Model ESFR-22 22.4 K-factor Pendent 
Rapid Install Sprinkler 
Early Suppression, Fast Response
Page 1 of 6 AUGUST 2021 TFP327
IMPORTANT
Refer to Technical Data Sheet 
TFP2300 for warnings pertaining to 
regulatory and health information.
Always refer to Technical Data 
Sheet TFP700 for the “INSTALLER 
WARNING” that provides cautions 
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and 
installation can permanently damage 
a sprinkler system or its compo-
nents and cause the sprinkler to fail 
to operate in a fire situation or cause 
it to operate prematurely.
Worldwide 
Contacts
www.tyco-fire.com
NOTICE
The TYCO Model ESFR-22 Pendent 
Rapid Install Sprinklers described 
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable 
standards of the NATIONAL FIRE PRO-
TECTION ASSOCIATION, in addition to 
the standards of any authorities having 
jurisdiction, such as FM Global. Failure 
to do so may impair the performance 
of these devices.
The owner is responsible for main-
taining their fire protection system 
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any 
questions.
In all cases, the appropriate NFPA or 
FM Global installation standard, or 
other applicable standard, must be 
referenced to ensure applicability and 
to obtain complete installation guide-
lines. The general guidelines in this 
data sheet are not intended to provide 
complete installation criteria.
Sprinkler 
Identification 
Number (SIN)
See Table A
The ESFR-22 RIS provides the system 
designer with hydraulic and sprinkler 
placement options not presently avail-
able to the traditional ESFR sprinklers 
with nominal K-factors of 14.0 and 
16.8. In particular, the ESFR-22 RIS is 
designed to operate at substantially 
lower-end head pressures, as com-
pared to ESFR sprinklers with nominal 
K-factors of 14.0 and 16.8. This feature 
offers flexibility when sizing system 
piping, as well as possibly reducing or 
eliminating the need for a system fire 
pump.
The ESFR-22 RIS can eliminate the use 
of in-rack sprinklers when protecting 
high-piled storage of specific materi-
als up to the following heights:
• NFPA: 40 ft (12,2 m) with ceilings up 
to 45 ft (13,7m)
• FM: 45 ft (13,7 m) with ceilings up to 
50 ft (15,2 m)
For more specific criteria, see Table B 
and the applicable design standard.
General 
Description
The TYCO Model ESFR-22 22.4 K-Fac-
tor Pendent Rapid Install Sprinkler 
(RIS), herein called the ESFR-22 RIS, 
is an Early Suppression, Fast Response 
(ESFR) sprinkler with a pre-installed 
rubber RIS gasket for quick and easy 
installation. The ESFR-22 RIS threads 
into a TYCO RIS welded fitting by hand 
without the need for tape or sealant. 
The sprinkler assembly is shown in 
Figure 1.
The ESFR-22 RIS is a suppression-
mode sprinkler that is especially advan-
tageous as a means of eliminating the 
use of in-rack sprinklers when protect-
ing high-piled storage.
The ESFR-22 RIS sprinkler is primarily 
used for ceiling-only sprinkler protec-
tion of, but not limited to, the following 
storage applications:
• Most encapsulated or non-encap-
sulated common materials including 
cartoned, unexpanded plastics
• Uncartoned (exposed) expanded 
plastics in accordance with the 
National Fire Protection Association 
(NFPA) standard NFPA 13 and FM 
Global standards.
• Some storage arrangements of rub-
ber tires, roll paper, flammable liq-
uids, aerosols, and automotive 
components
For more specific criteria, see Table B 
and the applicable design standard.