manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco
  6. •
  7. Firefighting Equipment
  8. •
  9. Tyco EC-25 User manual

Tyco EC-25 User manual

General
Description
TYCO Model EC-25 Extended Cover-
age Upright Sprinklers are UL Listed
standard response, extended cover-
age sprinklers for Storage Protection
(Area/Density) and FM Approved quick
response, extended coverage sprin-
klers for storage and non-storage ap-
plications. Their use is especially ad-
vantageous as a means of decreasing
the number of required sprinklers to
protect occupancies requiring an area/
density application of water.
These sprinklers offer a maximum
coverage area of 196 ft² (18,2 m²),
which is almost double the area of-
fered by standard coverage sprinklers
used for similar applications.
The Model EC-25 Sprinklers comply
with the criteria for the protection of
retail stores as described in the 2010
Edition of NFPA 13, Section 20.3.
Where the FM Approval is utilized, the
Model EC-25 Sprinkler has success-
fully undergone full-scale re testing at
FM Global for ceiling-only storage ap-
plications. When used in conformance
with applicable FM Global Property
Loss Prevention Data Sheets, the
Model EC-25 Sprinkler provides low
hydraulic demand, the spacing ad-
vantages of extended coverage, and
the obstruction benets of an upright
sprinkler.
For more information on applications
and benets of the Model EC-25 Sprin-
kler, refer to the available white papers
at www.tyco-re.com.
NOTICE
The Model EC-25 Sprinklers described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Pro-
tection Association, in addition to the
standards of any other Authorities
Having Jurisdiction (for example, FM
Global). Failure to do so may impair
the performance of these devices.
Owners are responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Number (SIN)
TY9128
Technical
Data
Approvals
• UL and C-UL Listed
• FM Approved
• NYC under MEA 355-01-E
(Approvals only apply to the service
conditions indicated in the Design Cri-
teria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
• 1 inch NPT
• ISO 7-R1
Discharge Coefficient
K=25.2 GPM/psi1/2 (362,9 LPM/bar1/2)
Temperature Ratings
• 165°F (74°C)
• 214°F (101°C)
Maximum Coverage Area
196 ft² (18,2 m²)
Finish
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . Brass
Deector . . . . . . . . . . . . . . . . .Copper
Compression Screw . . . . . . Stainless
Steel
Hook . . . . . . . . . . . . . . . . . . . . .Monel
Strut . . . . . . . . . . . . . . . . . . . . .Monel
Link Assembly . . . . . . . .Solder, Nickel
Button . . . . . . . . . . . . . . . . . . . . Brass
Sealing Assembly ........Beryllium
Nickel w/TEFLON
Ejection Spring . . . . . . . . . . . . Inconel
Deector Nut . . . . . . . . . . . . . . . Brass
Model EC-25
Extended Coverage Upright Sprinklers
K-Factor 25.2 (360)
Page 1 of 4 SEPTEMBER 2011 TFP213
IMP ORTA NT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and
installation of sprinkler systems and
components. Improper handling
and installation can permanently
damage a sprinkler system or its
components and cause the sprinkler
to fail to operate in a fire situation or
cause it to operate prematurely.
Technical Services
800-381-9312
+1-401-781-8220
www.tyco-fire.com
FIGURE 1
MODEL EC-25 EXTENDED COVERAGE
UPRIGHT SPRINKLER
7
11" NPT
8
6
9
5
4
2
WRENCH
FLATS
TEMPERATURE
RATING
9/16"
(14,3 mm)
MAKE-IN
NOMINAL
3-3/4"
(95,3 mm)
310
2-9/16" DIA.
(65,0 mm)
Operation
The fusible link assembly is com-
prised of two link halves that are
joined together by a thin layer of sol-
der. When the rated temperature is
reached, the solder melts and the
two link halves separate, allowing the
sprinkler to activate and ow water.
Design Criteria
UL AND C-UL LISTING
CRITERIA
The Model EC-25 Extended Coverage
Upright Sprinklers (TY9128) are UL
and C-UL Listed for installation in ac-
cordance with the extended coverage
upright spray sprinkler requirements
of NFPA 13 or other applicable NFPA
standards when used in conjunction
with the following guidelines:
• Suitable for the protection of extra
hazard and high-piled storage occu-
pancies where area/density design
criteria are provided.
• Suitable for “unobstructed” or
“noncombustible obstructed”
construction.
• The Model EC-25 Sprinklers hav-
ing been specically tested and
listed for noncombustible obstruct-
ed construction are suitable for use
within trusses or bar joists hav-
