Tyco DV-5 User manual

DV-5 Preaction Type A Valve
EN12845 Compliance
Page 1 of 16 AUGUST 2018 TFP1484
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
General
Description
Fire protection systems controlled by
the TYCO DV-5 Preaction Type A Valve
utilize automatic sprinklers and a sup-
plemental detection system. The sup-
plemental detection system is typically
comprised of 24 VDC heat detectors,
smoke detectors, and manual pull sta-
tions. Actuation of the detection system
automatically operates (releases) the
DV-5 Deluge Valve, allowing water to
flow into the sprinkler piping system
and to be discharged from any sprin-
klers that may subsequently open. In
the event of loss of power, the DV-5
Deluge Valve with Preaction Type A
Trim will act as a regular dry-pipe valve
station. The Preaction Type A assembly
is rated for a maximum service pres-
sure of 16 bar.
These DV-5 Preaction Type A Valves
have been designed in accordance with
the EN12845 Standard describing Pre-
action Type A Trim criteria. This stan-
dard defines operation as a dry pipe
system activated by an automatic fire
detection system but not operation of
sprinklers.
Typically, the system designer selects
detection components for the DV-5
Preaction Type A Valves that will
respond to a fire sooner than the auto-
matic sprinklers. Consequently, the
system will experience a minimal delay
in water delivery over that for a wet pipe
sprinkler system because the system
will have begun to fill with water before
a sprinkler operates. Preaction Type A
systems will need to be designed as
wet pipe systems or according to the
local authority having jurisdiction.
DV-5 Preaction Type A Valves are gen-
erally used to protect areas where there
is danger of serious water damage that
might result from damaged automatic
sprinklers or piping. Typically, such
areas include computer rooms, storage
areas for valuable artifacts, libraries,
and archives.
DV-5 Preaction Type A Valves are also
effectively used to protect properties
where a pre-alarm of a possible fire
condition may allow time for fire extin-
guishment by alternate suppression
means, prior to a sprinkler discharge.
In the event the fire cannot otherwise
be extinguished, the preaction sprinkler
system will then perform as the primary
fire protection system.
DV-5 Deluge Valve
The DV-5 Deluge Valve (Ref. Figure 1), is
a diaphragm-style valve that depends
upon water pressure in the Diaphragm
Chamber to hold the Diaphragm
closed against the water supply pres-
sure. When the DV-5 Preaction Type A
Valve is set for service, the Diaphragm
Chamber is pressurized through the
trim connections from the inlet side of
the system Main Control Valve, such as
an OS&Y gate valve or butterfly valve
(Ref. Figure 6). Refer to Technical Data
Sheet TFP1305 for more DV-5 Deluge
Valve details.
Riser Check Valve
In a DV-5 Preaction Type A Valve, a
Model CV-1FR Riser Check Valve (Ref.
Figure 2), which does not require the
use of priming water, provides an air
check so that the system can be auto-
matically pressurized with a nominal
supervisory air or nitrogen pressure
(Ref. Graph B). A supervisory low/high
pressure alarm switch that is set to
transfer its contacts at nominally 0,7
bar, on decreasing pressure, is uti-
lized to indicate whether there are any
abnormal leaks in the sprinkler system
piping. Loss of air pressure from the
system as a result of a damaged sprin-
OBSOLETE

TFP1484
Page 2 of 16
kler or broken piping will not cause the
DV-5 Valve to open since the air pres-
sure is for supervisory alarm only.
Detection System
Operation of an electrical detection
device such as a heat-sensitive ther-
mostat or smoke detector signals the
deluge valve releasing panel to ener-
gize the Solenoid Valve. In turn, the
energized Solenoid Valve opens to
release water from the Diaphragm
Chamber faster than it can be replen-
ished through the restriction provided
in the diaphragm supply connec-
tion. This release of water results in a
rapid pressure drop in the Diaphragm
Chamber to below the valve trip point.
The water supply pressure then forces
the Diaphragm open, permitting water
to flow into the system piping, as well
as through the Alarm Port to actuate
the system alarms.
In the event of a fault in the fire detec-
tion system, the installation shall
operate as an ordinary dry pipe system,
which means the energized-to-close
Solenoid Valve in the actuation loop
will open. As soon as a sprinkler oper-
ates/activates, the subsequent drop in
air pressure opens the Dry Pilot Actua-
tor. Water from the diaphragm pressure
piping will exit the Dry Pilot Actuator
through this drain, resulting in the acti-
vation of the DV-5 Deluge Valve.
Fail-Safe Valve
As water flows into the system, pres-
surization of the pilot chamber opens
the Model FSV-1 Fail-Safe Valve. With
the Model FSV-1 Valve open, make-up
pressure to the diaphragm chamber of
the DV-5 Valve cannot occur, thereby
preventing inadvertent closing of the
DV-5 Valve during a fire, as may be
the case should the Solenoid Valve
become de-energized after its initial
operation. Refer to Technical Data
Sheet TFP1386 for more Model FSV-1
Fail Safe Valve details.
Dry Pilot Actuator
In the case of dry pilot actuation, air
pressure is released from the system
piping due to the opening of an auto-
matic sprinkler. When actuated by this
event, the Model DP-1 Dry Pilot permits
the release of water pressure from the
deluge valve differential chamber,
thereby allowing the DV-5 Deluge Valve
to open. Refer to Technical Data Sheet
TFP1380 for more Model DP-1 Dry Pilot
Actuator details.
NOTICE
The DV-5 Preaction Type A Valves
described herein must be installed
and maintained in compliance with
this document, as well as with the
EN12825 installation standard of pre-
action systems, in addition to the stan-
dards of any other authorities having
jurisdiction. Failure to do so may impair
the performance of the related devices.
Owners are responsible for maintaining
their fire protection system and devices
in proper operating condition. Contact
the installing contractor or product
manufacturer with any questions.
Technical
Data
Approvals
Sizes DN100 and DN150 are VdS
Approved and have been designed in
accordance with EN12845.
For more information on approvals,
contact Johnson Controls at the fol-
lowing office:
Kopersteden 1
7547 TJ Enschede
The Netherlands
Tel: +31-(0)53-428-4444
Fax: +31-(0)53-428-3377
Nominal Sizes
DN40 thru DN200
Deluge Valve
DV-5
Riser Check Valve
Model CV-1FR
DN40 risers utilize a DN50 Riser Check
valve in combination with the DN40
DV-5 Deluge Valve.
Valve Trim
The trim arrangement is provided with
galvanized fittings. The galvanized trim
is intended for non-corrosive or corro-
sive conditions.
Maximum Service Pressure
16 bar
Detection System
In order for DV-5 Preaction Type A
Valves to be hydraulically calculated
as a wet pipe system, the detection
system must be designed to operate
sooner than the automatic sprinklers on
the sprinkler piping.
DV-5 Preaction Type A Valve provides
for electric operation of the DV-5 Valve
by a detection system consisting of
electrical devices such as heat sen-
sitive thermostats, smoke detectors,
and/or manual pull stations. Nominal
installation dimensions for the Pre-
action Type A Trim configuration are
shown in Figure 4.
NOTICE
Consult with the authority having juris-
diction regarding installation criteria
pertaining to electric actuation circuitry.
System Air Pressure
Requirements
The DV-5 Preaction Type A Valve
includes a Model DP-1 Dry Pilot Actu-
ator, an auxiliary releasing device. The
Model DP-1 Valve actuates control
valves upon release of air (or nitrogen)
pressure (Ref. TFP1380).
The air (or nitrogen) pressure in the
sprinkler system is recommended to
be automatically maintained using one
of the following pressure maintenance
devices, as appropriate:
• an air supply in combination with
Model AMD-1 Air Maintenance
Device (pressure-reducing type)
described in TFP1221
• an air supply in combination with
Model AMD-2 Air Maintenance
Device (compressor-control type)
described in TFP1231
• a nitrogen cylinder in combination
with Model AMD-3 Nitrogen Mainte-
nance Device (high pressure-reduc-
ing type) described in TFP1241
• the minimum system supply pressure
is 3,0 bar
NOTICE
The dew point of the air or nitrogen
supply for a system exposed to freez-
ing conditions must be maintained
below the lowest ambient tempera-
ture to which the system piping will be
exposed. Introduction of moisture into
the system piping can create ice build-
up which could prevent proper opera-
tion of the system.
The Supervisory Low/High Pressure
Alarm Switch (Ref. Figures 3, 5 and 6)
is factory set for 2,8 bar normal system
pressure. The low pressure alarm is set
to operate at a pressure decrease of
0,7 bar at 2,1 bar.
The high pressure alarm is set to
operate at a pressure increase of 0,7
bar at 3,5 bar. The Pressure Relief Valve
(Ref. Figure 3) is factory set to fully
open at 3,1 bar plus or minus 0,14 bar.
Friction Loss
The nominal pressure loss versus
flow data for the DV-5 Deluge Valve
plus Riser Check Valve is provided in
Graph A.
OBSOLETE

