Tyco RSV-1 User manual

Page 1 of 8 March 2012 TFP980
RAPID RESPONSE Model RSV-1 Residential
Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for
Dual-Purpose Residential Water Supply
Technical Services
800-381-9312
+1- 401-781-8220
www.tyco-fire.com
General
Description
The TYCO RAPID RESPONSE Model
RSV-1 Residential Shut-Off Valves
are intended for use in dual-purpose
residential water supply piping that
serves both domestic and residential
re protection sprinkler system needs.
The 1 Inch (DN25) Valve is intended
for NFPA 13D system needs, whereas
the 2 Inch (DN50) Valve is intended for
systems designed in accordance with
either NFPA 13D or NFPA 13R.
When a re sprinkler operates, the
Model RSV-1 Residential Shut-Off
Valve automatically shuts off water
ow to the domestic system and di-
verts the available water supply to the
re sprinkler system. Consequently,
when the Model RSV-1 Valve is uti-
lized, the system designer does not
need to add the domestic ow de-
mand to the re sprinkler system ow
demand, as would otherwise be re-
quired by NFPA 13R.
Consider use of the Model RSV-1
Residential Shut-Off Valve when either
the water supply cannot adequately
provide for both the domestic design
demand and the re sprinkler ow de-
mand, or it is necessary to increase
the effectiveness of the re sprinkler
system by automatically shutting off
the domestic ow.
The Model RSV-1 Residential Shut-
Off Valve maximizes the effective use
of an existing water supply. Therefore,
in areas with limited water supplies, it
may eliminate the need to add costly
pumps, pressurized reservoirs, or elec-
trically operated domestic shut-off
valves. The Model RSV-1 Valve has a
built-in check valve in the re sprinkler
system outlet that eliminates the need
for a separate check valve. Also, the
Model RSV-1 Valve automatically re-
sets, thereby eliminating the need for
valve disassembly after a re sprinkler
system test or operation.
NOTICE
The Model RSV-1 Residential Shut-Off
Valves described herein must be installed
and maintained in compliance with this
document, as well as with the applicable
standards of the National Fire Protection
Association, in addition to the standards
of any authorities having jurisdiction.
Failure to do so may impair the integrity
of this device.
The owner is responsible for maintaining
their fire protection system and devices in
proper operating condition. The installing
contractor or sprinkler manufacturer
should be contacted relative to any
questions.
Technical
Data
Approvals
•
The 1 Inch (DN25) Model RSV-1 Resi-
dential Shut-Off Valve is UL and C-UL
Listed. It is suitable for use in water
supply arrangements for residential
re sprinkler systems designed per
NFPA 13D.
•
The 2 Inch (DN50) Model RSV-1 Resi-
dential Shut-Off Valve is UL and C-UL
Listed and NSF-61 Annex G Approved.
It is suitable for use in water supply
arrangements for residential re sprin-
kler systems designed per NFPA 13D
or 13R.
Maximum Pressure
175 psi (12,1 bar)
Weight
1 Inch (DN25): 11 lbs. (5 kg)
2 Inch (DN50): 29 lbs. (11 kg)
Pressure Loss
Refer to Figures 5 and 6.
Patents
2 Inch (DN50) Model RSV-1 Valve:
Patent Pending
Physical Characteristics
Refer to Figures 3 and 4.
• 1 Inch (DN25) Valve
Body . . . . . . . . . . . . . .Copper Alloy
Top and
Bottom Cover . . . . . . .Copper Alloy
Upper Cap . . . . . . . . . . . . . . . Brass
Bottom Seal. . . . . . . . . . . . . . Brass
Piston. . . . . . . . . . Glass Reinforced
Polyphenylene Oxide
Differential
Ring . . . . . . . . . . . Glass Reinforced
Polyphenylene Oxide
Sleeve . . . . . . . . . Glass Reinforced
Polyphenylene Oxide
Upper and
Lower Seals . . . . . . . . . . . . . . EPDM
O-Rings . . . . . . . . . . . . . . . . Buna-N
Piston Spring . . . . . . Stainless Steel
Piston Screws . . . . . Stainless Steel
Cap Screw. . . . . . . . Stainless Steel
• 2 Inch (DN50) Valve
Body and
Cover . . . . . . . . . . . . . .Copper Alloy
Piston Insert . . . . . . . .Copper Alloy
Bottom Seal. . . . . . . . .Copper Alloy
Piston Cover . . . . Glass Reinforced
Polyphenylene Oxide
Insert Sleeve . . . . Glass Reinforced
Polyphenylene Oxide
Piston Seal. . . . . . . . . . . . . . . EPDM
O-Rings . . . . . . . . . . . . . . . . . EPDM
Piston Spring . . . . . . Stainless Steel
Piston Nut . . . . . . . . Stainless Steel
Retainer Ring. . . . . . Stainless Steel

