Tyco ESFR-17 User manual

Page 1 of 8 AUGUST 2022 TFP320
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycore/tfp320
Model ESFR-17
16.8 K-factor Dry Type Pendent Sprinklers
Early Suppression, Fast Response
tions in this data sheet. The insulating
seal assemblies are recommended to
be installed on smooth, at, and clean
surfaces. If it is expected that environ-
mental conditions may result in exces-
sive condensation, additional sealing of
the assembly is recommended.
There are specic situations, such as
corrugated surfaces where alternate
methods to seal the clearance hole are
recommended. For additional informa-
tion, contact Johnson Controls Techni-
cal Services.
NOTICE
The Model ESFR-17 Dry Type Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document, as well as with the
applicable standards of the National
Fire Protection Association (NFPA), in
addition to the standards of any author-
ities having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identication
Number (SIN)
See Table B
General
Description
The TYCO Model ESFR-17 Dry Type
Pendent Sprinklers are Early Suppres-
sion, Fast Response (ESFR) sprinklers
having a nominal K-factor of 16.8.
They are suppression mode sprinklers
that are especially advantageous as a
means of eliminating in-rack sprinklers
when protecting high-piled box-in-box
refrigerated storage areas.
The Model ESFR-17 Dry Type Pendent
Sprinkler is FM Approved and has
successfully undergone full-scale re
testing at FM Global, when used in con-
formance with applicable FM Global
Property Loss Prevention Data Sheets.
The Model ESFR-17 Dry Type Sprin-
kler consists of an ESFR sprinkler per-
manently secured to a sprinkler drop
featuring an inlet with both grooved
and threaded connections. The drop
between the inlet and sprinkler remains
dry until the sprinkler operates, allow-
ing for a pendent sprinkler installa-
tion on a wet pipe sprinkler system
where the dry drop and sprinkler are
located in an area subjected to freezing
temperatures.
The Model ESFR-17 Dry Type Sprin-
klers are primarily used for ceiling only
sprinkler protection, for example no
need for in-rack sprinklers, and used to
protect solid piled, palletized, and rack
storage that is subject to freezing tem-
peratures. The water supply is provided
from a wet pipe system located outside
of the refrigerated storage area. The
Model ESFR-17 Dry Type Sprinklers
feature all of the same design criteria
as 16.8 K-factor ESFR Pendent Sprin-
klers, and substantially lowers the end
head pressure requirement as com-
pared to the 14.0 K-factor ESFR Dry
Type Pendent Sprinklers.
Combining a 16.8 K-factor with a
dry-type sprinkler design, the Model
ESFR-17 Dry Type Sprinkler provides
the system designer with features that
offer flexibility when sizing system
piping, as well as possibly reducing or
eliminating the need for a system re
pump when protecting high-piled box-
in-box refrigerated storage areas.
The sprinkler also includes two insu-
lating seal assemblies that help seal
the clearance space around the sprin-
kler casing. The seal assemblies are
intended to slow the exchange of air
between the heated area and the pro-
tected area to help prevent humid-
ity and temperature differential in the
area around the sprinkler. Condensa-
tion on the sprinkler and subsequent
ice buildup on or around the sprinkler
can occur that might damage the sprin-
kler or prevent proper operation in a re
situation.
To install the Insulating seal assem-
blies, follow the installation instruc-

TFP320
Page 2 of 8
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
EAC Approved
(See Table D for specic details on
Laboratory listings and approvals.)
Grooved Connection
2 in. Standard Cut Grooved per
technical data sheet TFP1898
Finish
See Physical Characteristics
Physical Characteristics
Threaded and Grooved Inlet. . . . . . . . . . .Bronze
Casing ................Galvanized Steel Pipe
Frame .............................Brass
Deector ..........................Bronze
Hook ............................MONEL
Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Link Assembly................Solder, Nickel
Additional Technical Data
See Table B
Operation
The casing between the inlet and the
sprinkler remains dry until the sprinkler
operates. The fusible link assembly is
comprised of two link halves that are
joined together by a thin layer of solder.
