN
OPEN
SYSTEM
DRAIN
OPEN
MAIN
DRAIN
CLOSED
MAIN
DRAIN
OPEN
DIAPHRAGM
CHAMBER
SUPPLY
FROM
UPSTREAM
SIDE OF
SHUT-OFF
VALVE
DIAPHRAGM
CHAMBER
DIAPHRAGM
CHAMBER
OPEN TO
ATMOSPHERE
VALVE
WATERWAY
DIAPHRAGM
SEAT
VALVE
WATERWAY
DIAPHRAGM
CHAMBER
SUPPLY
FROM
UPSTREAM
SIDE OF
SHUT-OFF
VALVE
DIAPHRAGM
AUTOMATICALLY
FLEXES TO
ITS SEATED
POSTION
DIAPHRAGM
CHAMBER
OPEN TO
ATMOSPHERE
DIAPHRAGM
RETRACTS
OPENING
VALVE
WATERWAY
VALVE
WATERWAY
DIAPHRAGM
SEAT
VALVE
WATERWAY
OPERATED CONDITION
WATER SUPPLY SHUT OFF
RESIDUAL DRAIN CONDITION
WATERFLOW FROM WATER SUPPLY
WATERFLOW TO SYSTEM
RESIDUAL DRAIN FROM SYSTEM
SYSTEM
AIR
SUPPLY
AUTOMATIC
DRAIN VALVE
OPEN TO
ATMOSPHERE
AUTOMATIC
DRAIN VALVE
CLOSED
FIGURE 2
DV-5AVALVE OPERATION, PREACTION TYPE A SYSTEMS

TFP1485
Page 4 of 20
matically operates (releases) the DV-5a
Valve, allowing water to ow into the
sprinkler piping system and to be dis-
charged from any sprinklers that may
subsequently open. In the event of loss
of power, the DV-5aValve with Preac-
tion Type A Trim will act as a regular
dry-pipe valve system.
The DV-5aValve with Preaction Type
A Trim has been designed in accor-
dance with the EN12845. This standard
denes operation as a dry pipe system
principally activated by an automatic
re detection system rather than the
operation of sprinklers.
Typically, the system designer selects
detection components electrically
operated that will respond to a re
sooner than the automatic sprin-
klers. Consequently, the system will
experience a minimal delay in water
delivery over that for a wet pipe sprin-
kler system because the system will
have begun to ll with water before a
sprinkler operates. Preaction Type A
Systems are typically designed as wet
pipe systems or according to the local
authority having jurisdiction.
The DV-5aValve with Preaction Type
A Trim is generally used to protect
areas where there is danger of serious
water damage that might result from
damaged automatic sprinklers or
piping. Typically, such areas include
computer rooms, storage areas
for valuable artifacts, libraries, and
archives.
These systems are also effectively used
to protect properties where a pre-alarm
of a possible re condition may allow
time for re extinguishment by alternate
suppression means, prior to a sprinkler
discharge. In the event the re cannot
otherwise be extinguished, the preac-
tion sprinkler system will then perform
as the primary re protection system.
NOTICE
The DV-5aValve with Preaction Type A
Trim described herein must be installed
and maintained in compliance with this
document, as well as with the EN12845
installation standard, in addition to
the standards of any other authorities
having jurisdiction. Failure to do so may
impair the performance of the related
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Technical
Data
Approvals
VdS Approved
Listings and Approvals are based
on DV-5aValve being trimmed as
described in this technical data sheet.
For local EMEA regional approvals,
consult with your local distributor.
DV-5aDeluge Valve
Components for the DN40 through
DN200 DV-5aValve are shown in Figure
1. The DV-5AValves are for vertical
installations. They are rated for use at
a service pressures of 3,0 to 20,7 bar.
The take-out dimensions are shown in
Figure 3, and anged connections are
available drilled per ANSI, ISO, AS, and
JIS specications as shown in TableA.
Threaded inlet and outlet connec-
tions are available in NPT or ISO 7/1.
Threaded port connections are NPT
threaded.
NOTE: PN16 flanges are pressure rated
to 16 bar.
Valve Trim
Preaction Type A 1.5 in. and 2 in. Trim
are the lesser of 15 bar or the sepa-
rately ordered solenoid valves accord-
ing to Technical Data Sheet TFP2180.
Preaction Type A 3 in. through 8 in. Trim
are the lesser of 16 bar or the sepa-
rately ordered solenoid valves accord-
ing to Technical Data Sheet TFP2180.
When the system pressure is greater
than 12,1 bar, provision is to be made
to replace the standard order 20,7 bar
Water Pressure Gauges with sepa-
rately ordered 41,1 bar Water Pressure
Gauges.
If the addition of an Alarm Control Valve
is desired or required by the local AHJ,
the Alarm Control Valve noted as Item
H in Figure 8 is to be a separately
ordered electronically supervised nor-
mally open valve.
External trim connections are NPT
threaded. EMEA trim is provided with
NPT x ISO 7/1 thread adapters.
Pressure Loss
See Graph A
8 Inch (DN200)
6 Inch (DN150)
4 Inch (DN100)
3 Inch (DN80)
2 Inch (DN50)
1-1/2 Inch (DN40)
22-3/8"
(569 mm)
16-3/4"
(425 mm)
13-3/4"
(349 mm)
10-3/16"
(260 mm)
10-3/16"
(260 mm)
27-7/16"
(697 mm)
DIMENSIONS SHOWN
ARE APPLICABLE TO
ALL END CONNECTION
CONFIGURATIONS
AVAILABLE PER
VALVE SIZE
FIGURE 3
DV-5AVALVE
TAKE-OUT DIMENSIONS

TFP1485
Page 5 of 20
Detection System
In order for DV-5aValves with Preac-
tion Type A Trim to be hydraulically
calculated as a wet pipe system, the
detection system must be designed
to operate sooner than the automatic
sprinklers on the sprinkler piping.
The DV-5aValve with Preaction Type A
Trim provides for electric operation of
the DV-5aValve by a detection system
consisting of electrical devices such
as heat sensitive thermostats, smoke
detectors, and/or manual pull stations.
Nominal installation dimensions for the
Preaction Type A Trim conguration are
shown in Figure 7.
NOTICE
The one each normally closed and
normally open, de-energized Sole-
noid Valves are separately ordered
and selected based on the required
laboratory approval acceptable to the
authority having jurisdiction. Refer to
Technical data Sheet TFP2180 for spe-
cific laboratory approvals. Consult with
the authority having jurisdiction regard-
ing installation criteria pertaining to
electric actuation circuitry.
System Air Pressure
Requirements
The DV-5aValve with Preaction Type
A Trim includes a Model DP-1 Dry
Pilot Actuator. In a fault detection - for
example, loss of primary and back-up
battery electric power - the DP-1 can
actuate the DV-5aupon sprinkler oper-
ation and resulting loss of system air
(or nitrogen) pressure. For more infor-
mation, refer to Technical Data Sheet
TFP1380.
The air (or nitrogen) pressure in the
sprinkler system is recommended to
be automatically maintained using one
of the following pressure maintenance
devices, as appropriate:
• An air supply in combination with
Model AMD-1 Air Maintenance
Device (pressure-reducing type)
described in Technical Data Sheet
(TDS) TFP1221.
• An air supply in combination with
Model AMD-2 Air Maintenance
Device (compressor-control type)
described in TDS TFP1231
• A nitrogen cylinder in combination
with Model AMD-3 Nitrogen Mainte-
nance Device (high pressure-reduc-
ing type) described in TDS TFP1241
See Graph B for the minimum system
air pressure.
The Supervisory Low Pressure
Alarm Switch is typically eld set at
0,4 bar below the minimum system air
pressure.
The Pressure Relief Valve is factory set
to fully open at 44.96 psi (3,1 bar) plus
or minus 2.03 (0,14 bar).
3 INCH (DN80)
2 INCH (DN50)
4 INCH (DN100)
8 INCH (DN200)
1-1/2 INCH (DN40)
6 INCH (DN150), 165,1 mm
200 400 1000 3000200060010050
50002000 3000 1000070001000600400200
4000
15000
9.0
8.0
4.0
6.0
5.0
7.0
3.0
2.0
1.0
0.7
0.9
0.8
0.5
0.4
0.6
0.3
NOMINAL PRESSURE DROP IN BAR
(1 PSI = 0,06895 BAR)
FLOW RATE IN LITERS PER MINUTE (LPM)
(1 GPM = 3,785 LPM)
NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI)
FLOW RATE IN GALLONS PER MINUTE (GPM)
0,022
0,080
0,030
0,040
0,060
0,050
0,070
0,100
0,090
0,200
0,300
0,400
0,500
0,600
GRAPH A
DV-5AVALVE
NOMINAL PRESSURE LOSS VERSUS FLOW