TFP1484
Page 3 of 16
Detail Part Material Qty.
1Body Ductile
Iron 1
2Cover Ductile
Iron 1
3Cover
Gasket
Nitrile
Rubber 1
4Hex Cap
Screw
Steel, Zinc
Plated AR
5Clapper Stainless
Steel 1
Detail Part Material Qty.
6Clapper
Facing
EPDM
Grade “E” 1
7Spring Stainless
Steel 1
8Hinge
Shaft
Stainless
Steel 1
9Retaining
Ring
Stainless
Steel AR
11 Retention
Bolt
Stainless
Steel 1
Detail Part Material Qty.
13 Retaining
Disc
Stainless
Steel 1
14 Locknut Stainless
Steel 1
15 Adhesive Thread
Sealer AR
16 Nameplate Aluminum 1
17 Rivet Steel 2
1
Qty.
1
1
4
4
8
8
2
2
4
4
6
6
6
. . . . . . .
. . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . .
. . . . . . . . . .
. . . . . . . . . .
. . . . . . . . . .
. . . . . . . . . .
4
1
2
3
(a)
6
5
Diaphragm Cover NR
Flat Washer:
No. Description Repair Parts
(a)
Valve Body
Diaphragm
NR
VALVE PARTS
DN40 Valve,
M12 CH
DN50 & DN80 Valve,
M16
DN100 & DN150 Valve,
CH
M16
DN200 Valve,
M20
CH
CH
No. Description P/N
REPLACEMENT PARTS
Diaphragm Kit,
92-477-1-105DN40 Valve
92-477-1-107DN50 Valve
92-477-1-109DN80 Valve
92-477-1-101DN100 Valve
DN150 Valve 92-477-1-103
DN200 Valve 92-477-1-111
Includes Item 2:
Hex Nut:
DN100 & DN150 Valve,
M16 CH
DN200 Valve,
M20 CH
Hex Bolt:
DN40 Valve,
M12 x 30 mm CH
DN50 & DN80 Valve,
M16 x 50 mm
DN100 Valve,
CH
M16 x 50 mm
DN150 Valve,
CH
M16 x 55 mm
DN200 Valve,
CH
M20 x 70 mm CH
ORIENT
DIAPHRAGM TAB
PERPENDICULAR
TO VALVE BODY
CENTERLINE
DIAPHRAGM
ORIENTATION
TAB
6
(NOTE 3)
STUDS
(NOTE 3)
2
(NOTE 4)
V-RING
(NOTE 4)
4
3
5
1
4
1.
2.
3.
4.
Valve Bodies of DN100, DN150 & DN200
valves are equipped with studs and Valve
Covers are secured by Hex Nuts and Hex
Bolts.
NOTES:
V-Ring is attached to Diaphragm of DN100,
DN150 & DN200 valves at factory. If, during
internal valve inspection, V-Ring is
discovered to be detached from Diaphragm,
be advised that V-Ring is a required valve
component and that detachment will not
affect normal valve operation or
performance. Should V-Ring become
detached, reinstall between Diaphragm
and Diaphragm Cover concentrically as
shown.
NR - Not Replaceable
CH - Common Hardware
NOTE: Do not apply adhesives, lubricants,
or other substances to Diaphragm, V-Ring,
or Valve Body.
DETAIL B
SEE
1
VIEW A
SEE
16
17
3
2
4,15
2
9
8
7
5
13
14,15
6
5
11
DETAIL B
VIEW A
FIGURE 1
DV-5 VALVE ASSEMBLY
FIGURE 2
MODEL CV-1FR CHECK VALVE ASSEMBLY
OBSOLETE

TFP1484
Page 4 of 16
1
1
3
1
1
4
2
1
2
3
1
1
1
1
1
1
3
1
1
5
1
1
1
1
1
1
2
2
3
5
3
1
4
4
1
1
2
2
1
6
5
2
2
5
5
1
2
1
6
1
2
2
2
2
5
3
5
1
2
QTY QTY
. . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
51
56
59
58
57
54
55
53
52
46
49
50
48
47
41
45
44
43
42
37
36
40
39
38
35
34
NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
NO.
Deluge Valve, DV-5, 1-1/2" - DN40, ISO Ports;
Reducing Coupling, Figure 716, 2" x 1-1/2" - DN50 x DN40;
Riser Check Valve, Model CV-1FR, 2" - DN50;
Reducing Tee, 1" x 3/4" x 1/2"; P/N A130RFDE2
Plug, 3/4"; P/N A291E2
Pipe Nipple, 1" x 80mm; P/N AP80F2
Angle Valve, 3/4"; P/N 126S00270D
Pipe Nipple, 3/4" x 100mm; P/N AP100E2
Pipe Nipple, 1/2" x 40mm; P/N AP40D2
Reducer, DN20 x DN15; P/N RTEDMN
Pipe Nipple, 1/2" x 160mm; P/N AP160D2
Pipe Nipple, 1/2" x 250mm; P/N AP250D2
Pipe Nipple, 1/2" x 70mm; P/N AP70D2
Tube, 15 x 1mm, 550 x 400mm; P/N WS00000124
Tube, 15 x 1mm, 370 x 225mm; P/N WS00000096
Pipe, 10 x 12mm, 900mm; P/N WS00000007
Hose, 3 x 6mm, 1.2m; P/N WS00000004
Check Valve, 1/2" NPT; P/N V923221002
Union, DN15 x DN15; P/N UTDMDFN
Tee, DN20 x DN20 x DN20; P/N TTEMEEFN
Tee, DN20 x DN20 x DN20; P/N TTEEEFN
Tee, DN15 x DN15 x DN15; P/N TTDMDFDMN
Tee, DN15 x DN15 x DN15; P/N TTDMDDFN
Tee, DN15 x DN15 x DN15; P/N TTDDMDFN
Tee, DN15; P/N TTDDDFN
Adapter, DN15 x DN15; P/N STDDFN
Reducer, DN20 x DN15; P/N RTEMDFN
Reducer, DN15 x DN8; P/N RTDMBFN
Elbow, DN15 x DN15; P/N ETDMDFN
Elbow, DN15 x DN15; P/N ETDDMN
Elbow, DN15 x DN15; P/N ETDDFN
Adapter, DN20 x DN20; P/N ATEEMN
Compression Fitting, DN15 x 15mm; P/N ATDMCON
Pipe Nipple, 1/2" x 90mm; P/N AP90D2
Pipe Nipple, 3/4" x 80mm; P/N AP80E2
Pipe Nipple, 1/2" x 80mm; P/N AP80D2
Pipe Nipple, 1/2" x 60mm; P/N AP60D2
Pipe Nipple, 1/2" x 50mm; P/N AP50D2
Plug, 1/4"; P/N A290B2
Pressure Relief Valve, 1/4"; P/N 923431020
Air Pressure Gauge, 250 PSI; P/N 923431012
Tube Connector, 1/2" x 12mm; P/N 81900211
Restriction, 3mm Orice, 1/2" x 1/2"; P/N 700485
Ball Valve, DN15, Venthole M5; P/N 59304FO
Fail Safe Valve, Model FSV-1; P/N 523431001
Break Station, Model MC-1; P/N 522892001
Solenoid Valve, 24 VDC, 1/2" NPT, 20-250 PSI / 1.4-17.2 bar;
Dry Pilot Actuator, Model B-1; P/N 522801001
Check Valve, Swing Type, 3/4"; P/N 460491005
Check Valve, Swing Type, 1/2"; P/N 460491004D
Elbow, WES 3mm x M5; P/N 406012
Solenoid Valve, 24 VDC, 1/2" NPT, 0.2 - 16 bar;
Drain Valve, Self-Closing, 1/2" NPT; P/N 2162156
Strainer, 1/2" NPT; P/N 20005025
Ball Valve, DN20; P/N 1610000270
Ball Valve, DN15; P/N 1610000210
Pressure Switch, Model PS40-2; P/N 0263
Pressure Switch, Model PS10-2; P/N 0261
Water Pressure Gauge, 300 PSI; P/N 025500013
DESCRIPTION DESCRIPTION
P/N 524771919
P/N 716AE20151
P/N 595901020
P/N 522871124P
P/N 2191866
39
34
34
31
6
5
27
53
30
10
12
40
6
55
18
45
48
21
53
26 19 21
17
44
27 338 17
12
38
6
338
31
9
19
21
56 23
35
24
1
29 51
28 13 56
25
12 28
50 16
42
338 55 17
20
33
9
47
59
17
6
11
4
22
38
3
19
27
46
54
7
824
32
14
10
21
58
19
8
7
16
15
59
29
12
31
25
19
29
12
32
54
2
3
49
12
10
18
57
21
10 27
55
50
37
16
42
4
16
36
28
41
20
2
21
55
29 43
50
10
16
17
452 15
59
42
FIGURE 3 (1 OF 6)
DN40 DV-5 PREACTION TYPE A TRIM ASSEMBLY
EXPLODED VIEW
OBSOLETE