ing noncombustible web members
greater than 1 inch (25.4 mm) when
applying the 4 times obstruction cri-
teria rule dened under “Obstruc-
tions to Sprinkler Discharge Pattern
Development”.
• The maximum coverage area per
sprinkler is 196 ft.² (18,2 m²).
• The maximum distance between
sprinklers is 15 feet (4,6 m) when the
coverage area does not exceed 144
ft.² (13,4 m²), and the maximum dis-
tance between sprinklers is 14 feet
(4,3 m) when the coverage area
does not exceed 196 ft.² (18,2 m²).
• The minimum distance between
sprinklers is 8 feet (2,44 m).
• The minimum ow requirement is
based on the design density applied
over the actual coverage area per
sprinkler.
For example: when sprinkler spacing
is 14 ft. x 12 ft. - 6 in. (4,3 m x 3,8 m) or
175 ft² (16,3 m²), and the design
density is 0.6 GPM/ft² (24,4 mm/
min), the sprinkler design ow rate
is 105 GPM (397 LPM) and the re-
quired design pressure is 17.4 psi
(1,2 bar).
• The minimum clearance between
the deector and the top of storage
is 36 inches (0,9 m). For clearances
of 36 inches (0,9 m) up to 48 inches
(1,21 m), the minimum design pres-
sure is 22 psi (1,52 bar). For clear-
ances of 48 inches (1,21 m) and
greater, the minimum design pres-
sure is established by the minimum
ow requirement. However, the
pressure can never be less than 7
psi (0,5 bar).
• Ordinary and intermediate tem-
perature rated Model EC-25 Sprin-
klers have been investigated for use
in high-piled storage occupancies
at the hydraulic demand normally
associated with high temperature
sprinklers. As such, the Model EC-
25 Sprinklers are listed storage
sprinklers having a K-factor greater
than 11.2 (161,4) and having ordi-
nary and intermediate temperature
ratings (that is, 165°F or 74°C and
214°F or 101°C). Consequently, the
Model EC-25 Sprinklers, in accor-
dance with NFPA 13, may be used in
conjunction with the density curves
for high temperature sprinklers.
• NFPA obstruction rules for Extended
Coverage Sprinklers must be utilized.
1- Frame
2- Deector
3- Compression Screw
4- Hook
5- Strut
6- Link Assembly
7- Button
8- Gasketed Spring Plate
9- Ejection Spring
10- Deector Nut
TFP213
Page 2 of 4
FM APPROVAL CRITERIA
The Model EC-25 Extended Coverage
Upright Sprinklers (TY9128) are FM
Approved to be utilized in accordance
with the following guidelines.
Application
The Model EC-25 Extended Coverage
Upright Sprinklers are FM Approved
ceiling-level Storage Sprinklers for
storage occupancy hazards and oth-
er similar high heat release type res.
When compared with other FM Ap-
proved Storage Sprinklers, the Model
EC-25 Sprinkler provides low hydraulic
demand, the spacing advantages
of extended coverage, and the FM
obstruction benets of an upright
sprinkler.
Model EC-25 Sprinklers should be
used in conformance with applicable
FM Global Property Loss Prevention
Data Sheets.
Hydraulic Design
To determine the hydraulic design for
the Model EC-25 Sprinkler refer to the
applicable FM Global Property Loss
Prevention Data Sheet.
System Type
Wet-pipe systems are acceptable.
Sprinkler Spacing
The maximum coverage area per
sprinkler is 196 ft² (18,2 m²). The mini-
mum coverage area per sprinkler is
100 ft² (9,3 m²). The maximum distance
between sprinklers is 14 ft. (4,3 m). The
minimum distance between sprinklers
is 10 ft. (3,05 m).
Note: When a wall or obstruction makes
a minimum spacing of 10 ft. (3,05 m)
impossible, consult FM Global Property
Loss Prevention Data Sheet 2.0 for ap-
plicable guidelines.
Sprinkler Location
Locate sprinklers with respect to the
ceiling/roof in accordance with FM
Global Property Loss Prevention Data
Sheet 2.0.
Obstructions
Follow the obstruction requirements
as detailed in FM Global Property Loss
Prevention Data Sheet 2.0.
Other Details
All other design details should be in
accordance with FM Global Property
Loss Prevention Data Sheet 2.0 as well
as any other applicable FM Global
Data Sheet.
Installation
The TYCO Model EC-25 Upright
Sprinklers are to be installed in accor-
dance with the following instructions:
NOTICE
Damage to the fusible Link Assembly
during installation can be avoided by
handling the sprinkler using only the
frame arms and the appropriate sprin-
kler wrench. Do not grip or apply any
force to the Fusible Link Assembly.
Damaged sprinklers must be replaced
immediately.
Obtain a leak-tight 1 inch NPT sprin-
kler joint by applying a minimum-to-