TFP1485
Page 6 of 20
Materials of
Construction
Valve Body
Epoxy coated ductile iron per ASTM
A536-77, Grade 65-45-12
Diaphragm Cover
Epoxy coated ductile iron per ASTM
A536-77, Grade 65-45-12
Diaphragm
Polyester fabric reinforced, TEFLON
coated, EPDM rubber per ASTM D2000
Diaphragm Cover Fasteners
Aluminum zinc coated steel
Common Hardware Trim
•
Common hardware pipe ttings are
galvanized or black as required and
are malleable per ASME B16.3.
•
Common hardware pipe nipples are
galvanized or black as required and
are Schedule 40 per ASTM A53 or
A135.
•
Common hardware compression
ttings are brass per ASTM B16.
•
Common hardware tubing is Type L
copper per ASTM B88.
Operation
The TYCO DV-5aValve is a diaphragm
style valve that depends upon water
pressure in the Diaphragm Chamber
as shown in Figure 2A to hold the
Diaphragm closed against the water
supply pressure.
When the DV-5aValve is set for service,
the Diaphragm Chamber is pressurized
through the trim connections from the
inlet side of the system’s main control
valve.
Opening an actuation device (solenoid
valve or dry pilot actuator) trips the
Model MRA-1 Manual Reset Actuator.
Tripping the MRA-1 releases water from
the DV-5aDiaphragm Chamber faster
than it can be replenished through the
1/8 in. (3,2 mm) restriction located in
the diaphragm chamber supply con-
nection. Release of water through the
MRA-1 results in a rapid pressure drop
in the DV-5aDiaphragm Chamber. The
force differential applied through the
Diaphragm to hold the Diaphragm in
the set position is reduced below the
valve trip point. The water supply pres-
sure then forces the Diaphragm open
permitting water to ow into the system
piping, as well as through the Alarm
Port to actuate the system alarms as
shown in Figure 2B.
In normal operation, the system air
pressure is monitored by a Super-
visory Low Pressure Alarm Switch.
Should damage occur to a sprinkler or
the system piping, loss of air pressure
will not result in opening of the DV-5a
Valve and ooding of the system with
resulting inadvertent water discharge.
Loss of system air pressure will only
result in a low air alarm so that repairs
to the system can be facilitated to avoid
unnecessary water damage should the
system be activated in the event of a
re.
However, in the event of a re, opera-
tion of an electrical detection device
such as a heat-sensitive thermostat
or smoke detector signals the deluge
valve releasing panel to energize the
normally closed Solenoid Valve. In
turn, the energized Solenoid Valve
opens to release water from the Dia-
phragm Chamber faster than it can be
replenished through the restriction pro-
vided in the diaphragm supply connec-
tion. This release of water results in a
rapid pressure drop in the Diaphragm
Chamber to below the valve trip point.
The water supply pressure then forces
SYSTEM PIPING WITH AUTOMATIC SPRINKLERS - NORMALLY DRY
ELECTRIC DETECTION SYSTEM
(TYPICALLY 24 VOLTS DC)
HEAT DETECTORS, SMOKE DETECTORS,
MANUAL PULL STATIONS, ETC.
SYSTEM DRAIN VALVE
(NORMALLY CLOSED)
MAIN
DRAIN VALVE
(NORMALLY
CLOSED)
LOCAL
MANUAL
CONTROL
STATION
MAIN
CONTROL VALVE
(NORMALLY
OPEN)
WATER
SUPPLY
DIAPHRAGM CHAMBER
PRESSURE GAUGE
WATER SUPPLY
PRESSURE
GAUGE
MANUAL RESET
ACTUATOR
WATERFLOW
PRESSURE
ALARM
SWITCH
DELUGE VALVE
RELEASING PANEL
(AUTOMATIC
CONTROL UNIT
WITH BATTERY
BACK-UP)
MANUAL ELECTRIC
PULL STATION
(AS REQUIRED)
POWER
SUPPLY
(TYPICALLY
120 VOLTS AC)
AUTOMATIC
AIR/NITROGEN
SUPPLY
(GRAPH A)
DRY PILOT
ACTUATOR
SUPERVISORY
LOW PRESSURE
ALARM SWITCH
DRAIN
N.O.
RESTRICTION DRAIN
N.O.
DRAIN DRAIN
DRAIN
DRAIN
SOLENOID
VALVE
(NORMALLY
CLOSED
ENGERGIZED)
SOLENOID
VALVE
(NORMALLY
CLOSED
DE-ENGERGIZED)
DV-5A
VALVE
SYSTEM AIR
PRESSURE
GAUGE
WATER SUPPLY SHUT-OFF
(NORMALLY OPEN)
DIAPHRAGM
CHAMBER SUPPLY
CONTROL VALVE
(NORMALLY OPEN)
DIAPHRAGM CHAMBER
SUPPLY CONNECTION
FIGURE 4
DV-5AVALVE - PREACTION TYPE A SYSTEM
SCHEMATIC DIAGRAM