When the rated temperature is reached,
the solder melts and the two link halves
separate, activating the sprinkler and
allowing water to flow through the
casing and to the activated sprinkler.
Design
Criteria
The following general guidelines and
Table C, provide the key design criteria
for the TYCO Model ESFR-17 Dry Type
Pendent Sprinklers.
In all cases, the appropriate NFPA
installation standard, or other appli-
cable standard, must be referenced
to ensure applicability and to obtain
complete installation guidelines. The
general guidelines in this technical
data sheet are not intended to provide
complete installation criteria. For more
information, see Table C.
Ceiling Construction
Unobstructed or non-combustible
obstructed construction, such as
smooth ceiling, bar joists, beam and
girder.
Ceiling Slope
Maximum 2 in. rise for 12 in. run (16.7%)
Maximum Coverage Area
100 ft² (9,3 m²)
Minimum Coverage Area
64 ft² (5,8 m²)
DIM. 36 in.
(914 mm)
Sprinkler
30 in.
(762 mm)
Sprinkler
23 in.
(584 mm)
Sprinkler
A37.5 in.
(952,5 mm) 31.3 in.
(795 mm) 24.3 in.
(617 mm)
B36.2 in.
(919,5 mm) 30.0 in.
(762 mm) 23.0 in.
(584 mm)
C33.9 in.
(861 mm) 27.7 in.
(704 mm) 20.7 in.
(526 mm)
Item Description
Sprinkler Identication Number (SIN) TY7229
K-factor, gpm/psi½(Lpm/bar½)16.8 gpm/psi½(241,9 Lpm/bar½)
Thread Size 1 1/4 in. NPT or ISO 7-R 1 1/4
Sprinkler Orientation Pendent
Maximum Working Pressure, psi (bar) 175 psi (12 bar)
2" (DN50)
GROOVED
CONNECTION
1-1/4" NPT
OR ISO 7-R 1-1/4
PIPE THREADED
CONNECTION
INLET
WRENCH
HEX
THREADED
AND GROOVED
INLET
LINK
ASSEMBLY
GROOVED
COUPLING
GASKET
SEALING
SURFACE
BUTTON
WITH VENT
HOLES
TABLE A
DIM. A
TABLE A
DIM. B
TABLE A
DIM. C
DEFLECTOR
HOOK
STRUT
FRAME
CASING
CENTERLINE
OF THERMAL
SENSING
ELEMENT
TABLE A
SPRINKLER LENGTHS
FIGURE 1
MODEL ESFR-17 DRY TYPE PENDENT SPRINKLER (TY7229)
TABLE B
MODEL ESFR-17 DRY TYPE PENDENT SPRINKLER
TECHNICAL DATA

TFP320
Page 3 of 8
Maximum Spacing
• 12 ft (3,7 m) for ceiling heights up to
30 ft (9,1 m)
• 10 ft (3,1 m) for ceiling heights greater
than 30 ft (9,1 m)
Minimum Spacing
8 ft (2,4 m)
Minimum Clearance to Commodity
36 in. (914 mm)
NFPA
Deflector-to-Ceiling Distance
6 in. to 14 in. (152 mm to 356 mm)
FM Global
Centerline of Thermal Sensing
Element-to-Ceiling Distance
Refer to FM Global 2-0 for storage
sprinklers.
Sprinkler Threaded Fittings
1 1/4 in. NPT Model ESFR-17 Dry Type
Sprinklers are to be installed in the
1 1/4 in. NPT outlet or run of the follow-
ing ttings:
• Malleable or ductile iron threaded
tee fittings that meet the dimen-
sional requirements of ANSI B16.3
(Class 150)
• Cast iron threaded tee ttings that
meet the dimensional requirements
of ANSI B16.4 (Class 125)
Do not install Model ESFR-17 Dry Type
Sprinkler into elbow ttings. The inlet of
the sprinkler can contact the interior of
the elbow and result in damage to the
assembly, resulting in leakage.