TFP980
Page 2 of 8
Design Criteria
The TYCO RAPID RESPONSE Model
RSV-1 Residential Shut-Off Valve
must be installed vertically with the
Water Supply Port at the bottom, the
Fire Sprinkler Port at the top, and the
Domestic Port at the side (Figures 7
and 8). Figure 1 shows the typical in-
stallation arrangement. Refer to the
Installation section for additional de-
sign considerations.
Local regulations concerning pub-
lic water supplies may require a
backow prevention device. The de-
sign of the Model RSV-1 Residential
Shut-Off Valve anticipates that the
backow prevention device will be
located in the water supply upstream
of the Model RSV-1 Valve as shown
in Figure 1. Should local regulations
require the backow prevention de-
vice to be located in the re sprinkler
line downstream of the Model RSV-1
Valve, a by-pass per Figure 2 must be
installed.
NOTICE
Do not install a check valve between the
Model RSV-1 Residential Shut-Off Valve
and the fire sprinklers unless a by-pass
per Figure 2 is installed. Installing a by-
pass disables performance of the Model
RSV-1 Valve as a check valve.
Water Supply Requirements
• 1 Inch (DN25) Valve
In order for the 1 Inch (DN25) Model
RSV-1 Valve to operate automati-
cally upon sprinkler operation, the
re sprinkler system from the water
main to the most hydraulically re-
mote sprinkler must be designed to
provide a minimum single sprinkler
ow of 12.5 GPM (47,3 LPM) when
the supply pressure at the main is at
its minimum expected value.
The minimum single sprinkler ow
rate of 12.5 GPM (47,3 LPM), re-
quired for use with the 1 Inch (DN25)
Model RSV-1 Valve, does not take
precedence over any more hydrau-
lically demanding single sprinkler
ow rate specied for the residential
sprinklers in use.
When performing hydraulic design
calculations for the re sprinkler
system, you need not account for
the trickle ow through the 1 Inch
(DN25) Model RSV-1 Valve By-
Pass Restriction into the domestic
system.
For the 1 Inch (DN25) Model RSV-1
Valve, the maximum water supply
service line is 1 inch (DN25).
• 2 Inch (DN50) Valve
In order for the 2 Inch (DN50) Model
RSV-1 Valve to operate automati-
cally at sprinkler activation, the re
sprinkler system from the water
supply main to the most hydrauli-
cally remote sprinkler must be de-
signed to provide a minimum single
sprinkler ow of 8 GPM (30,5 LPM)
when the water supply pressure at
the water supply main is at its mini-
mum expected value.
The minimum single sprinkler ow
rate of 8 GPM (30,5 LPM), required
for use with the 2 Inch (DN50) Model
RSV-1 Valve, does not take prece-
dence over any more hydraulically
demanding single sprinkler ow rate
specied for the residential sprin-
klers in use.
SYSTEM PRESSURE
FIRE SPRINKLER
GAUGE
DETECTOR
WATERFLOW
(FIRE ALARM)
MODEL RSV-1
RESIDENTIAL
SHUT-OFF VALVE
(AUTOMATIC)
WATER
METER
MAIN
CONTROL
VALVE
WATER
SUPPLY
GATE
VALVE
WATER
SUPPLY
HAVING JURISDICTION
REQUIRED BY AUTHORITY
BACKFLOW PREVENTER AS
AUTOMATIC FIRE SPRINKLERS
TO DOMESTIC
SYSTEM
GAUGE
SUPPLY
PRESSURE
VALVE
CONTROL
DOMESTIC
TEST CONNECTION
DRAIN AND FLOW
ALARM TEST
CONNECTION
WATER SUPPLY
MAIN
FIGURE 1
TYPICAL INSTALLATION ARRANGEMENT
1/4 INCH
TO MAXIMUM
OUTSIDE
TO DOMESTIC
SYSTEM
SPRINKLER
TO FIRE
SYSTEM
PREVENTER
BACKFLOW
RSV-1
EQUIVALENT
BY-PASS
DIAMETER
TUBNG
FIGURE 2
REQUIRED BY-PASS FOR BACKFLOW PREVENTION
IN FIRE SPRINKLER LINE