TFP1485
Page 7 of 20
the Diaphragm open, permitting water
to ow into the system piping, as well
as through the Alarm Port to actuate
the system alarms.
In the event of a fault detection in the
re detection system, the system con-
verts to operate as an ordinary dry pipe
system, which means the energized-to-
close Solenoid Valve in the actuation
loop becomes de-energized and open
to communicate any system air pres-
sure loss to the DP-1 Dry Pilot Actu-
ator. As soon as a sprinkler operates/
activates, the subsequent drop in air
pressure opens the Dry Pilot Actuator.
Water from the diaphragm pressure
piping will exit the Dry Pilot Actuator
through this drain, resulting in the acti-
vation of the DV-5aDeluge Valve.
Upon opening of the DV-5aValve,
whether by Solenoid Valve or Dry Pilot
Actuator, the Model MRA-1 Manual
Reset Actuator opens to constantly
vent the DV-5aDiaphragm Chamber
to hydraulically latch the DV-5ain the
tripped position until manually reset.
For more information on the TYCO
Model MRA-1 Manual Reset Actuator,
refer to Technical Data Sheet TFP1387.
Due to the functionality of the Model
MRA-1 Manual Reset Actuator, the
release circuit of the releasing panel
need only provide the typical ten
minutes of alarm condition intended
to energize the Solenoid Valve to
open. After the ten minute duration, at
which point should the Solenoid Valve
become de-energized and close (espe-
cially while operating under battery
back-up), the MRA-1 will have already
automatically opened, thereby prevent-
ing the DV-5a Diaphragm Chamber
from becoming re-pressurized, and
preventing an inadvertent closing of
the DV-5a during a re event.
Installation
The TYCO DV-5aValve with Preaction
Type A Trim is to be installed in accor-
dance with this section.
NOTICE
DV-5AAutomatic Water Control Valves
are designed to be used in freshwa-
ter systems. When the supply is from
an alternative source such as brackish
water, saltwater, or contains additives
such as foam, the limited warranty is
reduced to one year from the time of
installation. An increase in frequency of
inspections is required when the valve
is exposed to such supplies and other
corrosive conditions or chemicals that
could impact valve materials or the
operation of the assembly. The system
and all components must be designed
accordingly for the increased demand.
It is required to thoroughly flush the
valve and trim assembly with freshwa-
ter and reset to the set condition after
each operation.
Proper operation of the DV-5aValve
depends upon its trim being installed in
accordance with the instructions given
in this technical data sheet. Failure to
follow the appropriate trim diagram
may prevent the DV-5aValve from func-
tioning properly, as well as void approv-
als and the manufacturer’s warranties.
The DV-5aValve must be installed in a
readily visible and accessible location.
The DV-5aValve and associated trim
must be maintained at a minimum tem-
perature of 40°F (4°C).
Heat tracing of the DV-5aValve or its
associated trim is not permitted. Heat
tracing can result in the formation of
hardened mineral deposits that are
capable of preventing proper operation.
Always open the system control valves
slowly to avoid a sudden rush of water
entering the system.
The DV-5aValve is to be installed in
accordance with the following criteria:
Step 1. All nipples, ttings, and devices
must be clean and free of scale and
burrs before installation. Use pipe
thread sealant sparingly on male pipe
threads only.
Step 2. The DV-5aValve must be
trimmed in accordance with Figure 5.
Note:If the addition of an Alarm Control
Valve is desired or required by the local
AHJ, the Alarm Control Valve noted as
Item H in Figure 8 is to be a separately
ordered electronically supervised nor-
mally open valve.
Step 3. Care must be taken to ensure
that check valves, strainers, globe
valves, etc. are installed with the ow
arrows in the proper direction.
Step 4. Drain tubing to the Drip Funnel
must be installed with smooth bends
that will not restrict ow.
Step 5. The Main Drain and Drip Funnel
Drain may be interconnected provided
a check valve is located at least 12 in.
(300 mm) below the Drip Funnel.
Step 6. Suitable provision must be
made for disposal of drain water. Drain-
age water must be directed such that
it will not cause accidental damage to
property or danger to persons.
Step 7. Connect the Diaphragm Supply
Valve to the inlet side of the System
Main Control Valve in order to facilitate
setting of the DV-5AValve as shown in
Figure 8.
Step 8. Provisions must be made for
installation of an Inspector's Test Con-
nection (ITC) at the most hydraulically
demanding location of the sprinkler
system. The maximum orice size of
the ITC is to be no greater than the
NOTES:
The dew point of the pilot line air pressure must be maintained
below the lowest ambient temperature to which the dry pilot
actuation system will be exposed. Accumulation of water in the
pilot line connection to the Actuator will lower the air pressure
at which the actuator will open and possibly prevent proper
operation. Also, introduction of moisture into the pilot lines
exposed to freezing temperatures can create an ice buildup
that could prevent proper operation of the Actuator.
An air dryer must be installed where the moisture content
of the air supply is not properly controlled at less than the
required value.
It is recommended that an AMD-3 Nitrogen Maintenance
Device be utilized in dry pilot actuation system applications
where the dew point must be maintained below -29°C. Refer
to Technical Data Sheet TFP1241.
WATER SUPPLY PRESSURE IN BAR
AIR PRESSURE IN BAR
1,0
0
2,0
3,0
4,0 6,0 10,0
16,0
8,0 12,0 14,03,0
SYSTEM AIR PRESSURE
RANGE OF ACTUATOR OPENING PRESSURE
GRAPH B
DV-5AVALVE - PREACTION TYPE A SYSTEM
AIR PRESSURE REQUIREMENTS

TFP1485
Page 8 of 20
Notes:
1. Port Connections P1 through P7 are described in Figure 2.
2. External Trim Connections C1 through C5 are described in Figure 8.
3. When ordering pre-assembled "DV-5AValve with Galvanized Valve Trim" Items A1 through A3 are provided. Solenoid valves are ordered separately.
4. When ordering DV-5A Trim separately from the DV-5AValve, Items A1 through A8 are separately ordered, as applicably related to valve size. Water
Pressure Gauges and Solenoid Valves are also separately ordered.
Assemble in order
from A to P.
NIPPLE SELECTION PER VALVE SIZE
NIPPLE 1-1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) 8 IN. (DN200)
56 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 3-1/4" 1/2" x 3-1/4" 1/2" x 3-1/4" 1/2" x 1-1/2"
60 1/2" x 5-1/2" 1/2" x 5-1/2" 1/2" x 4-1/2" 1/2" x 6" 1/2" x 9" 1/2" x 11"
61 1/2" x 9" 1/2" x 9" 1/2" x 8" 1/2" x 7-1/2" 1/2" x 9-1/2" 1/2" x 10"
C3
C5
C6
C7
C4
C2
C1
P1
P2
P3
P6
P7 P4
P5
54
59
58
A1
A5
A4
A3
A2
A6
A8
A7
E
D
C
A
B
G
H
J
K
L
M
N
P
F
FIGURE 5
DV-5AVALVE - PREACTION TYPE A TRIM
SEMI-ASSEMBLED

TFP1485
Page 9 of 20
Notes:
1. Port Connections P1 through P7 are
described in Figure 2.
2. External Trim Connections C1 through
C5 are described in Figure 8.
3. When ordering pre-assembled "DV-5A
Valve with Galvanized Valve Trim" Items
A1 through A8 are provided. Solenoid
valves are ordered separately.
4. When ordering DV-5A Trim separately
from the DV-5A Valve, Items A1 through
A8 are separately ordered, as applicably
related to valve size. Water
Pressure Gauges and Solenoid Valves
are also separately ordered.
ITEM QTY DESCRIPTION CH 1-1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150)b8 IN. (DN200)
1 2 1/4" INCH GAUGE TEST VALVE 460051003 460051003 460051003 460051003 460051003 460051003
2 1 MRA-1 MANUAL RESET ACTUATOR 545001000 545001000 545001000 545001000 545001000 545001000
3 1 MC-2 MANUAL CONTROL STATION 545002000 545002000 545002000 545002000 545002000 545002000
4 1 AD-3 AUTOMATIC DRAIN VALVE 547932004 547932004 547932004 547932004 547932004 547932004
5 1 DP-1 DRY PILOT ACTUATOR 522801001 522801001 522801001 522801001 522801001 522801001
6 1 PRIMING SUPPLY RESTRICTION 545100051 545100051 545100051 545100051 545100051 545100051
7 1 1/4" PRESSURE RELIEF VALVE 923431020 923431020 923431020 923431020 923431020 923431020
8 3 1/2" BALL VALVE 460501004 460501004 460501004 460501004 460501004 460501004
9 1 1/2" GLOBE VALVE 460471005 460471005 460471005 460471005 460471005 460471005
10 2 1/2" SPRING LOADED CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003
11 2 1/2" SWING CHECK VALVE 460491007 460491007 460491007 460491007 460491007 460491007
12 21/2" Y-STRAINER 523531006 523531006 523531006 523531006 523531006 523531006
13 1 3/4" ANGLE VALVE 460481010 460481010 460481010 460481010 460481010 460481010
14 1ANGLE VALVE 460481010 460481010 460481011 460481012 460481012 460481012
15 1DRIP FUNNEL BRACKET CONNECTOR 9221110 0 5 9 2 211100 5 9 2 2111005 9 221110 05 9221110 0 5 9 221110 05
16 1 DRIP FUNNEL BRACKET 9221110 0 3 9 2 211100 3 9 2 211100 3 9 2 2111003 9221110 03 9 2211100 3
17 1DRIP FUNNEL 923431007 923431007 923431007 923431007 923431007 923431007
18 2 COMP. FITTING 90° 1/2" MNPT x 1/2" OD TUBE 1001253-01 1001253-01 1001253-01 1001253-01 1001253-01 1001253-01
19 2 COMP. FITTING 90° 1/2" FNPT x 1/2" OD TUBE 1001420-01 1001420-01 1001420-01 1001420-01 1001420-01 1001420-01
20 4 FLARE FITTING 1/2" NPT x 1/2" TUBE 545100061 545100061 545100061 545100061 545100061 545100061
21 2 FLARE FITTING 90° 1/2" NPT x 1/2" TUBE 545100062 545100062 545100062 545100062 545100062 545100062
22 2 FLARE FITTING 3/4" NPT x 3/4" TUBE 545100063 545100063 545100063 545100063 545100063 545100063
23 2PIPE PLUG ✓1/4" 1/4" 1/4" 1/4" 1/4" 1/4"
C6
C7
C4
C2
C5
C3
C1
P1
P6
P7
P2
P3
P4
P5
A5
A4
A1
A3
A2
A6
A8
A7
2
10
18
14
34
62
61 22
13 3
30
40
15
12
38
28
38
8
25
54
22
53
25
32 36
123
26
50
21
39
8
38
28
21
44
6
46
63
17 16
4
33
24
60
55
33
43
27 56
57
59
37
30
67
68
63
19
37
19
47
48
39
58
28
18 5
49
65
51
37 37
30
29 30
37
25
37
37
37
38
20
29 66
52
30
20
12
20
31
37
11
37
30
9
37
32
8
37
38
28
41
64
28
23
37
11
42
30
28
37 1
35
31
38
64
37
20
10
7
45
FIGURE 6 (1 OF 2)
DV-5AVALVE - PREACTION TYPE A TRIM
EXPLODED VIEW