The Model ESFR-17 Dry Type Sprin-
kler can also be installed in the 1 1/4
in. NPT outlet of a GRINNELL Figure
730 Mechanical Tee.
Sprinkler
Type Temperature
Rating Laboratory Listings
and Approvals
Pendent
K=16.8 (TY7229)
165°F ( 74°C) 1, 2, 3
212°F (100°C) 1, 3
Notes:
1. UL and C-UL Listed
2. FM Approved
3. EAC Approved
Storage Type NFPA FM Global
Sprinkler Type ESFR Storage
Response Type FR QR
System Type Wet Wet
Temperature Rating ºF (ºC)1165°F (74°C)1
212°F (100°C) 165°F ( 74°C)1
Open Frame (i.e., no solid shelves) Single, Double, Multiple-
Row, or Portable Rack Storage of Class I-IV and Group A or
B Plastics Refer to NFPA 13 Refer to FM 2-0 and 8-9
Solid Pile or Palletized Storage of Class I-IV and Group A or
B Plastics Refer to NFPA 13 Refer to FM 2-0 and 8-9
Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0, 8-9, and 8-24
Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3
Roll Paper Storage
(Refer to the Standard) Refer to NFPA 13 Refer to FM 8-21
Flammable/Ignitable Liquid Storage
(Refer to the Standard) Refer to NFPA 30 Refer to FM 7-29
Aerosol Storage
(Refer to the Standard) Refer to NFPA 30B Refer to FM 7-31
Automotive Components in Portable Racks
(Control mode only; refer to the Standard) N/A N/A
Notes:
1. See Table D for specic details on Laboratory Listings and Approvals
N/A – Not Applicable
TABLE D
LABORATORY LISTINGS AND APPROVALS
TABLE C
MODEL ESFR-17 DRY TYPE PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

TFP320
Page 4 of 8
Sprinkler Grooved Connection
The Model ESFR-17 Dry Type Sprin-
klers can be installed in typical grooved
connection scenarios illustrated in
Figure 4.
For exible couplings, use of the 2 in.
Figure 705 GRINNELL Flexible Cou-
plings with “C” Shape Pre-Lubricated
Grade “A” EPDM Gasket (Refer to
TFP1820) is recommended.
For rigid couplings, use of the 2 in.,
Figure 577 GRINNELL G-FIRE Grooved
Rigid Coupling with “C” Shape Pre-
Lubricated Grade “A” EPDM Gasket
(Refer to TFP1854) is recommended.
Ambient
Temp. of
Protected
Area(a)
Exposed Barrel
Ambient
Temperature(b)(c)
40°F
(4°C) 50°F
(10°C) 60°F
(16°C)
Minimum Exposed
Barrel Length
Inches
(mm)
40°F
(4°C) 0 0 0
30 °F
(-1°C) 0 0 0
20°F
(-7°C) 4
(101,6) 0 0
10°F
(-12°C) 8
(203) 1
(25,4) 0
0°F
(-18°C) 12
(305) 3
(76) 0
-10°F
(-23°C) 14
(356) 4
(101,6) 1
(25,4)
-20°F
(-29°C) 14
(356) 6
(152) 3
(76)
-30°F
(-34°C) 16
(406) 8
(203) 4
(101,6)
-40°F
(-40°C) 18
(457) 8
(203) 4
(101,6)
-50°F
(-46°C) 20
(508) 10
(254) 6
(152)
-60°F
(-51°C) 20
(508) 10
(254) 6
(152)
Notes:
a. The area below the ceiling is referred to as the
protected area. Ambient temperature is the tem-
perature at the discharge end of the sprinkler. For
protected area temperatures that range between
the listed temperatures, use the next cooler
temperature.