TFP1484
Page 5 of 16
3
4
3
1
1
1
2
2
1
1
1
1
1
1
1
1
1
3
1
1
1
1
5
1
1
2
2
1
1
2
5
3
1
4
4
1
1
2
2
1
6
5
2
2
5
5
1
2
1
6
1
2
2
2
2
5
3
5
1
2
QTY QTY
. . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . .
51
56
60
59
58
57
55
54
52
53
50
49
47
48
46
45
44
42
43
41
38
40
39
37
36
35
34
NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
NO.
Deluge Valve, DV-5, 2" - DN50, ISO Ports;
Rigid Coupling, Figure 577, 2" - DN50; P/N 577ME00601
Riser Check Valve, Model CV-1FR, 2" - DN50;
Reducing Tee, 1" x 3/4" x 1/2"; P/N A130RFDE2
Plug, 3/4"; P/N A291E2
Pipe Nipple, 1" x 80mm; P/N AP80F2
Angle Valve, 3/4"; P/N 126S00270D
Pipe Nipple, 1/2" x 150mm; P/N AP150D2
Pipe Nipple, 1/2" x 40mm; P/N AP40D2
Reducer, DN20 x DN15; P/N RTEDMN
Pipe Nipple, 1/2" x 160mm; P/N AP160D2
Pipe Nipple, 3/4" x 100mm; P/N AP100E2
Pipe Nipple, 1/2" x 250mm; P/N AP250D2
Pipe Nipple, 1/2" x 70mm; P/N AP70D2
Tube, 15 x 1mm, 550 x 400mm; P/N WS00000124
Tube, 15 x 1mm, 370 x 225mm; P/N WS00000096
Pipe, 10 x 12mm, 900mm; P/N WS00000007
Hose, 3 x 6mm, 1.2m; P/N WS00000004
Check Valve, 1/2" NPT; P/N V923221002
Union, DN15 x DN15; P/N UTDMDFN
Tee, DN20 x DN20 x DN20; P/N TTEMEEFN
Tee, DN20 x DN20 x DN20; P/N TTEEEFN
Tee, DN15 x DN15 x DN15; P/N TTDMDFDMN
Tee, DN15 x DN15 x DN15; P/N TTDMDDFN
Tee, DN15 x DN15 x DN15; P/N TTDDMDFN
Tee, DN15; P/N TTDDDFN
Adapter, DN15 x DN15; P/N STDDFN
Reducer, DN20 x DN15; P/N RTEMDFN
Reducer, DN15 x DN8; P/N RTDMBFN
Elbow, DN15 x DN15; P/N ETDMDFN
Elbow, DN15 x DN15; P/N ETDDMN
Elbow, DN15 x DN15; P/N ETDDFN
Adapter, DN20 x DN20; P/N ATEEMN
Compression Fitting, DN15 x 15mm; P/N ATDMCON
Pipe Nipple, 1/2" x 90mm; P/N AP90D2
Pipe Nipple, 3/4" x 80mm; P/N AP80E2
Pipe Nipple, 1/2" x 80mm; P/N AP80D2
Pipe Nipple, 1/2" x 60mm; P/N AP60D2
Pipe Nipple, 1/2" x 50mm; P/N AP50D2
Plug, 1/4"; P/N A290B2
Pressure Relief Valve, 1/4"; P/N 923431020
Air Pressure Gauge, 250 PSI; P/N 923431012
Tube Connector, 1/2" x 12mm; P/N 81900211
Restriction, 3mm Orice, 1/2" x 1/2"; P/N 700485
Ball Valve, DN15, Venthole M5; P/N 59304FO
Fail Safe Valve, Model FSV-1; P/N 523431001
Break Station, Model MC-1; P/N 522892001
Solenoid Valve, 24 VDC, 1/2" NPT, 20-250 PSI / 1.4-17.2 bar;
Dry Pilot Actuator, Model B-1; P/N 522801001
Check Valve, Swing Type, 3/4"; P/N 460491005
Check Valve, Swing Type, 1/2"; P/N 460491004D
Elbow, WES 3mm x M5; P/N 406012
Solenoid Valve, 24 VDC, 1/2" NPT, 0.2 - 16 bar;
Drain Valve, Self-Closing, 1/2" NPT; P/N 2162156
Strainer, 1/2" NPT; P/N 20005025
Ball Valve, DN20; P/N 1610000270
Ball Valve, DN15; P/N 1610000210
Pressure Switch, Model PS40-2; P/N 0263
Pressure Switch, Model PS10-2; P/N 0261
Water Pressure Gauge, 300 PSI; P/N 025500013
DESCRIPTION DESCRIPTION
P/N 524771910
P/N 595901020
P/N 522871124P
P/N 2191866
44
43
35
35
31
6
5
27
54
30
10
12
40
6
51
10
16
17 56
18
4
46
49
21
54
26 19 21
17
45
27 339 17
12
39
6
339
31
9
19
21
57 23
36
24
1
29 52
28 13 56
25
12 28
51 16
42
339 56 17
20
34
9
48
60
17
6
11
4
22
39
3
19
27
47
55
7
824
33
14
10
21
59
19
8
7
16
15
60
29
12
32
25
19
29
12
42
33
60
55
2
3
50
12
10
18
58
21
10 27
56
51
38
16
42
4
16
37
28
41
20
2
21
56
29
53 15
FIGURE 3 (2 OF 6)
DN50 DV-5 PREACTION TYPE A TRIM ASSEMBLY
EXPLODED VIEW
OBSOLETE

TFP1484
Page 6 of 16
2
1
3
1
1
4
1
2
2
1
1
3
1
1
1
1
1
1
1
3
5
1
1
1
1
2
1
1
2
1
1
1
6
2
1
2
4
1
1
6
1
5
1
2
5
5
2
1
5
1
1
2
6
2
2
5
3
2
5
2
1
QTY QTY
. . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
NO.
Deluge Valve, DV-5, 3" - DN80, ISO Ports;
Rigid Coupling, Figure 577, 3" - DN80; P/N 577ME00891
Riser Check Valve, Model CV-1FR, 3" - DN80;
Reducing Tee, 1-1/4" x 1-1/4" x 1/2"; P/N A130RGDG2
Plug, 1-1/4"; P/N A291G2
Pipe Nipple, 1/2" x 40mm; P/N AP40D2
Pipe Nipple, 1-1/4" x 80mm; P/N AP80G2
Angle Valve, 1-1/4"; P/N 126S00420D
Reducer, DN20 x DN15; P/N RTEDMN
Pipe Nipple, 1/2" x 160mm; P/N AP160D2
Pipe Nipple, 3/4" x 100mm; P/N AP100E2
Pipe Nipple, 1/2" x 250mm; P/N AP250D2
Pipe Nipple, 1/2" x 70mm; P/N AP70D2
Tube, 15 x 1mm, 550 x 400mm; P/N WS00000124
Tube, 15 x 1mm, 370 x 225mm; P/N WS00000096
Pipe, 10 x 12mm, 900mm; P/N WS00000007
Hose, 3 x 6mm, 1.2m; P/N WS00000004
Check Valve, 1/2" NPT; P/N V923221002
Union, DN15 x DN15; P/N UTDMDFN
Tee, DN20 x DN20 x DN20; P/N TTEMEEFN
Tee, DN20 x DN20 x DN20; P/N TTEEEFN
Tee, DN15 x DN15 x DN15; P/N TTDMDFDMN
Tee, DN15 x DN15 x DN15; P/N TTDMDDFN
Tee, DN15 x DN15 x DN15; P/N TTDDMDFN
Tee, DN15; P/N TTDDDFN
Adapter, DN15 x DN15; P/N STDDFN
Reducer, DN20 x DN15; P/N RTFEMN
Reducer, DN20 x DN15; P/N RTEMDFN
Reducer, DN15 x DN8; P/N RTDMBFN
Elbow, DN15 x DN15; P/N ETDMDFN
Elbow, DN15 x DN15; P/N ETDDMN
Elbow, DN15 x DN15; P/N ETDDFN
Adapter, DN20 x DN20; P/N ATEEMN
Compression Fitting, DN15 x 15mm; P/N ATDMCON
Pipe Nipple, 1/2" x 90mm; P/N AP90D2
Pipe Nipple, 3/4" x 80mm; P/N AP80E2
Pipe Nipple, 1/2" x 80mm; P/N AP80D2
Pipe Nipple, 1/2" x 60mm; P/N AP60D2
Pipe Nipple, 1/2" x 50mm; P/N AP50D2
Pipe Nipple, 1/2" x 120mm; P/N AP120D2
Plug, 1/4"; P/N A290B2
Pressure Relief Valve, 1/4"; P/N 923431020
Air Pressure Gauge, 250 PSI; P/N 923431012
Tube Connector, 1/2" x 12mm; P/N 81900211
Restriction, 3mm Orice, 1/2" x 1/2"; P/N 700485
Ball Valve, DN15, Venthole M5; P/N 59304FO
Fail Safe Valve, Model FSV-1; P/N 523431001
Break Station, Model MC-1; P/N 522892001
Solenoid Valve, 24 VDC, 1/2" NPT, 20-250 PSI / 1.4-17.2 bar;
Dry Pilot Actuator, Model B-1; P/N 522801001
Check Valve, Swing Type, 3/4"; P/N 460491005
Check Valve, Swing Type, 1/2"; P/N 460491004D
Elbow, WES 3mm x M5; P/N 406012
Solenoid Valve, 24 VDC, 1/2" NPT, 0.2 - 16 bar;
Drain Valve, Self-Closing, 1/2" NPT; P/N 2162156
Strainer, 1/2" NPT; P/N 20005025
Ball Valve, DN20; P/N 1610000270
Ball Valve, DN15; P/N 1610000210
Pressure Switch, Model PS40-2; P/N 0263
Pressure Switch, Model PS10-2; P/N 0261
Water Pressure Gauge, 300 PSI; P/N 025500013
DESCRIPTION DESCRIPTION
P/N 524771922
P/N 595901030
P/N 522871124P
P/N 2191866
32
45
35
45
42
6
5
2
22 28
26
55
31
10
12
41
6
52
10
17
18
57
19
4
47
50
22
55
27 20 22
18
46
28 340 18
12
40
6
340
32
9
20
22
58 24
37
24
36
36
1
30 53
29 13 56
26
12 29
52 17
44
340 57 18
21
14
9
49
61
18
6
11
4
23
40
3
20
28
48
56
7
54
15
825
56
34
15
10
22
60
57
20
8
7
17
16
61
28
10
33
26
20
28
12
43
34
26
61
23
51
12
10
19
59
22
10 28
57
52
39
17
43
4
17
38
FIGURE 3 (3 OF 6)
DN80 DV-5 PREACTION TYPE A TRIM ASSEMBLY
EXPLODED VIEW
OBSOLETE