maximum torque of 20 to 30 ft.lbs.
(26,8 to 40,2 Nm). Higher levels of
torque may distort the sprinkler inlet
with consequent leakage or impair-
ment of the sprinkler.
1. Install the Model EC-25 Sprinkler
in the upright position.
2. With pipe-thread sealant applied,
hand-tighten the sprinkler into the
sprinkler tting. Do not apply any
force to the Link Assembly, and
handle the Model EC-25 Sprinkler
only by the Frame arms.
3. Wrench-tighten the Model EC-25
Sprinkler using only the W-Type 1
Sprinkler Wrench (Figure 2) and by
fully engaging (seating) the wrench
on the sprinkler Wrench Flats.
4. After installation, inspect the Link
Assembly of each Model EC-25
Sprinkler for damage. In particu-
lar, verify that the Link Assem-
bly and Hook are positioned as
illustrated in Figure 1, and that
the Link Assembly has not been
bent, creased, or forced out of
its normal position in any way.
Damaged sprinklers must be re-
placed immediately.
Care and
Maintenance
The TYCO Model EC-25 Sprinkler
must be maintained and serviced
in accordance with the following
instructions.
NOTICE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this decision.
Inspection, testing, and maintenance
must be performed as indicated be-
low and in accordance with the local
requirements and/or national codes.
Any impairment must be immediately
corrected.
Responsibility lies with owners for the
inspection, testing, and maintenance
of their re protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of any authorities having ju-
risdiction. Contact the installing con-
tractor or product manufacturer re-
garding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualied Inspec-
tion Service in accordance with local
requirements and/or national codes.
"FITTING SIDE"
FITTING
TOWARDS SPRINKLER
RECESS
WRENCH
FIGURE 2
W-T Y PE 1
SPRINKLER WRENCH
TFP213
Page 3 of 4
Limited
Warranty
Products manufactured by Tyco Fire
Protection Products (TFPP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in ma-
terial and workmanship when paid
for and properly installed and main-
tained under normal use and service.
This warranty will expire ten (10) years
from date of shipment by TFPP. No
warranty is given for products or com-
ponents manufactured by companies
not afliated by ownership with TFPP
or for products and components
which have been subject to misuse,
improper installation, corrosion, or
which have not been installed, main-
tained, modied or repaired in accor-
dance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Ma-
terials found by TFPP to be defective
shall be either repaired or replaced, at
TFPP’s sole option. TFPP neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products
or parts of products. TFPP shall not
be responsible for sprinkler system
design errors or inaccurate or incom-
plete information supplied by Buyer or
Buyer’s representatives.
In no event shall TFPP be liable, in
contract, tort, strict liability or under
any other legal theory, for inciden-
tal, indirect, special or consequential
damages, including but not limited to
labor charges, regardless of whether
TFPP was informed about the pos-
sibility of such damages, and in no
event shall TFPP’s liability exceed an
amount equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
press or implied, including warranties
of merchantability and tness for a
particular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, ma-
terials or components, whether the
claim is made in contract, tort, strict
liability or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product description and Part
Number (P/N).
Sprinkler Assemblies with 1-Inch
NPT Connections
Specify (temperature rating), natural
brass, Model EC-25 Extended Cov-
erage Upright Sprinkler (TY9128), and
P/N (below).
165°F (74°C) ..............P/N 58- 450-1-165
214°F (101°C) .............P/N 58-450-1-214
“Special Order”
Sprinkler Assemblies with ISO 7/1
Thread Connections
Specify (temperature rating), natural
brass, Model EC-25 Extended Cov-
erage Upright Sprinkler (TY9128) with
thread connection per ISO 7/1, and
P/N (below).
165°F (74°C) ..............P/N 58- 451-1-165
214°F (101°C) .............P/N 58-451-1-214
Sprinkler Wrench
Specify W-Type 1 Sprinkler Wrench,
P/N 56 -872-1-025.
Copyright © 2011 Tyco Fire Protection Products. All rights reserved.
TEFLON is trademark of The DuPont Corporation.
TFP213
Page 4 of 4