TFP1485
Page 10 of 20
ITEM QTY DESCRIPTION CH 1-1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150)b8 IN. (DN200)
24 1PIPE PLUG ✓3/4" 3/4" 3/4" 3/4" 3/4" 3/4"
25 3UNION ✓1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
26 1STREET ELBOW ✓1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90°
27 1ELBOW ✓1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45°
28 6ELBOW ✓1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90°
29 2COUPLING ✓1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
30 7TEE ✓1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
31 2REDUCING TEE ✓1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2"
32 2REDUCING TEE ✓1/2 "x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4"
33 2REDUCING TEE ✓3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4"
34 1REDUCING TEE ✓3/4" x 3/4" x 3/4" 3/4" x 3/4" x 3/4"
1-1/4
"
x 1-1/4
"
x 3/4
"
2" x 2" x 3/4" 2" x 2" x 3/4" 2" x 2" x 3/4"
35 1PIPE NIPPLE ✓1/4" x CLOSE 1/4" x CLOSE 1/4" x CLOSE 1/4" x CLOSE 1/4" x CLOSE 1/4" x CLOSE
36 1PIPE NIPPLE ✓1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2"
37 15 PIPE NIPPLE ✓1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE
38 6PIPE NIPPLE ✓1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2"
39 2PIPE NIPPLE ✓1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2"
40 1PIPE NIPPLE ✓1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2"
41 1PIPE NIPPLE ✓1/2" x 3" 1/2" x 3" 1/2" x 3" 1/2" x 3" 1/2" x 3" 1/2" x 3"
42 1PIPE NIPPLE ✓1/2" x 4" 1/2" x 4" 1/2" x 4" 1/2" x 4" 1/2" x 4" 1/2" x 4"
43 1PIPE NIPPLE ✓1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5"
44 1PIPE NIPPLE ✓3/4"x 1-1/2"3/4"x 1-1/2"3/4"x 1-1/2"3/4"x 1-1/2"3/4"x 1-1/2"3/4"x 1-1/2"
45 1PIPE NIPPLE ✓3/4"x 4-1/2"3/4"x 4-1/2"3/4"x 4-1/2"3/4"x 4-1/2"3/4"x 4-1/2"3/4"x 4-1/2"
46 1TUBING, MRA-1 DRAIN 535001420 535001420 535001430 535001440 535001460 535002180
47 1TUBING, MC-2 DRAIN 535001520 535001520 535001530 535001540 535001560 535001580
48 1TUBING, DP-1 DRAIN 535001620 535001620 535001630 535001640 535001660 535001680
49 1TUBING, SOLENOID DRAIN 5350 01720 5350 01720 535001730 5350 01740 535001760 535001780
50 1 TUBING ASSY, ALARM TEST INTERCONNECT 535000320 535000320 535000330 535000340 535000360 535000380
51 1TUBING ASSY, AIR SUPPLY INTERCONNECT 535001820 535001820 535001830 535001840 535001860 535001880
52 1TUBING ASSY, ACTUATION 535001900 535001900 535001901 535001902 535001903 535001904
53 1 TUBING ASSY, SYSTEM DRAIN 535000420 535000420 535000430 535000440 535000460 535000480
54 1PIPE NIPPLE ✓1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 3-1/4" 1/2" x 3-1/4" 1/2" x 3-1/4" 1/2" x 1-1/2"
55 1PIPE NIPPLE ✓1/2" x 3-1/2" 1/2" x 3-1/2" 1/2" x 4-1/2" 1/2" x 5-1/2" 1/2" x 5-1/2" 1/2" x 6-3/4"
56 1PIPE NIPPLE ✓1/2" x 5" 1/2" x 5" 1/2" x 5-1/2" 1/2" x 5-1/2" 1/2" x 5-1/2" 1/2" x 6-1/2"
57 1PIPE NIPPLE ✓1/2" x 5" 1/2" x 5" 1/2" x 4-1/2" 1/2" x 5" 1/2" x 7-1/2" 1/2" x 9-1/2"
58 1PIPE NIPPLE ✓1/2" x 5-1/2" 1/2" x 5-1/2" 1/2" x 4-1/2" 1/2" x 6" 1/2" x 9" 1/2" x 11"
59 1PIPE NIPPLE ✓1/2" x 9" 1/2" x 9" 1/2" x 8-1/2" 1/2" x 7-1/2" 1/2" x 9-1/2" 1/2" x 10"
60 1PIPE NIPPLE ✓3/4" x 5" 3/4" x 5" 3/4" x 6" 3/4" x 7" 3/4" x 9" 3/4" x 11-1/2"
61 1PIPE NIPPLE ✓3/4" x 4-1/2" 3/4" x 4-1/2" 1-1/4" x 3-1/4" 2" x 3" 2" x 3" 2" x 3"
62 1PIPE NIPPLE ✓3/4" x 6-1/2" 3/4" x 6-1/2" 1-1/4" x 5-1/2" 2" x 5" 2" x 6" 2" x 8"
63 2
WATER PRESSURE GAUGE, 300 PSI / 2000 kPa
(APAC)
923431005 923431005 923431005 923431005 923431005 923431005
63 2
WATER PRESSURE GAUGE, 20 bar / 2000 kPa
(EMEA)
025500013 025500013 025500013 025500013 025500013 025500013
64 2AIR PRESSURE GAUGE, 80 PSI / 550 kPa
RETARDED TO 250PSI / 1750 kPa 923431012 923431012 923431012 923431012 923431012 923431012
65 1
SOLENOID VALVE NORMALLY CLOSED (Separately
Ordered)
52 2871124 522871124 522871124 522871124 522871124 522871124
66 1
SOLENOID VALVE NORMALLY OPEN (Separately
Ordered)
2191866 2191866 2191866 2191866 2191866 2191866
67 1LABEL 545003006 545003006 545003006 545003006 545003006 545003006
68 1 LABEL WIRE — — — — — —
A1 1DV-5
A
VALVE REFER TO TABLE D FOR DV-5A PART NUMBERS
A2
1WATERFLOW PRESSURE ALARM SWITCH,
DOUBLE CONTACTS (APAC) 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102
1WATERFLOW PRESSURE ALARM SWITCH,
SINGLE CONTACTS (EMEA) 0260 0260 0260 0260 0260 0260
1WATERFLOW PRESSURE ALARM SWITCH,
DOUBLE CONTACTS (AMER) 25710 25710 25710 25710 25710 25710
A3
1 LOW AIR PRESSURE ALARM SWITCH (AMER) 25730 25730 25730 25730 25730 25730
1 LOW AIR PRESSURE ALARM SWITCH (EMEA) 0262 0262 0262 0262 0262 0262
1 LOW AIR PRESSURE ALARM SWITCH (APAC) 25730 or 100402 25730 or 100402 25730 or 100402 25730 or 100402 25730 or 100402 25730 or 100402
A4 1 BFV-300 BUTTERFLY VALVE, G x G — — 59300G030WS 59300G040WS 59300G060WS 59300G080WS
A5 1FIGURE 577 RIGID GROOVED COUPLING — — 57730ACP 5774 0AC P 57760ACP 57780ACP
A6 1INVERTED FLARE SHUT-OFF VALVEa— — 545100099 545100100 545100100 545100100
A7 1 FLARE FITTING 90° 1/2" NPT x 1/2" TUBE — — 545100062 545100062 545100062 545100062
A8 1TUBING ASSY, DIAPHRAGM CHAMBER SUPPLY — — 535000230 535000240 535000260 535000280
NOTES
a. Not VdS Approved
b. Also applicable to metric 165,1 mm size.
CH - Common Hardware - Refer to Materials of Construction section for specications.
FIGURE 6 (2 OF 2)
DV-5AVALVE - PREACTION TYPE A TRIM
EXPLODED VIEW