TFP1484
Page 7 of 16
QTY QTY
1
3
1
1
1
4
2
1
2
1
3
1
5
1
1
1
1
1
1
1
3
1
1
1
1
1
1
2
1
1
1
1
1
1
2
6
4
1
2
2
6
1
5
5
2
5
1
1
2
1
5
1
2
2
6
2
2
5
3
5
2
1
. . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
NO.
DESCRIPTION DESCRIPTION
Deluge Valve, DV-5, 4" - DN100, ISO Ports;
Rigid Coupling, Figure 577, 4" - DN100; P/N 577ME01141
Riser Check Valve, Model CV-1FR, 4" - DN100;
Reducer, DN20 x DN15; P/N RTEDMN
Pipe Nipple, 1/2" x 160mm; P/N AP160D2
Pipe Nipple, 3/4" x 100mm; P/N AP100E2
Pipe Nipple, 1/2" x 100mm; P/N AP100D2
Pipe Nipple, 1/2" x 250mm; P/N AP250D2
Pipe Nipple, 1/2" x 70mm; P/N AP70D2
Tube, 15 x 1mm, 550 x 400mm; P/N WS00000124
Tube, 15 x 1mm, 370 x 225mm; P/N WS00000096
Pipe, 10 x 12mm, 900mm; P/N WS00000007
Hose, 3 x 6mm, 1.2m; P/N WS00000004
Check Valve, 1/2" NPT; P/N V923221002
Union, DN15 x DN15; P/N UTDMDFN
Tee, DN20 x DN20 x DN20; P/N TTEMEEFN
Tee, DN20 x DN20 x DN20; P/N TTEEEFN
Tee, DN15 x DN15 x DN15; P/N TTDMDFDMN
Tee, DN15 x DN15 x DN15; P/N TTDMDDFN
Tee, DN15 x DN15 x DN15; P/N TTDDMDFN
Tee, DN15; P/N TTDDDFN
Adapter, DN15 x DN15; P/N STDDFN
Reducer, DN20 x DN15; P/N RTFEMN
Reducer, DN20 x DN15; P/N RTEMDFN
Reducer, DN15 x DN8; P/N RTDMBFN
Elbow, DN15 x DN15; P/N ETDMDFN
Elbow, DN15 x DN15; P/N ETDDMN
Elbow, DN15 x DN15; P/N ETDDFN
Adapter, DN20 x DN20; P/N ATEEMN
Compression Fitting, DN15 x 15mm; P/N ATDMCON
Pipe Nipple, 1/2" x 90mm; P/N AP90D2
Pipe Nipple, 2" x 80mm; P/N AP80I2
Pipe Nipple, 3/4" x 80mm; P/N AP80E2
Pipe Nipple, 1/2" x 80mm; P/N AP80D2
Pipe Nipple, 1/2" x 60mm; P/N AP60D2
Pipe Nipple, 1/2" x 50mm; P/N AP50D2
Pipe Nipple, 1/2" x 140mm; P/N AP140D2
Pipe Nipple, 1/2" x 120mm; P/N AP120D2
Plug, 2"; P/N A291I2
Plug, 1/4"; P/N A290B2
Reducing Tee, 2" x 2" x 1/2"; P/N A130RIDI2
Pressure Relief Valve, 1/4"; P/N 923431020
Air Pressure Gauge, 250 PSI; P/N 923431012
Tube Connector, 1/2" x 12mm; P/N 81900211
Restriction, 3mm Orice, 1/2" x 1/2"; P/N 700485
Ball Valve, DN15, Venthole M5; P/N 59304FO
Fail Safe Valve, Model FSV-1; P/N 523431001
Break Station, Model MC-1; P/N 522892001
Solenoid Valve, 24 VDC, 1/2" NPT, 20-250 PSI / 1.4-17.2 bar;
Dry Pilot Actuator, Model B-1; P/N 522801001
Check Valve, Swing Type, 3/4"; P/N 460491005
Check Valve, Swing Type, 1/2"; P/N 460491004D
Elbow, WES 3mm x M5; P/N 406012
Solenoid Valve, 24 VDC, 1/2" NPT, 0.2 - 16 bar;
Drain Valve, Self-Closing, 1/2" NPT; P/N 2162156
Strainer, 1/2" NPT; P/N 20005025
Ball Valve, DN20; P/N 1610000270
Ball Valve, DN15; P/N 1610000210
Angle Valve, 2"; P/N 028300060
Pressure Switch, Model PS40-2; P/N 0263
Pressure Switch, Model PS10-2; P/N 0261
Water Pressure Gauge, 300 PSI; P/N 025500013
P/N 524771923
P/N 595901040
P/N 522871124P
P/N 2191866
36
46
43
45
6
5
2
22 28
26
56
30
10
12
42
6
53
32
10
17
18 58
19
4
48
51
22
56
27 20 22
18
47
28 341 18
12
41
6
341
31
9
20
22
59
24
38
24
37
37
1
27 54
26 13 56
26
12 29
53 17
44
341 58 18
3
20
14
9
50
62
18
6
11
4
23
41
3
20
28
49
62
44
57
7
55
35
15
825
57 25
34
15
10
22
61
58
20
8
7
17
16
62
52
28
10
33
12
10
19
60
22
10 28
58
53
40
17
44
4
17
39
2
26
20
28
12
FIGURE 3 (4 OF 6)
DN100 DV-5 PREACTION TYPE A TRIM ASSEMBLY
EXPLODED VIEW
OBSOLETE