TFP980
Page 3 of 8
Operating
Principles
When a re sprinkler activates dur-
ing domestic usage, the TYCO RAPID
RESPONSE Model RSV-1 Residential
Shut-Off Valve automatically shuts off
ow to the domestic system and di-
verts the available water supply to the
re sprinkler system, thereby eliminat-
ing a reduced ow condition in the
sprinkler system that might otherwise
be caused by possible signicant do-
mestic water usage.
When the Model RSV-1 Valve is in the
normal standby position as shown in
Figures 7 and 8, the Piston Assembly,
assisted by its Spring, is in the down
position. With the Piston Assembly in
the down position, the Fire Sprinkler
Seal permits the Model RSV-1 Valve
to perform as a conventional check
valve. Also, with the Piston Assembly
in the down position, water is avail-
able on demand through the Domestic
Flow Passage and out the Domestic
Port.
Upon operation and with a minimum
design water ow (e.g., 12.5 GPM (47,3
LPM) for the 1 inch Valve or 8 GPM
(30,5 LPM) for the 2 Inch Valve) to the
automatic residential re sprinkler
system, the Piston Assembly moves
upward. With the Piston Assembly in
the up position, any water ow to the
Domestic Port is diverted to the Fire
Sprinkler Port.
The contours of the Piston Assembly
are specically congured to minimize
its upward movement except under
the level of sustained re sprinkler
system ow resulting from operation
of one or more re sprinklers. How-
ever, because most re sprinkler sys-
tems contain air pockets, the Piston
Assembly tends to move momentarily
upward when there is a surge in sup-
ply pressure.
The momentary opening and re-clos-
ing of the Piston Assembly at the Fire
Sprinkler Line Seal traps a portion
of the pressure increase within the
re sprinkler system. Trapped pres-
sure increases within the re sprinkler
system help to prevent a subsequent
surge in the supply pressure from
causing the water-ow detector to sig-
nal a false alarm (unless a by-pass is
installed per Figure 2).
-
2
Body1 -
4
9
12
13
1
7
8
6
3
2
5
(208,0 mm)
8-3/16"
(125,4 mm)
4-15/16"
(82,6 mm)
3-1/4"
2-3/8"
(60,3 mm)
WATER
PORT, 1" NPT
SUPPLY
(92,1 mm)
3-5/8" DIA.
PORT, 1" NPT
SPRINKLER
FIRE
1" NPT
PORT,
DOMESTIC
11
14
15
10
5
Top Cover
Screw,
Upper Cap
3-
Upper Cap
-
4
Cover (2)
O-Ring,5 -
Upper Seal6 -
Upper Sleeve
O-Ring,7 -
Sleeve8 -
Spring9 -
Ring
Differential10 -
Lower Seal11 -
Piston (4)
Screw,12 -
Bottom Cover13 -
Piston
-
14
Lower Sleeve
O-Ring,15 -
Components:
FIGURE 3
1 INCH (DN25) MODEL RSV-1 RESIDENTIAL SHUT-OFF VALVE
ASSEMBLY AND DIMENSIONS
Components:
4-1/2"
(114,3 mm)
4-9/16"
(115,9 mm)
5-3/8" DIA.
(136,5 mm)
3-3/4"
(95,3 mm)
9-1/16"
(230,2 mm)
FIRE
PORT, 2" NPT
SUPPLY
PORT, 2" NPT
DOMESTIC
PORT,
2" NPT
SPRINKLER
WATER
-
2 Insert Sleeve
Cover O-Ring
Insert Sleeve
O-Ring (2)
Piston Seal
Bottom Seal
-
8
-
4
7-
3-
Body1 -
Piston Nut
Piston Spring
-
6
5-
Piston Cover
Piston Insert
Cover
Retainer Ring
9-
10 -
11 -
12 -
-
13 Bottom Seal
O-Ring
3
7
9
4
2
9
11
10
6
5
1
12
8
13
FIGURE 4
2 INCH (DN50) MODEL RSV-1 RESIDENTIAL SHUT-OFF VALVE
ASSEMBLY AND DIMENSIONS
(Continued on Page 4)