b. Lengths are inclusive of wind velocities up to
30 mph (48,3 km/h) and assume a minimum 40°F
(4°C) in heated area.
c. Minimum exposed barrel length when Insulating
Seal Assembly is installed on exterior surface of
ceiling:
• Threaded Fitting Installation
5 in. (125 mm), see Figure 2
• Grooved Fitting Installation
4 1/2 in. (114 mm), see Figure 3
PROTECTED
AREA
HEATED
AREA
EXPOSED
BARREL
LENGTH
(REFER TO
TABLE D
AND DESIGN
CRITERIA)
FACE OF
SPRINKLER
FITTING
CEILING
DEPTH
6" (152 mm)
MINIMUM
14" (356 mm)
MAXIMUM
CLEARANCE
HOLE
2-1/2" to 3"
(65 to 75 mm)
DIA.
END OF
SPRINKLER
INLET
THREADED
FITTING
(REFER TO
DESIGN
CRITERIA)
INSULATING
SEAL
ASSEMBLIES
EXTERIOR
SURFACE OF
CEILING
INTERIOR
SURFACE OF
CEILING
DIM. A
TABLE A
DIM. B
TABLE A
1" (25,4 mm) NOMINAL SYSTEM
PIPE
HEATED
AREA
PROTECTED
AREA
EXPOSED
BARREL
LENGTH
(REFER TO
TABLE D
AND DESIGN
CRITERIA)
FACE OF
SPRINKLER
FITTING
EXTERIOR
SURFACE OF
CEILING
INTERIOR
SURFACE OF
CEILING
CEILING
DEPTH
6" (152 mm)
MINIMUM
14" (356 mm)
MAXIMUM
CLEARANCE
HOLE
2-1/2" to 3"
(65 to 75 mm)
DIA.
SYSTEM
PIPE
END OF
SPRINKLER
INLET GROOVED
FITTING AND
RIGID OR
FLEXIBLE
COUPLING
(REFER TO
DESIGN
CRITERIA)
INSULATING
SEAL
ASSEMBLIES
1-3/8"
(35 mm)
DIM. B
TABLE A
DIM. A
TABLE A
TABLE E
MINIMUM EXPOSED
BARREL LENGTH REQUIRED
PER AMBIENT TEMPERATURE
FIGURE 2
THREADED CONNECTION INSTALLATION
FIGURE 3
GROOVED CONNECTION INSTALLATION

TFP320
Page 5 of 8
When using tees, use of the Figure
219 GRINNELL Grooved Ductile Iron
Cast Fittings (Refer to TFP1810) is
recommended.
NOTICE
Do not install Model ESFR-17 Dry Type
Sprinkler into any other type fitting
connection without first consulting
Johnson Controls Technical Services.
Failure to use the appropriate fitting
may result in insufficient engagement
of the inlet pipe threads with conse-
quent leakage.
Exposure Length
When using Model ESFR-17 Dry Type
Sprinklers to protect areas subject to
freezing temperatures, use Figure 2,
Figure 3, and Table E to determine a
sprinkler’s appropriate exposed barrel
length to prevent water from freezing in
the connection pipes due to conduc-
tion. The exposed barrel length mea-
surement must be taken from the face
of the sprinkler tting to the exterior
surface of the structure or insulation
that is exposed to the heated area.
Do not attempt to add additional insu-
lation around the barrel in the heated
area as a method to minimize conden-
sation. This will reduce the calculated
exposure length.
Clearance Space
In accordance with NFPA 13, when
protecting insulated freezer structures
with dry type sprinklers, the clear-
ance hole around the sprinkler barrel
of the dry type sprinkler and the clear-
ance hole must be sealed. Sealing is
accomplished by use of the insulating
seal assemblies as shown in Figure7.
Failure to use the insulating seal
assemblies will increase the potential
for the formation of condensation on
the sprinkler and subsequent ice build-
up on or around the sprinkler can occur
that might damage the dry type sprin-
kler and/or prevent proper operation in
a re situation.