TFP1484
Page 8 of 16
QTY
1
3
1
1
1
1
1
1
1
1
3
1
1
2
2
4
1
1
1
3
QTY
1
5
1
1
1
1
2
1
2
2
1
1
1
2
2
1
1
6
1
3
2
1
1
6
5
5
2
5
3
1
5
1
1
6
2
5
2
5
3
2
2
1
. . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
NO.
DESCRIPTION
Tube, 15 x 1mm, 550 x 400mm; P/N WS00000124
Tube, 15 x 1mm, 370 x 225mm; P/N WS00000096
Pipe, 10 x 12mm, 900mm; P/N WS00000007
Hose, 3 x 6mm, 1.2m; P/N WS00000004
Check Valve, 1/2" NPT; P/N V923221002
Union, DN15 x DN15; P/N UTDMDFN
Tee, DN20 x DN20 x DN20; P/N TTEMEEFN
Tee, DN20 x DN20 x DN20; P/N TTEEEFN
Tee, DN15 x DN15 x DN15; P/N TTDMDFDMN
Tee, DN15 x DN15 x DN15; P/N TTDMDDFN
Tee, DN15 x DN15 x DN15; P/N TTDDMDFN
Tee, DN15; P/N TTDDDFN
Adapter, DN15 x DN15; P/N STDDFN
Reducer, DN20 x DN15; P/N RTFEMN
Reducer, DN20 x DN15; P/N RTEMDFN
Reducer, DN15 x DN8; P/N RTDMBFN
Elbow, DN15 x DN15; P/N ETDMDFN
Elbow, DN15 x DN15; P/N ETDDMN
Elbow, DN15 x DN15; P/N ETDDFN
Adapter, DN20 x DN20; P/N ATEEMN
Compression Fitting, DN15 x 15mm; P/N ATDMCON
Plug, 2"; P/N A291I2
Plug, 1/4"; P/N A290B2
Reducing Tee, 2" x 2" x 1/2"; P/N A130RIDI2
Pressure Relief Valve, 1/4"; P/N 923431020
Air Pressure Gauge, 250 PSI; P/N 923431012
Tube Connector, 1/2" x 12mm; P/N 81900211
Restriction, 3mm Orice, 1/2" x 1/2"; P/N 700485
Riser Check Valve, Model CV-1FR, 6" - DN150;
Ball Valve, DN15, Venthole M5; P/N 59304FO
Rigid Coupling, Figure 577, 6" - DN150; P/N 577ME01681
Deluge Valve, DV-5, 6" - DN150, ISO Ports;
Fail Safe Valve, Model FSV-1; P/N 523431001
Break Station, Model MC-1; P/N 522892001
Solenoid Valve, 24 VDC, 1/2" NPT, 20-250 PSI / 1.4-17.2 bar;
Dry Pilot Actuator, Model B-1; P/N 522801001
Check Valve, Swing Type, 3/4"; P/N 460491005
Check Valve, Swing Type, 1/2"; P/N 460491004D
Elbow, WES 3mm x M5; P/N 406012
Solenoid Valve, 24 VDC, 1/2" NPT, 0.2 - 16 bar;
Drain Valve, Self-Closing, 1/2" NPT; P/N 2162156
Strainer, 1/2" NPT; P/N 20005025
Ball Valve, DN20; P/N 1610000270
Ball Valve, DN15; P/N 1610000210
Angle Valve, 2"; P/N 028300060
Pressure Switch, Model PS40-2; P/N 0263
Pressure Switch, Model PS10-2; P/N 0261
Water Pressure Gauge, 300 PSI; P/N 025500013
DESCRIPTION
P/N 595901060
P/N 524771925
P/N 522871124P
P/N 2191866
Pipe Nipple, 1/2" x 190mm; P/N AP190D2
Pipe Nipple, 1/2" x 250mm; P/N AP250D2
Pipe Nipple, 1/2" x 70mm; P/N AP70D2
Pipe Nipple, 1/2" x 90mm; P/N AP90D2
Pipe Nipple, 2" x 80mm; P/N AP80I2
Pipe Nipple, 3/4" x 80mm; P/N AP80E2
Pipe Nipple, 1/2" x 80mm; P/N AP80D2
Pipe Nipple, 1/2" x 60mm; P/N AP60D2
Pipe Nipple, 1/2" x 50mm; P/N AP50D2
Pipe Nipple, 1/2" x 150mm; P/N AP150D2
Pipe Nipple, 1/2" x 140mm; P/N AP140D2
Pipe Nipple, 1/2" x 130mm; P/N AP130D2
Pipe Nipple, 1/2" x 120mm; P/N AP120D2
Pipe Nipple, 3/4" x 100mm; P/N AP100E2
46
36
43
45
6
5
2
21
27
58
56
29
10
12
42
6
53
34
34
10
62
16
44
17 58
18
4
48
52
19
57
7
51
27
21
56
27
27 19
21 2
17
47
25 341 17
12
41
6
341
30
9
19
21
59
23
38
23
55
32
15
824
57 24
35
15
10
21
61 15
16
26
8
7
62
10
33
12
10
18
60
37
37
21
10 27
58
53
40
16
44
4
16
39 1
32
12
25 54
31
19
13 56
25
12 28
53 16
44
341 58 17
3
20
14
9
50
62
17
6
11
4
22
41
3
19
27
49
FIGURE 3 (5 OF 6)
DN150 DV-5 PREACTION TYPE A TRIM ASSEMBLY
EXPLODED VIEW
OBSOLETE

TFP1484
Page 9 of 16
QTY
1
2
5
3
2
5
2
2
2
6
1
5
1
1
3
5
5
2
5
1
6
1
2
2
2
5
1
1
3
1
1
1
3
1
1
1
2
1
1
1
5
1
1
3
1
1
1
1
1
1
1
1
3
1
1
2
2
4
1
1
1
3
QTY
. . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
NO.
DESCRIPTION
Tube, 15 x 1mm, 550 x 400mm; P/N WS00000124
Tube, 15 x 1mm, 370 x 225mm; P/N WS00000096
Pipe, 10 x 12mm, 900mm; P/N WS00000007
Hose, 3 x 6mm, 1.2m; P/N WS00000004
Check Valve, 1/2" NPT; P/N V923221002
Union, DN15 x DN15; P/N UTDMDFN
Tee, DN20 x DN20 x DN20; P/N TTEMEEFN
Tee, DN20 x DN20 x DN20; P/N TTEEEFN
Tee, DN15 x DN15 x DN15; P/N TTDMDFDMN
Tee, DN15 x DN15 x DN15; P/N TTDMDDFN
Tee, DN15 x DN15 x DN15; P/N TTDDMDFN
Tee, DN15; P/N TTDDDFN
Adapter, DN15 x DN15; P/N STDDFN
Reducer, DN20 x DN15; P/N RTFEMN
Reducer, DN20 x DN15; P/N RTEMDFN
Reducer, DN15 x DN8; P/N RTDMBFN
Elbow, DN15 x DN15; P/N ETDMDFN
Elbow, DN15 x DN15; P/N ETDDMN
Elbow, DN15 x DN15; P/N ETDDFN
Adapter, DN20 x DN20; P/N ATEEMN
Compression Fitting, DN15 x 15mm; P/N ATDMCON
Pipe Nipple, 1/2" x 90mm; P/N AP90D2
Pipe Nipple, 2" x 80mm; P/N AP80I2
Pipe Nipple, 3/4" x 80mm; P/N AP80E2
Pipe Nipple, 1/2" x 80mm; P/N AP80D2
Pipe Nipple, 1/2" x 60mm; P/N AP60D2
Pipe Nipple, 1/2" x 50mm; P/N AP50D2
Pipe Nipple, 1/2" x 300mm; P/N AP300D2
Pipe Nipple, 1/2" x 220mm; P/N AP220D2
Pipe Nipple, 1/2" x 150mm; P/N AP150D2
Pipe Nipple, 1/2" x 140mm; P/N AP140D2
Pipe Nipple, 1/2" x 130mm; P/N AP130D2
Pipe Nipple, 1/2" x 120mm; P/N AP120D2
Pipe Nipple, 3/4" x 100mm; P/N AP100E2
Pipe Nipple, 1/2" x 100mm; P/N AP100D2
Plug, 2"; P/N A291I2
Plug, 1/4"; P/N A290B2
Reducing Tee, 2" x 2" x 1/2"; P/N A130RIDI2
Pressure Relief Valve, 1/4"; P/N 923431020
Air Pressure Gauge, 250 PSI; P/N 923431012
Tube Connector, 1/2" x 12mm; P/N 81900211
Restriction, 3mm Orice, 1/2" x 1/2"; P/N 700485
Riser Check Valve, Model CV-1FR, 8" - DN200;
Ball Valve, DN15, Venthole M5; P/N 59304FO
Rigid Coupling, Figure 577, 8'' - DN200; P/N 577ME02191
Deluge Valve, DV-5, 8" - DN200, ISO Ports;
Fail Safe Valve, Model FSV-1; P/N 523431001
Break Station, Model MC-1; P/N 522892001
Solenoid Valve, 24 VDC, 1/2" NPT, 20-250 PSI / 1.4-17.2 bar;
Dry Pilot Actuator, Model B-1; P/N 522801001
Check Valve, Swing Type, 3/4"; P/N 460491005
Check Valve, Swing Type, 1/2"; P/N 460491004D
Elbow, WES 3mm x M5; P/N 406012
Solenoid Valve, 24 VDC, 1/2" NPT, 0.2 - 16 bar;
Drain Valve, Self-Closing, 1/2" NPT; P/N 2162156
Strainer, 1/2" NPT; P/N 20005025
Ball Valve, DN20; P/N 1610000270
Ball Valve, DN15; P/N 1610000210
Angle Valve, 2"; P/N 028300060
Pressure Switch, Model PS40-2; P/N 0263
Pressure Switch, Model PS10-2; P/N 0261
Water Pressure Gauge, 300 PSI; P/N 025500013
DESCRIPTION
P/N 595901080
P/N 524771926
P/N 522871124P
P/N 2191866
45
6
5
48
52
19
2
21
57
7
51
36
26
43
21
56
26
35 19
21 2
17
47
32
26
58
56
28
10
12
42
341 17
12
41
6
341
29
46
6
53
33
33
10
62
16
44
17 58
18
4
9
19
21
59
23
38
23
55
31
15
824
57 24
34
15
10
21
61 15
16
33
8
7
62
10
30
12
10
18
60
37
37
21
10 26
58
53
40
16
44
4
16
39 1
29
12
25 54
29
19
13 56
25
12 27
53 16
44
341 58 17
3
20
14
9
50
62
17
6
11
4
22
41
3
19
26
49
FIGURE 3 (6 OF 6)
DN200 DV-5 PREACTION TYPE A TRIM ASSEMBLY
EXPLODED VIEW
OBSOLETE