TFP980
Page 4 of 8
As indicated above, domestic system
usage can reduce the pressure avail-
able to the re sprinkler system. How-
ever, when utilizing the Model RSV-1
Valve, you do not need to include ad-
ditional hydraulic ow of the domestic
system, when otherwise required by
NFPA standards (NFPA 13R), to deter-
mine the minimum possible residual
(owing) pressure available to the re
sprinkler system.
For operation of the Model RSV-1 Res-
idential Shut-Off Valve, you need only
design the re sprinkler system from
the water supply main to the most hy-
draulically remote sprinkler. Domestic
ow does not require consideration.
As long as the single sprinkler ow
is equal to or greater than 12.5 GPM
(47,3 LPM) for the 1 Inch Valve or 8
GPM (30,5 LPM) for the 2 Inch Valve
when the supply pressure at the main
is at its minimum expected value,
the Model RSV-1 Valve automatically
shuts off the domestic ow.
After the Piston Assembly has moved
to the full up position, only a small
amount of water is permitted to trickle
through the Internal By-Pass Restric-
tion to the Domestic Port (Figures 7
and 8). The trickle ow through the
Internal By-Pass Restriction permits
the Model RSV-1 Valve to reset auto-
matically after a sprinkler operation or
test without draining the re sprinkler
system.
When the Domestic Control Valve is
closed, the Internal By-Pass Restric-
tion allows the Supply and Domestic
Port pressures to equalize and the
Piston Assembly to move back down
to the standby position.
The maximum ow rate through the
Internal By-Pass Restriction, when
the Model RSV-1 Valve is in the op-
erated position, is less than 1/4 GPM
(0,9 LPM) for a typical residual (ow-
ing) pressure of 40 psi (2,8 bar) at the
inlet. Consequently, when performing
hydraulic design calculations for the
re sprinkler system, you do not need
to consider trickle ow through the
Model RSV-1 Valve Internal By-Pass
Restriction into the domestic system.
FIGURE 5
NOMINAL PRESSURE LOSS VERSUS FLOW FOR
1 INCH (DN25) MODEL RSV-1 VALVE
FLOW RATE IN GALLONS PER MINUTE (GPM)
0.6
0.9
1.0
0.7
0.8
3.0
4.0
5.0
2.0
6050 80 100 200
10.0
9.0
8.0
7.0
6.0
0,09
0,08
0,10
0,07
0,05
0,06
0,20
0,30
0,60
0,40
0,50
200 500400300 700 900
NOMINAL PRESSURE DROP IN BAR
(1 PSI = 0.06895 BAR)
IN POUNDS PER SQUARE INCH (PSI)
NOMINAL PRESSURE DROP
(1 GPM = 3.785 LPM)
FLOW RATE IN LITRES PER MINUTE (LPM)
DOMESTIC PORT
FIRE SPRINKLER PORT
FIGURE 6
NOMINAL PRESSURE LOSS VERSUS FLOW FOR
2 INCH (DN50) MODEL RSV-1 VALVE
FLOW RATE IN GALLONS PER MINUTE (GPM)
2.0
0.4
0.1
0.2
0.3
0.6
0.5
0.8
1.0
3.0
4.0
6.0
5.0
56 10820304050
NOMINAL PRESSURE DROP
IN POUNDS PER SQUARE INCH (PSI)
0,04
0,03
0,02
0,01
0,30
0,20
0,08
0,10
0,06
0,05
0,40
NOMINAL PRESSURE DROP IN BAR
(1 PSI = 0.06895 BAR)
20 4030 60 8050 100
FLOW RATE IN LITRES PER MINUTE (LPM)
(1 GPM = 3.785 LPM)
DOMESTIC PORT
FIRE SPRINKLER PORT
200