TFP1485
Page 11 of 20
Nominal
Valve
Size
ANSI
Inches
(DN)
Inches
(mm)
A B C D E F G H J
1-1/2
(40)
2.8
(71)
10.4
(264)
9.8
(249)
17.7
(450)
23.0
(584)
7.4
(188)
10.2
(259)
8.02
(204)
1.2
(31)
2
(50)
2.8
(71)
10.4
(264)
9.8
(249)
17.7
(450)
23.0
(584)
7.4
(188)
10.2
(259)
8.09
(205)
2.9
(74)
3
(80)
4.0
(102)
12.8
(325)
11.5
(292)
17.9
(455)
24.7
(627)
6.2
(158)
13.8
(351)
3.8
(96)
3.6
(91)
4
(100)
4.5
(114)
14.0
(356)
12.6
(320)
17.0
(432)
25.5
(648)
5.5
(140)
16.8
(427)
4.54
(115)
4.3
(109)
63
(150)
5.7
(145)
15.5
(394)
14.5
(368)
20.8
(528)
28.5
(724)
3.8
(97)
22.4
(569)
5.83
(148)
5.7
(145)
8
(200)
6.8
(174)
16.4
(417 )
16.7
(424)
22.3
(566)
30.9
(785)
3.3
(84)
27. 5
(699)
5.24
(133)
6.7
(170)
NOTES
1.
Dimensions based on drain valves being open.
2.
Dimensions do not provide installation clearance.
3. Also applicable to metric 165,1 mm size.
HF
E
DCB
J
A
G
FIGURE 7
DV-5AVALVE - PREACTION TYPE A
NOMINAL DIMENSIONS

TFP1485
Page 12 of 20
smallest orice sprinkler installed in
the system.
Step 9. An Air Maintenance Device,
as described in the Technical Data
section, must be provided for air supply
connection.
Step 10. A desiccant dryer, when spec-
ied, is to be installed between a drip
leg and the Air Maintenance Device.
Step 11. The Supervisory Low Pres-
sure Alarm Switch is to be adjusted to
provide a low air alarm at approximately
0,4 bar below the system air pressure
requirement shown in Graph B.
Step 12. Unused Pressure Alarm
Switch connections must be plugged.
Step 13. The Pressure Relief Valve pro-
vided with the Preaction Type A Trim is
factory set to relieve at a pressure of
approximately 3,1 bar, which can typi-
cally be used for a maximum system
pressure of 2,8 bar. The Pressure Relief
Valve may be reset; however, it must be
reset to relieve at a pressure which is
in accordance with the requirements of
the authority having jurisdiction.
To reset the Pressure Relief Valve, rst
loosen the jam nut and then adjust the
cap accordingly, clockwise for a higher
pressure setting or counter clockwise
for a lower pressure setting. After ver-
ifying the desired pressure setting,
tighten the jam nut.
Step 14. Conduit and electrical con-
nections are to be made in accordance
with the applicable standards of the
approval agency.
Step 15. Before a system hydrostatic
test is performed, the DV-5aDiaphragm
Chamber is to be depressurized, the
Automatic Drain Valve is to be tem-
porarily replaced with a plug, and the
Diaphragm Cover Bolts must be uni-
formly and securely tightened using
a cross-draw sequence.After tight-
ening, double-check to make certain
that all of the Diaphragm Cover Bolts
are securely tightened. See Table B in
the Care and Maintenance section for
torque specications.
Valve Setting
Procedure
Perform Steps 1 through 16 when ini-
tially setting the TYCO DV-5aValve with
Preaction Type A Trim, after an opera-
tional test of the re protection system,
or after system operation due to a re.
The valve with trim is shown in Figure 8.
Step 1. Close the System Main Control
Valve (B).
Step 2. Close the Diaphragm Supply
Valve (P). Close the Air Supply Control
Valves (X) and (Y).
Step 3. Open the Main Drain Valve (D),
System Drain Valve (E), and all auxil-
iary drains in the system. Also, remove
the plug from the Air Supply Strainer
(W) to drain any water that is present
and to ensure the it is clean and free of
debris. Close the auxiliary drain valves,
System Drain Valve (E), and reassemble
the Air Supply Strainer (W) after water
ceases to discharge. Leave the Main
Drain Valve (D) open.
At this time make certain that the
Pressure Gauge Valves and the Alarm
Control Valve (H), as applicable, are
open.
Step 4. Depress the plunger of the
Automatic Drain Valve (F) to verify that
it is open.
Step 5. Clean the Diaphragm Supply
Strainer (Q) by removing the clean-
out plug and strainer basket. The Dia-
phragm Supply Strainer (Q) may be
ushed out by momentarily opening
the Diaphragm Supply Valve (P).
Step 6. Replace operated automatic
sprinklers on the system piping.
NOTICE
In order to prevent the possibility of a
subsequent operation of an overheated
solder type pilot sprinkler, any solder
type pilot sprinklers that were possibly
exposed to a temperature greater than
their maximum rated ambient must be
replaced.
Step 7. Reset the DV-5aValve Releas-
ing Panel in accordance with the manu-
facturer instructions.
Step 8. Re-establish system air pres-
sure to reset the Model DP-1 Dry Pilot
Actuator (T) by opening the Air Supply
Control Valve (X). Do not open the Air
Supply Control Valve (Y) at this time.
The Dry Pilot Actuator (T) air pressure
will be indicated on the Dry Pilot Gauge
(Z).
Step 9. Operate (open) the Manual
Control Station (M) and then open
the Diaphragm Supply Valve (P). After
unaerated water ceases to discharge
from the Manual Control Station (M)
drain tube, slowly close the operating
lever by pushing it up. Do not close the
hinged cover at this time.
Step 10. After allowing water to ow
out of the Manual Reset Actuator (N)
drain tube until aerated water ceases
to discharge, reset the Manual Reset
Actuator (N) by pressing the Reset
Knob and hold until water stops owing
from its drain tube and the pressure
builds and reaches approximately 15
psi (1,0 bar) on the Diaphragm Gauge
(K). Pressure will then build up in the
DV-5aDiaphragm Chamber.
Step 11. Verify the ability for the DV-5a
Diaphragm to hold pressure as follows:
•
With the diaphragm chamber
pressurized per Step 10, tempo-
rarily close the Diaphragm Supply
Valve (P), and then observe the
Diaphragm Gauge (K) for a drop in
pressure.
•
If a drop in pressure is noted, the
DV-5aDiaphragm is to be replaced
and/or any leaks must be corrected
before proceeding to the next step.
•
If the Diaphragm Gauge (K)
indicates no drop in pressure,
re-open the Diaphragm Supply
Valve (P) and proceed to the next
step.
Step 12. Open the Air Supply Control
Valve (Y) to pressurize the system
piping. The system air pressure will be
indicated on the System Gauge (L).
Step 13. Partially open the System
Main Control Valve (B). Slowly close the
Main Drain Valve (D) as soon as water
discharges from the Main Drain Valve
(D). Observe the Automatic Drain Valve
(F) for leaks. If there are leaks, deter-
mine/correct the cause of the leakage
problem before proceeding.
NOTICE
When the System Main Control Valve
(B) is partially opened, the pressure on
the DV-5aDiaphragm Chamber may
increase. This increase in pressure is
normal, and if the pressure is greater
than the valve trim maximum pressure
rating provided in the Technical Data
section, the pressure is to be relieved
to at least the valve trim pressure rating
by partially and temporarily opening the
Manual Control Station (M); however,
do not allow the pressure as indicated
on the Diaphragm Gauge (K) to drop
below the supply pressure shown on
the Water Supply Gauge (J), since this
action may result in tripping of the
DV-5aValve.
Step 14. Close the hinged cover on the
Manual Control Station (M) and insert a
new break rod in the small hole through
the top of the enclosing box.
Step 15. Fully open the System Main
Control Valve (B).
Step 16. After setting a re protec-
tion system, notify the proper authori-
ties and advise those responsible for
monitoring proprietary and/or central
station alarms.