FM Global 2-0
Consult FM Global and/or FM Global
guidelines for allowable vertical dis-
tance from ceiling to centerline of
thermal sensing element.
GROOVED
TEE
WELDED
GROOVED OUTLET
GROOVED
DROP NIPPLE
GROOVED
RIGID OR
FLEXIBLE
COUPLING
(REFER TO
DESIGN
CRITERIA)
GROOVED
RIGID OR
FLEXIBLE
COUPLING
(REFER TO
DESIGN
CRITERIA)
GROOVED
RIGID OR
FLEXIBLE
COUPLING
(REFER TO
DESIGN
CRITERIA)
MODEL
ESFR-17
DRY PENDENT
SPRINKLER
MODEL
ESFR-17
DRY PENDENT
SPRINKLER
MODEL
ESFR-17
DRY PENDENT
SPRINKLER
APPLY WRENCH
JAW TO INLET
WRENCH HEX
"INLET
SIDE"
W-TYPE 26
WRENCH
WRENCH
JAW
THREADED
SPRINKLER
FITTING
SPRINKLER
FRAME
ARMS
SYSTEM
PIPE
SPRINKLER
FITTING
CLEARANCE
HOLE
CEILING
"FRAME
ARMS"
REFERENCE
MARKS
INDICATE
RELATIVE
SPRINKLER
FRAME ARM
ORIENTATION
BELOW
CEILING
ORIENT
HOUSING
SLOT 180°
OPPOSED
TO INSERT
SLOT
INSERT
HOUSING
INSULATION
RING
CLEARANCE
HOLE
SELF
TAPPING
SCREWS
ORIENT
INSULATION
RING SPLIT
BETWEEN
HOUSING
SLOT AND
SCREW
FIGURE 4
TYPICAL GROOVED
CONNECTION
OPTIONS
FIGURE 6
SPRINKLER FRAME ARMS
ORIENTATION MARK
FIGURE 7
INSULATING SEAL ASSEMBLY
INSTALLATION
FIGURE 5
W-T YPE 26
SPRINKLER
WRENCH

TFP320
Page 6 of 8
Installation
TYCO Model ESFR-17 Early Suppres-
sion, Fast Response 16.8K Pendent
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Avoid damage to the fusible link assem-
bly during installation by using only the
Casing to handle the sprinkler and by
using the appropriate sprinkler wrench.
Do not apply pressure to the fusible
link assembly. Failure to do so can
lead to an unstable link assembly and
premature activation of the sprinkler.
Damaged sprinklers must be replaced.
Model ESFR-17 Dry Type Sprinklers
must only be installed in ttings/con-
nections that meet the requirements
of the Design Criteria section. See
the Design Criteria section for other
important requirements regarding
piping design, exposure length, and the
sealing of the clearance space around
the sprinkler casing.
If a sprinkler using a threaded con-
nection (verus a grooved connec-
tion) requires replacement, remove
the sprinkler using only the W-Type
26 Sprinkler Wrench. Fully engage the
wrench on the inlet wrench hex, as
shown in Figure 5. Replace with the
new sprinkler following the installation
instructions in this section.
Threaded Connection
Instructions
A leak-tight 1 1/4 in. NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 45 lb-ft
to 65 lb-ft (61 N∙m to 88 N∙m). Higher
levels of torque can distort the sprin-
kler inlet with consequent leakage or
impairment of the sprinkler.
Note: Install the Model ESFR-17 Dry Type
Pendent Sprinkler in the pendent position
as shown in Figure 5 by carefully raising the
pendent sprinkler through the clearance
hole. The deflector of the pendent sprinkler
is to be parallel to the ceiling.
Step 1. Apply a non-hardening pipe
thread sealant such as TEFLON to the
male 1 1/4 in. NPT inlet threads.