TFP980
Page 5 of 8
SUPPLYSUPPLY
DOMESTIC
TO
SPRINKLERS
TO FIRE
OPERATEDSTANDBY
SPRINKLER
PASSAGE
FLOW
FIRE
SUPPLY
PORT
SPRINKLER
PORT
FIRE
DOMESTIC
PORT
SPRINKLER
SEAT
FIRE
SUPPLY
PORT
SPRINKLER
SEAT
FIRE
DOMESTIC
PORT
SPRINKLER
PORT
FIRE
PISTON
ASSEMBLY
DOMESTIC
SEAT
BY-PASS
RESTRICTION
INTERNAL
PISTON
ASSEMBLY
FLOW
PASSAGE
DOMESTIC
DOMESTIC
SEAT
FIGURE 7
STANDBY AND OPERATED POSITIONS FOR 1 INCH (DN25) MODEL RSV-1 VALVE
FIGURE 8
STANDBY AND OPERATED POSITIONS FOR 2 INCH (DN50) MODEL RSV-1 VALVE
OPERATEDSTANDBY
SUPPLYSUPPLY
SPRINKLERS
TO FIRE
DOMESTIC
TO
SPRINKLER
PASSAGE
FLOW
FIRE
SUPPLY
PORT
SPRINKLER
PORT
FIRE
DOMESTIC
PORT
SPRINKLER
SEAT
FIRE
SUPPLY
PORT
SPRINKLER
SEAT
FIRE
DOMESTIC
PORT
SPRINKLER
PORT
FIRE
PISTON
ASSEMBLY
DOMESTIC
SEAT
BY-PASS
RESTRICTION
INTERNAL
PISTON
ASSEMBLY
FLOW
PASSAGE
DOMESTIC
DOMESTIC
SEAT