TFP1485
Page 13 of 20
Note:
Port Connections P1 through P7 are described in Figure 2.
Item Description
N
P
Q
R
S
T
U
V
W
X
Y
Z
AA
Manual Reset Actuator
Diaphragm Supply Valve
Diaphragm Supply Strainer
Solenoid Valve (NC) De-Energized #1
Solenoid Valve (NC) Energized #2
Dry Pilot Actuator
Pressure Relief Valve
Supervisory Low Pressure Alarm Switch
Air Supply Strainer
Air Supply Control Valve "A"
Air Supply Control Valve "B"
Dry Pilot Gauge
Inverted Flare Shut-Off Valve
Item Description
A
B
C
D
E
F
G
H
J
K
L
M
DV-5aValve
System Main Control Valve
Waterow Pressure Switch
Main Drain Valve
System Drain Valve
Automatic Drain Valve
Alarm Test Valve
Alarm Control Valve (Optional)
Water Supply Gauge
Diaphragm Gauge
System Gauge
Manual Control Station
External Trim Connections
C1
C2
C3
C4
C5
C6
C7
Diaphragm Supply Connection
Water Motor Alarm Connection
Air Supply Connection
Waterow Pressure Alarm
Switch Connection
Low Air Pressure Switch
Connection
Main Drain Connection
Drip Funnel Drain Connection
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
C6
C7
C2
C5
C3
C4
C1
A
B
C
JK
D
E
F
G
N
P
Q
V
X
Y
M
W
S
T
R
L
Z
U
H
AA
P1
P6
P7
P2
P3
P4
P5
FIGURE 8
DV-5AVALVE - PREACTION TYPE A
(Refer to Figures 6 for specific Bills of Materials)

TFP1485
Page 14 of 20
Care and
Maintenance
The following procedures and inspec-
tions must be performed as indicated,
in addition to any specic requirements
of EN12845. Any impairment must be
immediately corrected. The DV-5a
valve and trim assembly is shown in
Figure 8.
NOTICE
If the water supply needs to be shut off
to the DV-5avalve and trim and cannot
be shut off upstream of the system,
close the System Main Control Valve
(B), the Diaphragm Supply Valve (P),
and the Inverted Flare Shut-Off Valve
(AA). This will allow any trim above the
System Main Control Valve (B) to be
taken apart for service if necessary.
The frequency at which the following
procedures and inspections are to be
performed are to be in accordance with
EN12845.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down
the affected fire protection systems
must first be obtained from the proper
authorities and all personnel who may
be affected by this action must be
notified.
Some of the procedures outlined in
this section will result in operation of
the associated alarms. Consequently,
notification must first be given to the
owner and the fire department, central
station, or other signal station to which
the alarms are connected.
The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this docu-
ment, as well as with applicable stan-
dards of EN12845 in addition to the
standards of any authority having juris-
diction. Contact the installing contrac-
tor or product manufacturer with any
questions.
Some procedures in this section result
in the operation of the associated
alarms. Notify the owner and the fire
department, central station, or other
signal station to which the alarms are
connected before performing the tests.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Drop in Water Supply Pressure
Below Normal Range
NOTICE
If the water supply pressure is signif-
icantly reduced below the normally
expected static pressure range (as
could occur in the case of a water main
break or repair), and there is a subse-
quent drop in the diaphragm chamber
water pressure below its normal range
(for example, due to a leak in a piping
connection to or from the diaphragm
chamber or, a leak in the diaphragm
chamber check valve caused by dirt or
debris in the check valve seal area), a
valve such as the DV-5acould inadver-
tently trip, if its water supply pressure
is quickly restored.
A drop in the water supply pressure
to below its normal range (as in the
case of an interrupted water supply
condition) constitutes an emergency
impairment.
Should this condition occur, immedi-
ately close the main control valve and
use the following procedure to reset the
system:
Step 1. Prior to the water supply pres-
sure being restored to the closed
System Main Control Valve (B), note the
pressure indicated by the Diaphragm
Gauge (K) and determine if the pres-
sure is within the normally expected
range.
Step 2. If the diaphragm chamber pres-
sure is below the normal range, check
for and correct any source of leakage
from the diaphragm chamber prior to
resetting the system.
Step 3. After the water supply pres-
sure is restored to the System Main
Control Valve (B), reset the DV-5aValve
in accordance with the Valve Setting
Procedure section.
NOTICE
For fire protection systems subject to
an emergency impairment caused by
an interrupted water supply condition,
it is recommended that consideration
be given to installing a low water supply
pressure switch with the appropriate
alarm/indications to monitor the water
supply pressure.
Waterflow Alarm Test Procedure
To test the waterow alarm, open the
Alarm Test Valve (G), which will allow a
ow of water to the Waterow Pressure
Switch (C) and/or Water Motor Alarm.
Upon satisfactory completion of the
test, close the Alarm Test Valve (G).
To ensure drainage of the alarm line,
depress the plunger on the Automatic
Drain Valve (F).
Solenoid Valve
Test Procedure For
Electric Actuation
Proper operation of the Solenoid Valve
(R) for electric actuation must be veri-
ed at least quarterly as follows:
Step 1. Close the System Main Control
Valve (B).
Step 2. Open the Main Drain Valve (D).
Step 3. Test the deluge releasing panel
in accordance with the manufacturer’s
instructions to energize the Solenoid
Valve (R).
Step 4. Verify that there is a ow of
water from the Solenoid Valve (R) drain
connection.
Step 5. Verify that the Diaphragm
Chamber pressure has decreased
to below 25% of the water supply
pressure.
Step 6. Reset the electric detection
system in accordance with the manu-
facturer’s instructions to de-energize
the Solenoid Valve (R), and proceed as
follows:
• Water should cease draining from the
Solenoid Valve (R) but remain drain-
ing from the Manual Reset Actuator
(N).
• Press the Reset Knob on the Man-
ual Reset Actuator (N) and hold it a
few seconds until water stops ow-
ing from its drain tube.
• Pressure will then build up in the
DV-5A Diaphragm Chamber.
• After system pressure is restored
in the DV-5A Diaphragm Chamber,
inspect the Solenoid Valve (R) and
Manual Reset Actuator (N) for leaks
at the drain tube. Any leaks must be
corrected before proceeding to the
next step.
Step 7. Partially open the System Main
Control Valve (B). Slowly close the Main
Drain Valve (D) as soon as water dis-
charges from the Main Drain Valve (D).
Observe the Automatic Drain Valve
(F) for leaks. If there are leaks, deter-
mine/correct the cause of the leakage
problem. If there are no leaks, the
DV-5AValve is ready to be placed in
service and the System Main Control
Valve (B) must then be fully opened.
Solenoid Valve and
Dry Pilot Actuator Test Procedure
Proper operation of the Solenoid Valve
(S) and Dry Pilot Actuator (T) must be
veried at least quarterly as follows:
Step 1. Close the System Main Control
Valve (B).
Step 2. Open the Main Drain Valve (D).