TFP1484
Page 10 of 16
Installation
DV-5 Preaction Type A Valves are to
be installed in accordance with this
section.
General Instructions
Proper operation of the DV-5 Pre-
action Type A Valve depends upon
installation in accordance with the
instructions given in this technical data
sheet. Failure to follow the appropriate
steps may prevent the DV-5 Valve with
Preaction Type A Trim from function-
ing properly, may void the manufactur-
er’s warranty, and will void listings and
approvals.
The DV-5 Preaction Type A Valve must
be maintained at a minimum tempera-
ture of 40°F (4°C).
NOTICE
Heat tracing of the DV-5 Preaction Type
A Valve is not permitted. Heat tracing
can result in the formation of hardened
mineral deposits that are capable of
preventing proper operation.
Notes:
• Install the valve in a readily visible and
accessible location.
• Ensure the fully assembled Preaction
Type A Trim is installed in accordance
with Figure 3.
• Ensure suitable provision for disposal
of drain water. Direct drainage water so
that it will not cause accidental damage
to property or danger to persons.
Step 1. Connect the Diaphragm
Chamber Supply Control Valve to the
inlet side of the system’s Main Control/
Shut-off Valve in order to facilitate
setting of the Preaction Type A Trim
(Ref. Figures 3, 5 and 6).
Step 2. Install a suitable automatic
supervisory air (nitrogen) supply,
as described in the Technical Data
section, in accordance with the refer-
enced Technical Data Sheet. Set the
device according to Graph B.
Step 3. Install a desiccant dryer, when
required for the supervisory air supply,
between a drip leg and the Model
AMD-1 Air Maintenance Device or
between the Automatic Supervisory Air
Supply and the Preaction Type A Trim.
Step 4. Wire the Supervisory Low Pres-
sure Alarm Switch to the supervisory
alarm initiating circuit of an alarm panel.
Step 5. Make conduit and electrical
connections in accordance with the
requirements of the authority having
jurisdiction.
Nominal
Valve Size
Nominal Dimensions in Millimeters
AB* C* DE* F* G
DN40 376 346 356 236 323 221 178
DN50 390 346 356 243 316 221 155
DN80 536 432 356 276 284 184 111
DN100 645 478 356 314 275 176 68
DN150 759 500 356 380 286 140 36
DN200 936 529 406 420 309 88 N/A
*Minimum Clearance
* * * *
E D B C F
A
G
FRONT VIEWLEFT VIEW
FIGURE 4
DV-5 PREACTION TYPE A VALVE
NOMINAL INSTALLATION DIMENSIONS
OBSOLETE

TFP1484
Page 11 of 16
Valve Setting
Procedure
With reference to Figures 5 and 6,
perform these steps when initially
setting the DV-5 Preaction Type A
Valve, after an operational test of the
fire protection system, or after system
operation due to a fire.
Step 1. Close the Main Control/Shut-
off Valve.
Step 2. Close the Diaphragm Chamber
Supply Control Valve and the Air Supply
Control Valve.
Step 3. Open the Main Drain Valve,
System Drain Valve, and all auxil-
iary drains in the system. After water
ceases to discharge, close the System
Drain Valve and auxiliary drain valves.
Leave the Main Drain Valve open.
Step 4. Depress the plunger of the
Automatic Drain Valve to verify that it
is open and that the Preaction Type A
Trim is completely drained.
Step 5. Clean the Strainers in the Dia-
phragm Chamber Supply connection
and in the pneumatic actuation loop
by removing the clean-out plug and
strainer basket.
Step 6. Replace operated automatic
sprinklers on the system piping.
NOTICE
In order to prevent the possibility of a
subsequent operation of an overheated
solder type automatic sprinkler, any
solder type automatic sprinklers that
were possibly exposed to a tempera-
ture greater than their maximum rated
ambient must be replaced.
Step 7. Reset the Local Hydraulic
Manual Pull Station by pushing the
operating lever up; however, do not
close the hinged cover at this time.
Step 8. Reset the Deluge Valve Releas-
ing Panel in accordance with the manu-
facturer’s instructions.
Step 9. Re-establish system air pres-
sure to reset the Model DP-1 Dry Pilot
Actuator by opening the Air Supply
Control Valve, which allows the
system to automatically re-establish
its nominal air pressure. Observe the
Automatic Drain Valve for leaks. If there
are leaks, determine/correct the cause
of the leakage problem within the Riser
Check Valve.
Step 10. Drain the actuation loop to
remove any water out of the piping.
Step 11. Re-establish system air pres-
sure to reset the Model DP-1 Dry Pilot
Actuator if applicable.
Step 12. Open the Diaphragm
Chamber Supply Control Valve and
allow time for full pressure to build up
in the Diaphragm Chamber.
Step 13. Operate (open) the Manual
Control Station to vent trapped air
from the Diaphragm Chamber. If nec-
essary, first open the hinged cover, and
then fully pull down on the operating
lever. Slowly close the operating lever,
by pushing it up, after aerated water
ceases to discharge from the Manual
Control Station drain tubing. Close the
hinged cover and insert a new break
rod in the small hole through the top of
the enclosing box.
Step 14. Inspect the drain connections
from the Manual Control Station and
the Solenoid Valve. Correct any leaks
must before proceeding to the next
step.
Step 15. Verify the ability for the DV-5
Diaphragm to hold pressure as follows:
With the diaphragm chamber pressur-
ized per Step 8, temporarily close the
Diaphragm Chamber Supply Control
Valve, and monitor the Diaphragm
Chamber Pressure Gauge for a drop
in pressure. If a drop in pressure is
noted, the DV-5 Diaphragm is to be
replaced and/or any leaks must be cor-
rected before proceeding to the next
step. If the Diaphragm Chamber Pres-
sure Gauge does not indicate a drop
in pressure, re-open the Diaphragm
Chamber Supply Control Valve and
proceed to the next step.
Step 16. Slowly open the Main Control
Valve. Close the Main Drain Valve as
soon as water discharges from the
drain connection. Observe the Auto-
matic Drain Valve for leaks. If there are
leaks, determine/correct the cause of
the leakage problem. If there are no
leaks, the DV-5 Preaction Type A Valve
is ready to be placed in service and the
Main Control Valve must then be fully
opened.
NOTICE
When the Main Control Valve is
opened, the pressure on the Dia-
phragm Chamber may increase. This
increase in pressure is normal, and if
the pressure is greater than 16 bar, the
pressure is to be relieved by partially
and temporarily opening the Manual
Control Station; however, do not allow
the pressure as indicated on the Dia-
phragm Chamber Pressure Gauge to
drop below the supply pressure shown
on the Water Supply Pressure Gauge,
since this action may result in tripping
of the DV-5 Preaction Type A Valve.
After setting a fire protection system,
notify the proper authorities and advise
those responsible for monitoring pro-
prietary and/or central station alarms.
OBSOLETE

TFP1484
Page 12 of 16
Care and
Maintenance
With reference to Figures 5 and 6, the
following procedures, inspections, and
maintenance must be performed as indi-
cated, in addition to any specific require-
ments of EN12845, and any impairment
must be immediately corrected.
Before closing a fire protection system
Main Control Valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Some of the procedures outlined in
this section will result in operation of
the associated alarms. Consequently,
notification must first be given to the
owner and the fire department, central
station, or other signal station to which
the alarms are connected.
The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this doc-
ument, as well as with the applicable
standards of EN12845 in addition to the
standards of any authority having juris-
diction. Contact the installing contrac-
tor or product manufacturer with any
questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Weekly Waterflow Alarm
Test Procedure
Testing of the system waterflow alarms
must be performed quarterly. To test
the waterflow alarm, open the Alarm
Test Valve, which will allow a flow of
water to the Waterflow Pressure Alarm
Switch and/or Water Motor Alarm.
Upon satisfactory completion of the
test, close the Alarm Test Valve.
MANUAL CONTROL
STATION
MODEL FSV-1
FAIL-SAFE VALVE
(NORMALLY
CLOSED)
DV-5 DELUGE
VALVE
AUTOMATIC
DRAIN
VALVE
SYSTEM
WATER
SUPPLY
PRESSURE
GAUGE
ALARM
TEST VALVE
(NORMALLY
CLOSED)
ALARM
CONTROL
VALVE
(NORMALLY
OPEN)
WATERFLOW
PRESSURE
ALARM
SWITCH
DIAPHRAGM
CHAMBER SUPPLY
CONTROL VALVE
(NORMALLY OPEN)
PNEUMATIC
ACTUATION LOOP
DRAIN VALVE
(NORMALLY
CLOSED)
MODEL DP-1
DRY PILOT
ACTUATOR
(NORMALLY
OPEN)
MAIN
DRAIN VALVE
(NORMALLY
CLOSED)
MODEL CV-1FR
CHECK VALVE
DIAPHRAGM
CHAMBER
PRESSURE
GAUGE
SYSTEM
ACTUATION
SOLENOID VALVE
(NORMALLY
CLOSED) SYSTEM
PRESSURE
GAUGE
SYSTEM
AIR SUPPLY
CONTROL VALVE
(NORMALLY
OPEN)
LOW AIR
PRESSURE
ALARM
SWITCH
SYSTEM
AIR SUPPLY
PRESSURE
GAUGE
SYSTEM
DRAIN VALVE
(NORMALLY
CLOSED)
PNEUMATIC
ACTUATION
SOLENOID VALVE
(NORMALLY
OPEN)
NORMAL OPERATION:
SINGLE INTERLOCK ELECTRIC
AFTER FAULT DETECTION
(LOSS OF PRIMARY AND
BACK-UP BATTERY POWER):
DRY PIPE SYSTEM
PREACTION TYPE A NOTES
1.
2.
FIGURE 5
DV-5 PREACTION TYPE A VALVE
TRIM ASSEMBLY FUNCTIONAL COMPONENTS
OBSOLETE