TFP980
Page 6 of 8
Installation
NOTICE
A fire sprinkler water supply connection
to a public water supply is usually subject
to local regulations concerning metering
and backflow prevention requirements.
Consult with the local water authorities
concerning local requirements that
may apply to the arrangement of these
components in the fire sprinkler system
water supply.
Figure 1 illustrates a typical installation
arrangement using the TYCO RAPID
RESPONSE Model RSV-1 Residential
Shut-Off Valve. The arrangement may
need to be modied to meet the re-
quirements of the authority having ju-
risdiction. However, the Model RSV-1
Valve must be installed in accordance
with the following criteria.
Note: For the 1 Inch (DN25) Valve, the
maximum water supply service line is
1 Inch (DN25).
1. Ensure that the water supply to the
Model RSV-1 Valve is free of contami-
nants and particles of a size greater
than 1/8 inch (3,2 mm).
2. Install the Model RSV-1 Valve verti-
cally with the Supply Port at the bot-
tom, the Fire Sprinkler Port at the top,
and the Domestic Port at the side.
Ensure that the arrows cast on the
Body point in the direction of ow.
A suitable clamp along the water
supply riser piping is recommended
to provide support for the weight of
the Model RSV-1 Valve.
3.
Place a Domestic Control Valve be-
tween the Model RSV-1 Valve and
the domestic system. Position the
inlet to the Domestic Control Valve
within 12 inches of the Domestic Port
of the Model RSV-1 Valve.
4.
The Drain and Flow Test Connection
(Figure 1) is recommended to be a
minimum 1/2 inch (DN15) size for
systems per NFPA 13D, and it must
be a minimum 1 inch (DN25) size for
systems per NFPA 13R.
5.
Install an Alarm Test Connection
with a test orice equal to or less
than the smallest K-factor sprinkler
in the system downstream of the
Waterow Detector.
6.
Apply pipe-thread sealant sparingly
only to the male pipe threads that are
to be assembled to the three ports of
the Model RSV-1 Valve. The use of a
non-hardening pipe-thread sealant
such as TEFLON is recommended.
Valve Setting
Procedure
Perform steps 1 through 9 when initial-
ly lling the re sprinkler and domestic
system piping with water or after a re
sprinkler operation (Figure 1).
1. Close the Main Control Valve.
2.
Close the Domestic Control Valve
and all water outlets in the domestic
piping system.
3.
In addition to the Drain and Flow
Test Connection in the re sprinkler
system, close all drain valves and
replace all operated sprinklers as
necessary.
4.
Partially open the Main Control Valve
until the sound of owing water just
begins, then leave the Main Control
Valve in the partially open position.
5. After the re sprinkler system pres-
sure gauge indicates approximately
the same pressure as the supply
pressure gauge, fully open the Main
Control Valve.
6.
Open the highest elevation outlet on
the domestic system.
7.
Partially open the Domestic Control
Valve until the sound of owing water
begins. Allow the domestic piping to
ll slowly with water.
8.
Close the highest elevation water
outlet on the domestic system when
unaerated water begins to ow.
9.
Completely open the Domestic Control
Valve, then check that the domestic
system is properly pressurized by
verifying that at least three water
outlets in the domestic system can
ow full at the same time.
•
If the water outlets ow fully, the
Model RSV-1 Valve is set and ready
for service. Close the water outlets
on the domestic system.
•
If the water outlets do not ow
fully, re-close the Domestic Con-
trol Valve, wait a minimum of ten
seconds, and ensure that there is
no ow from the re sprinkler sys-
tem piping. Reopen the Domestic
Control Valve, then recheck that
the water outlets are owing fully.
Care and
Maintenance
The following inspection procedure for
the TYCO RAPID RESPONSE Model
RSV-1 Residential Shut-Off Valve
must be performed as indicated, in
addition to any specic requirements
of the NFPA. Any impairment must be
immediately corrected.
NOTICE
Make no attempt to repair any Model
RSV-1 Valve component in the field. The
Model RSV-1 Valve is not field-repairable.
If malfunction occurs, the entire unit
must be replaced.
The operational test and flow test
procedures result in operation of
the associated alarms, as well as an
interruption of the domestic water
supply service. You must notify the
owner, building occupants, and the fire
department, central station, or other
signal station to which the alarms are
connected.
Before closing a fire protection system
control valve for inspection or maintenance
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection system
from the proper authorities and notify
all personnel who may be affected by
this action.
After placing a fire protection system in
service, notify the proper authorities and
advise those responsible for monitoring
proprietary and/or central station alarms.
The owner is responsible for the in-
spection, testing, and maintenance of
their re protection system and devic-
es in compliance with this document,
as well as with the applicable stan-
dards of the National Fire Protection
Association (e.g., NFPA 25), in addition
to the standards of any authority hav-
ing jurisdiction. Contact the installing
contractor or product manufacturer
regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualied Inspec-
tion Service in accordance with local
requirements and/or national codes
and standards.