Other Tyco Firefighting Equipment manuals

Tyco FSC 80 K-factor Flush Sprinkler User manual

Tyco

Tyco FSC 80 K-factor Flush Sprinkler User manual

Tyco EC-5 Series User manual

Tyco

Tyco EC-5 Series User manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco B-1 User manual

Tyco

Tyco B-1 User manual

Tyco PROTECTOSPRAY EA-1 User manual

Tyco

Tyco PROTECTOSPRAY EA-1 User manual

Tyco K17-231 User manual

Tyco

Tyco K17-231 User manual

Tyco 802SB User manual

Tyco

Tyco 802SB User manual

Tyco EC-25 User manual

Tyco

Tyco EC-25 User manual

Tyco Issue A User manual

Tyco

Tyco Issue A User manual

Tyco D3 PROTECTOSPRAY User manual

Tyco

Tyco D3 PROTECTOSPRAY User manual

Tyco EC-11 Series User manual

Tyco

Tyco EC-11 Series User manual

Tyco Issue D QUARTZOID User manual

Tyco

Tyco Issue D QUARTZOID User manual

Tyco AQUAMIST AM4 User manual

Tyco

Tyco AQUAMIST AM4 User manual

Tyco DV-5A User manual

Tyco

Tyco DV-5A User manual

Tyco RAPID RESPONSE RSV-1 User manual

Tyco

Tyco RAPID RESPONSE RSV-1 User manual

Tyco EC-HS User manual

Tyco

Tyco EC-HS User manual

Popular Firefighting Equipment manuals by other brands

Ampac SmartTerminal Installation, commissioning & operation

Ampac

Ampac SmartTerminal Installation, commissioning & operation

Intelagard MERLIN Operator's manual

Intelagard

Intelagard MERLIN Operator's manual

Janus FM-200 Sv Series Operation & service manual

Janus

Janus FM-200 Sv Series Operation & service manual

Meggitt F251 Series Maintenance manual

Meggitt

Meggitt F251 Series Maintenance manual

FIRETRACE FSCK manual

FIRETRACE

FIRETRACE FSCK manual

Kidde Fire Systems FM-200 ECS Series Design, Installation, Operation, and Maintenance Manual

Kidde Fire Systems

Kidde Fire Systems FM-200 ECS Series Design, Installation, Operation, and Maintenance Manual

ADC EcoDry ADFG Installation & operator's manual

ADC

ADC EcoDry ADFG Installation & operator's manual

Meggitt F116 Series Maintenance manual

Meggitt

Meggitt F116 Series Maintenance manual

Task Force Tips 125 Nozzle Series Maintenance and Service Procedure

Task Force Tips

Task Force Tips 125 Nozzle Series Maintenance and Service Procedure

Fike 403-0006 Installation and maintenance instructions

Fike

Fike 403-0006 Installation and maintenance instructions

Dräger PSS Merlin System Instructions for use

Dräger

Dräger PSS Merlin System Instructions for use

Projoy Electric PEFS-24V-CN Series installation guide

Projoy Electric

Projoy Electric PEFS-24V-CN Series installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.