TFP1485
Page 15 of 20
Step 3. Simulate power failure by dis-
connecting main power (circuit breaker)
to the releasing panel, and disconnect-
ing the battery back-up. Refer to the
releasing panel manufacturer's instruc-
tions for specic details. This step is
intended to allow the Solenoid Valve
(S) to open.
Step 4. Open the system's Inspector's
Test Connection to relieve system air
pressure.
Step 5. Verify that there is a ow of
water from the Dry Pilot Actuator (T)
drain connection.
Step 6. Verify that the Diaphragm
Chamber pressure has decreased
to below 25% of the water supply
pressure.
Step 7. Close the Inspector's Test Con-
nection and allow the system air pres-
sure to re-establish and proceed as
follows:
• Water should cease draining from
the Dry Pilot Actuator (T) but remain
draining from the Manual Reset Actu-
ator (N).
• Press the Reset Knob on the Man-
ual Reset Actuator (N) and hold it a
few seconds until water stops ow-
ing from its drain tube.
• Pressure will then build up in the
DV-5aDiaphragm Chamber.
• After system pressure is restored
in the DV-5aDiaphragm Chamber,
inspect the Solenoid Valve (R) and
Manual Reset Actuator (N) for leaks
at the drain tube. Any leaks must be
corrected before proceeding to the
next step.
Step 8. With reference to the releas-
ing panel manufacturer's instructions,
reestablish battery and main power to
the releasing panel.
Step 9. Partially open the System Main
Control Valve (B). Slowly close the Main
Drain Valve (D) as soon as water dis-
charges from the Main Drain Valve (D)
and then close the Main Drain Valve
(D). Observe the Automatic Drain Valve
(F) for leaks. If there are leaks, deter-
mine/correct the cause of the leakage
problem. If there are no leaks, the
DV-5aValve is ready to be placed in
service and the System Main Control
Valve (B) must then be fully opened.
Supervisory Low Pressure Alarm
Test Procedure and Validation
of the Normally Closed
Solenoid Valve (S)
Proper operation of the Supervisory
Low Pressure Alarm Switch and vali-
dation of the normally closed Solenoid
Valve (S) must be performed as follows:
Step 1. Close the System Main Control
Valve (B).
Step 2. Open the Main Drain Valve (D).
Step 3. Crack open the system's
Inspector's Test Connection to relieve
air pressure from the system. Verify that
the Supervisory Low Pressure Alarm
Switch (V) is operational and that the
low pressure set point is approximately
0,4 bar under the minimum system air
pressure.
Step 4. Allow the system air pressure
to decay to 0 psig (1,01 bar). Verify that
there is no water draining from the Dry
Pilot Actuator (T), as will be the case if
the Solenoid Valve (S) is in the normally
closed position.
Step 5. Close the system's Inspector's
Test Connection and allow the system
supervisory pressure to be automati-
cally re-established. As necessary,
open and then close the quick ll air
supply control valve in the automatic air
maintenance device. The Supervisory
Low Pressure Alarm Switch (V) should
return to its "normal" condition.
Step 6. Verify that the system air pres-
sure is returned to normal and the
DV-5adiaphragm chamber remains
pressurized as indicated by the Dia-
phragm Gauge (K).
Step 7. Partially open the System Main
Control Valve (B). Slowly close the Main
Drain Valve (D) as soon as water dis-
charges from the Main Drain Valve (D).
Observe the Automatic Drain Valve
(F) for leaks. If there are leaks, deter-
mine/correct the cause of the leakage
problem. If there are no leaks, the
DV-5aValve is ready to be placed in
service and the System Main Control
Valve (B) must then be fully opened.
Operation Test Procedure
Proper operation of the DV-5aValve
with Preaction Type A Trim (i.e., opening
of the DV-5aValve as during a re con-
dition) must be veried at least once a
year as follows:
If water must be prevented from owing
beyond the riser, perform the following
steps:
• Close the System Main Control Valve
(B).
• Open the Main Drain Valve(D).
• Open the System Main Control Valve
(B) one turn beyond the position at
which water just begins to ow from
the Main Drain Valve (D).
• Close the Main Drain Valve (D).
Step 1. Test the deluge releasing panel
in accordance with the manufacturer’s
instructions to energize the Solenoid
Valve (R).
NOTICE
Be prepared to perform Steps 2, 3, and
4 quickly if water must be prevented
from flowing beyond the riser.
Step 2. Verify that the DV-5aValve has
tripped, as indicated by the ow of
water into the system.
Step 3. Close the System Main Control
Valve (B).
Step 4. Close the Diaphragm Supply
Valve (P) and the Air Supply Control
Valves (X) and (Y).
Step 5. Reset the DV-5aValve with Pre-
action Type A Trim in accordance with
the Valve Setting Procedure.
Internal Valve Inspection
Once every ve years during the annual
operational test procedure and prior
to the DV-5aValve being reset and
with the DV-5aValve de-pressurized,
the interior of the DV-5aValve must
be cleaned and inspected for wear
and damage. Damaged or worn parts
must be replaced. (Replacement of the
Diaphragm every ten years is recom-
mended, or more frequently if inspec-
tions and/or wear and tear warrant
more frequent replacement.)
NOTICE
The Diaphragm Cover may be removed
between Steps 4 and 5 of the reset-
ting instructions, since at that point the
DV-5aValve should be de-pressurized
as evident by a zero gauge reading on
the Diaphragm Gauge (K) and Water
Supply Gauge (J), as well as no water
discharging from the Automatic Drain
Valve (F).
When reinstalling the Diaphragm Cover,
complete the following steps to assure
the Diaphragm Cover Fasteners are
uniformly and securely tightened.
To perform internal valve inspection
between Steps 4 and 5 of the Valve
Setting Procedure remove the Dia-
phragm cover as follows:
Step 1. Close the Inverted Flare Shut-
Off Valve (AA).
Step 2. Remove the Copper Tube
Fitting between the Diaphragm Supply
Valve (P) and the Inverted Flare Shut-
Off Valve (AA).
Step 3. Disconnect the conduit from
the Solenoid Valve (S).
Step 4. Loosen the nut securing the
copper piping to the tee connection
below the Air Supply Control Valve “B”
(Y).
Step 5. Remove the nut from the tting
located at the Air Supply Strainer (W).
Step 6. Loosen the union below the
Dry Pilot Actuator and below the Dia-
phragm Gauge (K).

TFP1485
Page 16 of 20
Step 7. Disassemble the union between
the Diaphragm Cover and the MRA-1
Manual Reset Actuator (N) and remove
the assembly.
Step 8. Remove the Diaphragm Valve
Cover hardware, then slowly remove
the Diaphragm Cover and perform
internal valve inspection. Clean the
valve interior and replace parts as
necessary.
After cleaning and inspecting valve
interior, and replacing parts as nec-
essary, reinstall the Diaphragm Cover
by completing the following steps to
assure the Diaphragm Cover Fasteners
are uniformly and securely tightened.
Step 1. Ensure that the Diaphragm is
properly oriented as shown in Figure 1,
and that the proper hardware arrange-
ment is utilized when assembling the
Diaphragm Covers. The hardware
arrangements differ depending on the
size of the DV-5A Valve.
Step 2. By rst using the Long Hex
Bolts, support of the Diaphragm Cover
will be provided before installing the
Short Hex Bolts. Align Diaphragm in
proper orientation with Valve Body, and
then align Diaphragm Cover in proper
orientation with Valve Body. Hand-
tighten all fasteners.
Step 3. Using crossdraw sequence
to assure uniformity, wrench-tighten
Long Hex Bolts and Short Hex Bolts
to appropriate torque values. Repeat
crossdraw sequence two to three
times at incremental torque valves
until reaching the torque valves found
in Table B.
Step 4. Inspect to assure all Hex Bolts
are securely tightened.
Step 5. Secure the assembly by reas-
sembling the union between the MRA-1
Manual Reset Actuator (N) to the Dia-
phragm Cover.
Step 6. Align the copper piping below
the Air Supply Strainer (W) and replace
the nut. Then tighten the nut located
below the Air Supply Control Valve “B”
(Y).
Step 7. Connect the conduit to the
Solenoid Valve (S).
Step 8. Replace the Copper Tube
Fitting between the Diaphragm Supply
Valve and the Inverted Flare Shut-Off
Valve (AA).
Step 9. Ensure that the unions and are
ttings are securely tightened.
Step 10. With the Diaphragm Supply
Valve (P) closed, fully open the Inverted
Flare Shut-Off Valve (AA) stainless
steel screw (approximately ½ in.) until
resistance is met so as not to break
the internal roll-pin. The internal roll-
pin stops the removal of the Inverted
Flare Shut-Off Valve (AA) stainless steel
screw.
Step 11. Proceed to Step 5 of the Valve
Setting Procedures section in this data
sheet.
NOTICE
If the water supply contains chemicals
which tend to attack a polyester fabric-
reinforced, EPDM rubber or the five year
inspection indicates a build-up of debris
within the DV-5aValve that could affect
its proper operation, then the frequency
of the internal valve inspection procedure
must be appropriately increased.
With reference to Figure 1, make
certain that the Diaphragm is correctly
oriented; otherwise, the DV-5aValve
cannot be properly set.
Under-tightening the Diaphragm Cover
Bolts can result in internal and external
leakage.
Use only TYCO replacement fasteners
as specified in Figure 1.
Do not apply adhesives, lubricants, or
other substances to the Diaphragm
Valve Body.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-re.com.
Ordering
Procedure
The TYCO DV-5aAutomatic Water
Control Valves may be ordered as
follows:
Pre-Assembled Ordering
DV-5
A
Valves with Galvanized Valve
Trim
Specify: Size (specify), DV-5aAuto-
matic Water Control Valve, (specify)
end connection with assembled galva-
nized (EMEA or APAC) Preaction Type
A Valve Trim, P/N (See Table C)
Separate Parts Ordering
DV-5
A
Valves
For ange drilling specications, see
Table A
Specify: Size (specify), DV-5aAuto-
matic Water Control Valve, (specify)
end connection, P/N (See Table D)
DV-5
A
Valve Trim
Specify: Size (specify), nish (specify),
(specify) Preaction Type A Valve Trim
for DV-5aAutomatic Water Control
Valves used in Preaction Type A Fire
Protection System, P/N (See Table E)
DV-5
A
Valve Trim Accessories
(for separately ordered valve trim)
See Table F for separately ordered
accessories not included with the Valve
Trim.
DV-5
A
Valve Replacement Parts
Specify: (Description) for use with
(specify size) DV-5aAutomatic Water
Control Valve, P/N (See Figure 1)
DV-5
A
Valve Trim Replacement
Parts
Specify: (Description) for use with
DV-5aValve Trim, P/N (See Figure 6)
Nominal
Valve Sizes
ANSI
Inches
(DN)
Torque
lb-ft
(N∙m)
Nuts Short
Hex
Bolts
1 1/2
(40)
44
(59,7)
35
(47,5)
2
(50)
44
(59,7)
35
(47,5)
3
(80)
125
(169,5)
125
(169,5)
4
(100)
150
(203,4)
150
(203,4)
61
(150)
150
(203,4)
150
(203,4)
8
(200)
188
(254,9)
188
(254,9)
NOTES
1. Also applicable to metric 165,1 mm size.
TABLE B
DIAPHRAGM COVER BOLTS
MINIMUM TORQUE