TFP980
Page 7 of 8
Operation Test Procedure
1.
Fully open two or three water outlets
in the domestic piping system.
2.
To simulate a sprinkler operation,
open the Alarm Test Connection of
the re sprinkler system.
3.
Verify that any alarms are operating
and that the ow from the domestic
water outlets decreases to no more
than a trickle.
4.
Reset the Model RSV-1 Valve in ac-
cordance with the Valve Setting Pro-
cedure described in this data sheet.
Flow Test Procedure
1.
While there is no water owing in the
domestic system, completely open
the Drain and Flow Test Connection.
2.
While water is owing, record the
pressure reading on the re sprin-
kler system pressure gauge and
then compare this reading to previ-
ous readings.
If there is a signicant decrease
in pressure since the last time the
pressure reading was taken and this
decrease is not due to a normally
expected drop in the water supply
pressure, an impairment may exist
that should be immediately identied
and corrected.
3.
Close the Drain and Flow Test Con-
nection to allow the Model RSV-1
Valve to reset automatically. Automatic
resetting occurs within ten seconds.
4.
After waiting ten seconds, completely
open at least three water outlets in
the domestic system and allow these
outlets to ow simultaneously.
If the water outlets ow fully, the
Model RSV-1 Valve is set and ready
for service. Close the water outlets
on the domestic system.
If the water outlets do not ow fully,
close the Domestic Control Valve
and verify that there is no ow from
the re sprinkler system piping, such
as at the Inspector’s Test Connec-
tion. Wait a minimum of ten seconds.
Re-open the Domestic Control Valve
and then recheck that the domestic
system water outlets are owing full.
Limited
Warranty
Products manufactured by Tyco Fire
Production Products (TFPP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years from
date of shipment by TFPP. No war-
ranty is given for products or com-
ponents manufactured by companies
not afliated by ownership with TFPP
or for products and components
which have been subject to misuse,
improper installation, corrosion, or
which have not been installed, main-
tained, modied or repaired in accor-
dance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
authorities having jurisdiction. Mate-
rials found by TFPP to be defective
shall be either repaired or replaced, at
TFPP’s sole option. TFPP neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products
or parts of products. TFPP shall not
be responsible for sprinkler system
design errors or inaccurate or incom-
plete information supplied by Buyer or
Buyer’s representatives.
In no event shall TFPP be liable, in
contract, tort, strict liability or under
any other legal theory, for inciden-
tal, indirect, special or consequential
damages, including but not limited to
labor charges, regardless of whether
TFPP was informed about the pos-
sibility of such damages, and in no
event shall TFPP’s liability exceed an
amount equal to the sales price.
The foregoing warranty is made in
lieu of any and all other warranties,
express or implied, including warran-
ties of merchantability and tness for
a particular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Information
Contact your local distributor for avail-
ability. When placing an order, indi-
cate the full product name and Part
Number (P/N).
Valves with NPT Connections
Specify: 1 Inch NPT (DN25) Model
RSV-1 Residential Shut-Off Valve, P/N
52-540-1-001.
Specify: 2 Inch NPT (DN50) Model
RSV-1 Residential Shut-Off Valve, P/N
52-540-1-002.
Valves with ISO Connections
Specify: ISO Rc1 (DN25) Model
RSV-1 Residential Shut-Off Valve, P/N
52-540-1-011.
Specify: ISO Rc2 (DN50) Model
RSV-1 Residential Shut-Off Valve, P/N
52-540-1-204.

TFP980
Page 8 of 8
Copyright © 2012 Tyco Fire Protection Products. All rights reserved.
TEFLON is trademark of The DuPont Corporation.
Table of contents
Other Tyco Control Unit manuals
Popular Control Unit manuals by other brands

Talis
Talis ERHARD INFINITY 0140160 Series Installation, operation and maintenance manual

AMI
AMI Sample Pump manual

AMTC
AMTC HYBRIDFLUSH AEF-801 SERIES Installation and owner's manual

Booma-RC
Booma-RC Intelliswitch V3 manual

Visual Productions
Visual Productions IOCORE manual

Kaelus
Kaelus ACU0001F1V1 user guide