Step 2. Wrench-tighten the Model
ESFR-17 Dry Type Sprinkler using only
the W-Type 26 Sprinkler Wrench and
by fully engaging the wrench on the
inlet wrench hex as shown in Figure
5. For reference, the “FRAME ARMS”
marking can be used to align the frame
arms with the system pipe as shown in
Figure 6.
Step 3. After installation, inspect the
link assembly of each Model ESFR-17
Dry Type Sprinkler for damage. In par-
ticular, verify that the link assembly
and hook are positioned as illustrated
in Figure 1, and that the link assembly
is not bent, creased, or forced out of
normal position in any way. Replace
damaged sprinklers.
Step 4. Install the insulation rings of the
insulating seal assemblies by slipping
the insulation rings around the sprin-
kler casing as shown in Figure 7. Place
the inserts over the insulation rings by
sliding the inserts around the casing.
Place the housings over the inserts and
insulation rings ensuring that the slot
on the housings are 180 degrees to the
inserts slot. Ensure that the insulating
seal assemblies are snug against the
refrigerated storage ceiling. Secure the
insulating seal assemblies to the ceiling
using two self-tapping screws for each
assembly.
Grooved Connection
Instructions
The following instructions are based
on using the 2 in. Figure 705 Grooved
Flexible Coupling or the 2 in. Figure 577
Grooved Rigid Coupling.
Step 1. Inspect the exterior groove
and the end connection of the mating
grooved connection and sprinkler to
verify all burrs, loose debris, dirt, chips,
paint and other foreign materials such
as grease are removed. Sealing sur-
faces must be free from sharp edges,
projections, indentations, and/or other
defects.
Step 2. Verify that the coupling and
gasket grade are correct for the appli-
cation intended. Refer to Technical
Data Sheet TFP1895 for additional
gasket information. The sealing edges
and the outer surfaces of the gasket
should be covered with a ne layer of
lubricant. To prevent deterioration of
the gasket material, a silicone lubricant
should be used to prevent freezing of
the lubricant.
Step 3. Install the Model ESFR-17
Dry Type Pendent Sprinkler in the
pendent position as shown in Figure
4 and Figure 7, by carefully raising the
pendent sprinkler through the clear-
ance hole. The deector of the pendent
sprinkler is to be parallel to the ceiling.
Also, ensure that the “FRAME ARMS”
markings on the sprinkler casing are
aligned with the system pipe as shown
in Figure 6.
Step 4. Install the gasket by placing it
over the sealing portion of the grooved
inlet connection so that the gasket lip
does not extend beyond the end of
the groove sealing surface. Bring end
of the grooved inlet together with end
of grooved tting ensuring vertical and
horizontal alignment. Slide the gasket
over both sealing surfaces.
Step 5. With one bolt and nut removed,
separate the coupling housings and
place over the gasket. Verify that the
coupling housings are over the gasket
and that the coupling housing keys are
fully engaged into the grooves.
Step 6. Insert the bolt and nut into the
coupling and nger tighten both nuts.
Verify that the bolt heads are fully
recessed in the housing.
The 2 in. Figure 705 Grooved Flexible
Coupling Housing bolt pads must be
in metal-to-metal contact. For exible
coupling deection data, refer to Tech-
nical Data Sheet TFP1820.
The 2 in. Figure 577 Grooved Rigid
Coupling has an intended gap of up to
1/16 of an inch at each pad to allow
for positive rigid gripping onto the
pipe. The patented tongue and groove
design provides protection to the back
of the gasket during installation.
Step 7. Alternate between both sides of
the coupling when tightening the bolts.
Torque bolts to 30 lb-ft (41 N∙m).
Step 8. Install the insulation rings of the
insulating seal assemblies by slipping
the insulation rings around the sprin-
kler casing as shown in Figure 7. Place
the inserts over the insulation rings by
sliding the inserts around the casing.