TFP1484
Page 13 of 16
Quarterly Solenoid Valve
Test Procedure for
Electric Actuation
Proper operation of the Solenoid Valves
for electric actuation must be verified at
least quarterly as follows:
Step 1. Close the Main Control Valve.
Step 2. Open the Main Drain Valve.
Step 3. Test the deluge releasing panel
in accordance with the manufacturer’s
instructions to energize the Solenoid
Valves.
Step 4. Verify that the flow of water
from the Solenoid Valve drain connec-
tion increases to a full flow.
Step 5. Verify that the Diaphragm
Chamber pressure has decreased
to below 25% of the water supply
pressure.
Step 6. Reset the electric detection
system in accordance with the manu-
facturer’s instructions to de-energize
the solenoid valve. Check the Solenoid
Valve drain for leaks. Correct any leaks
before proceeding to the next step.
Step 7. Slowly open the Main Control
Valve. Close the Main Drain Valve as
soon as water discharges from the
drain connection. Observe the Auto-
matic Drain Valve for leaks.
If there are leaks, determine/correct the
cause of the leakage problem.
If there are no leaks, the DV-5 Preac-
tion Type A Valve is ready to be placed
in service and the Main Control Valve
must then be fully opened.
Quarterly Solenoid Valve
Test Procedure for
Pneumatic Actuation Loop
(Detection Failure)
Proper operation of the Solenoid Valve
must be verified at least quarterly as
follows:
Step 1. Close the Main Control Valve.
Step 2. Open the System Drain Valve.
Step 3. Test the deluge releasing panel
in accordance with the manufacturer’s
instructions to de-energize the Sole-
noid Valve.
Step 4. Verify that the flow of water
from the Dry Pilot Valve drain connec-
tion increases to a full flow.
Step 5. Verify that the Diaphragm
Chamber pressure has decreased
to below 25% of the water supply
pressure.
Step 6. Reset the electric detection
system in accordance with the manu-
facturer’s instructions to energize the
Solenoid Valve. Check the Dry Pilot
Valve drain for leaks. Correct any leaks
before proceeding to the next step.
DELUGE VALVE
RELEASING PANEL
(AUTOMATIC
CONTROL UNIT
WITH BATTERY
BACK-UP)
ALARM
TEST VALVE
(NORMALLY
CLOSED)
WATER
SUPPLY
PRESSURE
GAUGE
POWER
SUPPLY
(TYPICALLY
230 VOLTS AC)
DIAPHRAGM CHAMBER
SUPPLY CONTROL VALVE
(NORMALLY OPEN)
MODEL FSV-1
FAIL-SAFE VALVE
(NORMALLY CLOSED)
WATERFLOW
PRESSURE
ALARM
SWITCH
TO
MECHANICAL
ALARM
AUTOMATIC
DRAIN VALVE
MAIN
DRAIN VALVE
(NORMALLY
CLOSED)
SYSTEM AIR
PRESSURE
GAUGE
SYSTEM
PRESSURE
GAUGE SYSTEM
DRAIN VALVE
(NORMALLY
CLOSED)
WATER
SUPPLY
MAIN SUPPLY CONTROL/
SHUT-OFF VALVE
(NORMALLY OPEN)
AIR SUPPLY
CONTROL VALVE
(NORMALLY
OPEN)
ALARM
CONTROL
VALVE
(NORMALLY
OPEN)
MODEL DP-1
DRY PILOT
ACTUATOR
(NORMALLY
OPEN)
DV-5
DELUGE
VALVE
MODEL
CV-1FR
CHECK
VALVE
PNEUMATIC
ACTUATION
SOLENOID VALVE
(TYPICALLY 24 VOLTS DC,
NORMALLY OPEN;
ENERGIZED TO
CLOSE)
CONTROL VALVE
(NORMALLY OPEN)
AUTOMATIC
AIR/NITROGEN
SUPPLY
LOCAL
HYDRAULIC
MANUAL PULL
STATION
DIAPHRAGM
CHAMBER
PRESSURE
GAUGE
SYSTEM
ACTUATION
SOLENOID VALVE
(TYPICALLY
24 VOLTS DC,
NORMALLY
CLOSED)
LOW AIR
PRESSURE
ALARM SWITCH
ACTUATION LOOP
DRAIN VALVE
(NORMALLY
CLOSED)
SYSTEM PIPING WITH AUTOMATIC SPRINKLERS - NORMALLY DRY
RESTRICTION
STRAINER
STRAINER
FIGURE 6
DV-5 PREACTION TYPE A VALVE
FUNCTIONAL SYSTEM SCHEMATIC
OBSOLETE

TFP1484
Page 14 of 16
Step 7. Slowly open the Main Control
Valve. Close the Main Drain Valve as
soon as water discharges from the
drain connection. Observe the Auto-
matic Drain Valve for leaks. If there are
leaks, determine/correct the cause of
the leakage problem. If there are no
leaks, the DV-5 Preaction Type A Valve
is ready to be placed in service and the
Main Control Valve must then be fully
opened.
NOTICE
When the Main Control Valve is
opened, the pressure on the Dia-
phragm Chamber may increase. This
increase in pressure is normal, and if
the pressure is greater than 16 bar, the
pressure is to be relieved by partially
and temporarily opening the Manual
Control Station; however, do not allow
the pressure as indicated on the Dia-
phragm Chamber Pressure Gauge to
drop below the supply pressure shown
on the Water Supply Pressure Gauge,
since this action may result in tripping
of the DV-5 Preaction Type A Valve.
Quarterly
Supervisory Low Pressure Alarm
Test Procedure
Proper operation of the Supervisory
Low Pressure Alarm Switch must be
performed quarterly as follows:
Step 1. Crack open the System Drain
Valve for the Riser Check Valve to
slowly relieve air pressure from the
system. Verify that the Supervisory Low
Pressure Alarm Switch is operational
and that the low pressure set point is
approximately 0,7 bar under the system
pressure.
Step 2. Close the System Drain Valve
and allow the system supervisory pres-
sure to be automatically re-established.
The Supervisory Low Pressure Alarm
Switch should return to its “normal”
condition.
Annual
Operation Test Procedure
Proper operation of the DV-5 Preaction
Type A Valve (i.e., opening of the DV-5
Valve as during a fire condition) must be
verified at least once a year as follows:
If water must be prevented from flowing
beyond the riser, perform the following
steps:
• Close the Main Control Valve.
• Open the Main Drain Valve.
•
Open the Main Control Valve one
turn beyond the position at which
water just begins to ow from the
Main Drain Valve.
• Close the Main Drain Valve.
Step 1. Test the deluge releasing panel
in accordance with the manufacturer’s
instructions to energize the Solenoid
Valve.
FLOW RATE IN LITERS PER MINUTE (LPM)
NOMINAL PRESSURE DROP IN BAR
200 1000600400 2000 70003000 5000 10000
0,04
0,03
0,05
0,08
0,06
0,07
0,09
0,10
0,20
0,40
0,30
0,60
0,50
DN50
DN40
DN150
DN100
DN80
DN200
15000
0,02
GRAPH A
DN40 THRU DN200 DV-5 VALVE AND MODEL CV-1FR VALVE
NOMINAL PRESSURE LOSS VERSUS FLOW
OBSOLETE

TFP1484
Page 15 of 16
NOTICE
Be prepared to perform Steps 2, 3, and
4 quickly if water must be prevented
from flowing beyond the riser.
Step 2. Verify that the DV-5 Preaction
Type A Valve has tripped, as indicated
by the flow of water into the system.
Step 3. Close the system’s Main
Control Valve.
Step 4. Close the Diaphragm Chamber
Supply Control Valve and the Air Supply
Control Valve.
Step 5. Reset the DV-5 Preaction Type
A Valve in accordance with the Valve
Setting Procedure.
Pressure Relief Valve
Maintenance
Over pressurization of the system
piping with air will result in the opening
of the Pressure Relief Valve. If the Relief
Valve continues to bleed air after the
system pressure has been reduced to
its normal supervisory pressure range,
most likely debris became lodged in
the seating area. Open the Pressure
Relief Valve and clean the seating area.
Internal Valve Inspection
With reference to Figure 1, once every
five years during the annual opera-
tional test procedure and prior to the
DV-5 Deluge Valve being reset, the
interior of the Deluge Valve must be
cleaned and inspected for wear and
damage. Damaged or worn parts
must be replaced. (Replacement of
the Diaphragm every ten years is
recommended, or more frequently
if inspections and/or wear and tear
warrant more frequent replacement.)
When reinstalling the Diaphragm Cover,
complete the following steps to assure
the Diaphragm Cover Fasteners (Hex
Bolts) are uniformly and securely
tightened.
Step 1. Align Diaphragm and Dia-
phragm Cover in proper orientation
with valve body (Ref. Figure 1) and hold
in place
Step 2. Assemble Flat Washers onto
Hex Bolts
Step 3. Apply LOCTITE No. 242 (or
equivalent) to Hex Bolt threads
Step 4. Insert Hex Bolts through Dia-
phragm Cover and Diaphragm, hand-
tighten into valve body
Step 5. Using crossdraw sequence to
assure uniformity, wrench-tighten Hex
Bolts to appropriate torque values (Ref.
Table A)
Step 6. Inspect to assure all Hex Bolts
are securely tightened
NOTICE
If the water supply contains chemi-
cals which tend to attack a nylon fab-
ric-reinforced, natural rubber or the
five year inspection indicates a build-
up of debris within the Deluge Valve
that could affect its proper operation,
then the frequency of the internal valve
inspection procedure must be appro-
priately increased. If the system has
a seawater or brackish water supply,
then the frequency of the internal valve
inspection procedure must be appro-
priately increased. (An annual internal
valve inspection for a system having a
seawater or brackish water supply is
recommended.)
With reference to Figure 1, make
certain that the Diaphragm is correctly
oriented; otherwise, the DV-5 Deluge
Valve cannot be properly set.
Under-tightening the Diaphragm Cover
Bolts can result in internal and external
leakage.
The V-Ring is attached to the Dia-
phragm at the factory. If, during an
internal valve inspection, the V-Ring
is discovered to be detached from the
Diaphragm, be advised that the V-Ring
is a required valve component and that
detachment will not affect normal valve
operation or performance. Should the
V-Ring become detached, reinstall
it between the Diaphragm and Dia-
phragm Cover concentrically as shown
in Figure 1.
Note: Do not apply adhesives, lubricants,
or other substances to the Diaphragm,
V-Ring, or Valve Body.
Nominal
Valve Sizes
DN
Torque
Nm
DN40 22
DN50 29
DN80 54
DN100 65
DN150 72
DN200 87
WATER SUPPLY PRESSURE IN BAR
SYSTEM AIR PRESSURE
AIR PRESSURE IN BAR
1,0
1,0
0
2,0
3,0
4,0 7,0 10,0 13,0
16,0
RANGE OF ACTUATOR OPENING PRESSURE
GRAPH B
AIR (NITROGEN)
MINIMUM SUPPLY PRESSURE (VdS) 3 BAR
PRESSURE REQUIREMENT
TABLE A
DIAPHRAGM COVER BOLTS
MAXIMUM TORQUE
OBSOLETE