TFP1485
Page 17 of 20
NOTES
1. EMEA DV-5
A
Valve with Trim: EMEA pressure switches, P/N 52-287-1-124 solenoid valve, P/N 1001295 solenoid valve, bar/psi water pressure gauges,
and NPT to ISO threaded trim adaptors for external connections are provided.
2. APAC DV-5
A
Valve with Trim: APAC pressure switches, P/N 52-287-1-124 solenoid valve, P/N 1001295 solenoid valve, and psi/kPa water pressure
gauges are provided.
EMEA1APAC2
G x G Valve Size
1-1/2 in. (DN40) 55 0111615 5 50011615
2 in. (DN50) 55 0111620 5 50011620
3 in. (DN80) 550111630 550 0116 30
4 in. (DN100) 550111640 550 011640
6 in. (DN150) 55 01116 6 0 550011660
165,1 mm 55 01116 6 6 550011666
8 in. (DN200) 55 01116 8 0 550011680
F x F ANSI Valve Size
3 in. (DN80) 550121630 550021630
4 in. (DN100) 550121640 550021640
6 in. (DN150) 550121660 550021660
8 in. (DN200) 550121680 550021680
F x G ANSI Valve Size
3 in. (DN80) 550131630 550031630
4 in. (DN100) 550131640 550031640
6 in. (DN150) 550131660 550031660
8 in. (DN200) 550131680 550031680
F x F ISO Valve Size
3 in. (DN80) 550141630 550041630
4 in. (DN100) 550141640 550041640
6 in. (DN150) 550141660 550041660
8 in. (DN200) 550141680 550041680
F x G ISO Valve Size
3 in. (DN80) 550151630 550051630
4 in. (DN100) 550151640 550051640
6 in. (DN150) 550151660 550051660
8 in. (DN200) 550151680 550051680
T x T ISO Valve Size
1-1/2 in. (DN40) 550171615 550061615
2 in. (DN50) 550171620 550061620
TABLE C
DV-5AVALVES WITH GALVANIZED VALVE TRIM
PART NUMBER SELECTION
— PREACTION TYPE A SYSTEM —

TFP1485
Page 18 of 20
NOTES
1. EMEA Valve Trim: Pressure switches, solenoid valves for electric actuation, water pressure gauges, and BFV-300 Buttery Valve are separately ordered.
NPT to ISO threaded adaptors are provided for External Trim Connections (drains, pressure switches, water motor alarms, etc.).
2. APAC Valve Trim: Pressure switches and/or solenoid valves for electric actuation are separately ordered.
3. Also applicable to metric 165,1 mm size.
REGIONS OF TYPICAL AVAILABILITY (indicated by “X”)
AMERICAS ———————
EMEA ✔ ✔ ✔ ✔ ✔ ✔ ✔
APAC ✔ ✔ ✔ ✔ ✔ ✔ ✔
Valve Size Nominal Groove
O.D. G x G F x F ANSI F x G ANSI T x T NPT F x F ISO F x G ISO T x T ISO
1-1/2 in. (DN40) 1.990 in. (50,5 mm) 530010015 — — 530060015 — — 530070015
2 in. (DN50) 2.375 in. (60,3 mm) 530010020 — — 530060020 — — 530070020
3 in. (DN80) 3.500 in. (88,9 mm) 530010030 530020030 530030030 —530040030 530050030 —
4 in. (DN100) 4.500 in. (114,3 mm) 530010040 530020040 530030040 —530040040 530050040 —
6 in. (DN150) 6.625 in. (168,3 mm) 530010060 530020060 530030060 —530040060 530050060 —
165,1 mm 6.625 in. (165,1 mm) 530010066 — — — — — —
8 in. (DN200) 8.625 in. (219,1 mm) 530010080 530020080 530030080 —530040080 530050080 —
NOTES
a. Valves are typically provided with ange drilling per ANSI B16.1 (Class 125) or ISO (7005-2 PN16).
b. Upon request, valves can be provided with ange drilling per JIS B 2210 or AS 2129. In which case part numbers are not assigned.
Valve Size EMEA Galvanized1EMEA Black1
1-1/2 in. (DN40) 540101620 542101620
2 in. (DN50) 540101620 542101620
3 in. (DN80) 540101630 542101630
4 in. (DN100) 540101640 542101640
6 in. (DN150)3540101660 542101660
8 in. (DN200) 540101680 542101680
Valve Size APAC Galvanized2APAC Black2
1-1/2 in. (DN40) 540001620 542001620
2 in. (DN50) 540001620 542001620
3 in. (DN80) 540001630 542001630
4 in. (DN100) 540001640 542001640
6 in. (DN150)3540001660 542001660
8 in. (DN200) 540001680 542001680
TABLE D
DV-5AVALVES PART NUMBER SELECTION
TABLE E
DV-5AVALVE TRIM
PART NUMBER SELECTION
— PREACTION TYPE A SYSTEM —

TFP1485
Page 19 of 20
ACCESSORIES, DELUGE FIRE PROTECTION SYSTEMS P/N Data
Sheet
Waterow Pressure Alarm Switch (APAC) 25710 or 100102 —
Waterow Pressure Alarm Switch (EMEA) 0260 —
Air Pressure Alarm Switch (APAC) 25730 or 100402 —
Air Pressure Alarm Switch (EMEA) 0262 —
Model AMD-1 Air Maintenance Device 523242002 TFP1221
Model AMD-2 Air Maintenance Device 523262001 TFP1231
Model AMD-3 Nitrogen Maintenance Device 523282001 TFP1241
Water Gauges with bar/psi 025500013 —
N.C. De-energized Solenoid Valve for Releasing Service 522871124 TFP2180
N.O. De-energized Solenoid Valve for Releasing Service 2191866 TFP2180
600 psi Water Gauge psi/kPa (service pressure over 300 psi) 923431004 —
TABLE F
DV-5AVALVES TRIM ACCESSORIES
PART NUMBER SELECTION
— PREACTION TYPE A SYSTEM —

TFP1485
Page 20 of 20
TEFLON is a trademark of The Chemours Company FC, LLC
1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Other manuals for DV-5A
13
Table of contents
Other Tyco Control Unit manuals
Popular Control Unit manuals by other brands

GEZE
GEZE Slimdrive SD Auxiliary installation instructions

Espressif
Espressif PAN100 manual

Bray
Bray 752 Series Installation, operation and maintenance manual

SMC Networks
SMC Networks VQZ 1000 Installation and maintenance manual

Eaton
Eaton Crouse-hinds series instruction sheet

Stacore
Stacore ADVANCED user manual