TFP1484
Page 16 of 16
LOCTITE is a registered trademark of Henkel Corporation
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product description and Part
Number (P/N).
Preaction Type A
Trim Configuration
(DV-5 Deluge Valve included)
Specify: (specify size) TYCO DV-5 Pre-
action Type A Valve, P/N (specify from
Table B)
Accessories
Releasing Panel
(select one)
Specify: Hekatron Integral IP MXF/MXE
(VdS: G204109) Releasing Panel Pro-
grammed for Preaction Type A
Specify: Hekatron Integral IP CXF/CXE
(VdS: G205049) Releasing Panel Pro-
grammed for Preaction Type A
Supervisory Air Supply *
(select one)
Specify: Model (specify number)
(specify Air or Nitrogen, as applicable)
Mainenance Device, P/N (specify):
Model AMD-1
Air Maintenance Device
(Ref. TFP1221) ............... 52-324-2-002
Model AMD-2
Air Maintenance Device
(Ref. TFP1231) ................52-326-2-001
Model AMD-3
Nitrogen Maintenance Device
(Ref. TPF1241) ................52-328-2-001
*A device capable of maintaining a nominal system air
or nitrogen pressure must be separately ordered
Water Motor Alarm
(ordered separately)
Specify: Model WMA-1 Water
Motor Alarm European Conformity,
P/N 52-630-1-021R
*Refer to Technical Data Sheet TFP922
TRIM
90 Preaction A*
SIZE
ADN40
2DN50
3DN80
4DN100
6DN150
(168,3 mm)
7DN150
(165,1 mm)
8 DN200
* Preaction Type A accord-
ing to EN12845
P/N X X—X—X X—X X—X—X X
END
CONNECTION
74 Flange x Groove,
PN16
75 Groove x Groove
SWITCH
2PS10-2
ACCESSORIES
00 None
STOP
VALVE
00 To Be Ordered
Separately
TABLE B
DV-5 PREACTION TYPE A VALVE
PART NUMBER SELECTION
OBSOLETE

Appendix A of TFP1484 (08/2018)
Summary Instructions (if problems occur, consult full document)
EN12845 Compliance DV-5 Preaction Type A Valve, DN40 thru DN200
I. Normal Conditions
• The Main Control Valve is open and
locked.
• The Diaphragm Chamber Supply
Valve (Q) is open.
• The Air Supply Control Valve (Y) is
open.
• The Alarm Test Valve (G) and Drain
Valves (E, P, and X) are closed.
• The Alarm Control Valve (2) is nor-
mally open.
• The Pneumatic Actuation Loop Drain
Valve (P) is closed.
• The Pressure Gauge Valves are open:
—Pressure gauge (H) reads the sys-
tem water supply pressure.
—Pressure gauge (J) reads the sys-
tem air supply pressure.
—Pressure gauge (K) reads the dia-
phragm chamber pressure.
II. Operation
When set for service, the TYCO DV-5
Preaction Type A Valve (A) utilizes au-
tomatic sprinklers and a supplemen-
tal detection system. The supple-
mental detection system is typically
comprised of 24 VDC heat detectors,
smoke detectors, and manual pull sta-
tions. Actuation of the detection sys-
tem automatically operates (releases)
the DV-5 Deluge Valve, allowing water
to ow into the sprinkler piping system
and to be discharged from any sprin-
klers that may be open.
At the same time, the Model FSV-1 Fail-
Safe Valve (T) pilot chamber is pressur-
ized, opening the Model FSV-1 Valve
(T). Make-up pressure to the diaphragm
chamber of the DV-5 Valve cannot oc-
cur. The main waterway is now open
and water now enters into the system
piping.
In case of an emergency, the valve can
be operated manually by opening the
Manual Control Station (M).
In case of a power cut, the Solenoid
Valve (N) will open. As soon as a sprin-
kler operates/activates, air pressure will
drop, opening the Dry Pilot Actuator (S).
Water from the diaphragm pressure
piping will leave the Dry Pilot Actuator
through this drain, resulting in the ac-
tivation of the DV-5 Deluge Valve (A).
III. Removing System from Service
Step 1. Close the Main Control Valve
and close the Water Motor Alarm
Control Valve (2).
Step 2. Close the Diaphragm Chamber
Supply Valve (Q).
Step 3. Close the Air Supply Control
Valve (Y).
Step 4. Drain the system with drain
valves E, P, and X. Open all other valves
in the system to make sure that cross-
mains and branchlines are vented and
drained.
IV. Returning System to Service
Step 1. Replace operated/damaged
sprinklers and/or reset the manual
control station.
Step 2. Close System Drain Valve (E).
Step 3. Clean the Diaphragm Supply
Strainer (R) and the strainer in the
pneumatic actuation loop.
Step 4. Reset the actuation system:
Manual Actuation — Push the operat-
ing lever of the Manual Control Station
(M) up. However, do not close the
hinged cover at this time.
Electric Actuation — Reset the electric
detection system to de-energize the
Solenoid Valve (F).
Step 5. Open the Diaphragm Chamber
Supply Valve (Q) to pressurize the DV-5
diaphragm chamber.
Step 6. Open and then close the
Manual Control Station (M) to vent
trapped air from the DV-5 diaphragm
chamber.
Step 7. Close Dry Pilot Drain Valve (P).
Step 8. Reset the air pressure in the
sprinkler system by opening the Air
Supply Control Valve (Y).
Step 9. Slowly open the Main Control
Valve. Close all Drain Valves (E, P, and
X).
Step 10. Observe for leaks. If there
are no leaks, the DV-5 Deluge Valve is
ready to place in service.
Step 11. Reset fire alarm panel and
notify central alarm station.
V. Weekly Test
Note: Prior to closing any valves or
activating any alarms, notify local security
guards and the central alarm station, if
applicable.
Step 1. Check self-closing Drain Valve
(V) for leaks.
Step 2. Open the Alarm Test Valve (G);
verify that the alarm signal created by
the Waterflow Switch (C) is visible at
the fire panel. If applicable, check that
the sound of the Water Motor Alarm is
clear and steady. Close the Alarm Test
Valve (G).
Step 3. Drain the alarm line by pushing
the self-closing Drain Valve (V). If the
supply pressure is below the normal,
use the instructions from the water
supply to obtain the usual pressure.
G
B
A
W
D
R
Q
H
T
E
J
P
M
S
K
L
U
X
V
N
C
F
Y
OBSOLETE
Other manuals for DV-5
7
Table of contents
Other Tyco Control Unit manuals

Tyco
Tyco DN40 User manual

Tyco
Tyco 8700 Series User manual

Tyco
Tyco ACC-1 User manual

Tyco
Tyco DV-5 Operating and maintenance instructions

Tyco
Tyco Varec 2440 User manual

Tyco
Tyco RSV-1 User manual

Tyco
Tyco 4100ES User manual

Tyco
Tyco Grinnell F540 User manual

Tyco
Tyco RV-1A User manual

Tyco
Tyco DV-5A User manual
Popular Control Unit manuals by other brands

Telit Wireless Solutions
Telit Wireless Solutions SE867-AGPS user guide

SMC Networks
SMC Networks VHK-A Operation manual

Eaton
Eaton Char-Lynn VersaSteer 10 Series Parts and Repair Information

Infineon
Infineon REF-AIRCON-C302A-IM564 user guide

TECHCON SYSTEMS
TECHCON SYSTEMS TS5624DMP user guide

Mesto
Mesto Neles XH Series Installation maintenance and operating instructions