Place the housings over the Inserts and
insulation rings ensuring that the slot
on the housings is 180 degrees to the
inserts slot. Ensure that the Insulating
seal assemblies are snug against the
refrigerated storage ceiling. Secure the
insulating seal assemblies to the ceiling
using two self-tapping screws for each
assembly.

TFP320
Page 7 of 8
Care and
Maintenance
TYCO Model ESFR-17 Early Suppres-
sion, Fast Response 16.8K Pendent
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a re protection system
main control valve for maintenance
work on the re protection system that
it controls, obtain permission to shut
down the affected re protection from
the proper authorities and notify all
personnel who may be affected by this
action.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
ed or overheated sprinklers must be
replaced.
A vent hole is provided in the link
assembly button as shown in Figure1
to indicate if the dry sprinkler is remain-
ing dry. Evidence of leakage from the
vent hole indicates potential leakage
past the inlet seal and the need to
remove the sprinkler to determine the
cause of leakage; such as an improper
installation or an ice plug. Close the re
protection system control valve and
drain the system before removing the
sprinkler.
When replacing a sprinkler, remove and
discard the old insulating seal assem-
blies, and replace as shown in Figure 7.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced.
The owner is responsible for the
inspection, testing, and maintenance of
their re protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associ-
ation such as NFPA 25, in addition to
the standards of any authorities having
jurisdiction. Contact the installing con-
tractor or product manufacturer with
any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualied Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-re.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and part number
(P/N).
Sprinkler Assemblies
Specify: Model ESFR-17 Dry Type Early
Suppression, Fast Response 16.8K
Pendent Sprinklers (TY7229) with
two (2) Insulating Sealing Assemblies,
P/N (specify):
36 in. Sprinkler
165°F ( 74°C) ..................61-441-1-360
212°F (100°C) .................61-442-1-360
30 in. Sprinkler
165°F ( 74°C) ..................61-441-1-300
212°F (100°C) .................61-442-1-300
23 in. Sprinkler
165°F ( 74°C) ..................61-441-1-230
212°F (100°C) .................61-442-1-230
Special Order
Sprinkler Assemblies with
ISO 7-1 Thread Connections
Specify: Model ESFR-17 Dry Type
Early Suppression, Fast Response
16.8K Pendent Sprinkler (TY7229) with
ISO 7-1 thread connection and two (2)
Insulating Sealing Assemblies, (specify
temperature rating), P/N (specify):
36 in. Sprinkler
165°F ( 74°C) .................I-61-441-1-360
212°F (100°C) ................I-61-442-1-360
30 in. Sprinkler
165°F ( 74°C) .................I-61-441-1-300
212°F (100°C) ................I-61-442-1-300
23 in. Sprinkler
165°F ( 74°C) .................I-61-441-1-230
212°F (100°C) ................I-61-442-1-230
Sprinkler Wrench
Specify: W-Type 26 Sprinkler Wrench,
P/N 56-341-1-001
Insulating Seal Assembly Kit
Each Insulating Seal Assembly kit con-
sists of one (1) Insulation Ring, one (1)
Insert, one (1) Housing, and two (2)
Screws.
Specify: Insulating Sealing Assembly,
P/N 91-106-1-500

TFP320
Page 8 of 8
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
MONEL and INCONEL are registered trademarks of Special Metals Corporation
1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

TFP320
Change History Appendix
Worldwide
Contacts
www.tyco-fire.com
1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
ISSUE DATE NOTES
08-22
Page 1, updated QR code and URL; Page 8, changed corporate address and telephone number to 1467
Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220, formerly 1400 Pennbrook Parkway,
Lansdale, PA 19446 | Telephone +1-215-362-0700.
05-22 Page 2, Approvals sub-section, added C-UL Listed; Page 3, Table D, added C-UL Listed for all tem-
perature ratings.
04-22 Page 1, added QR code and URL to allow convenient access to electronic version from printed docu-
ment; Page 2, Approvals sub-section and Page 3, Table D, added EAC Approved.
08-21
General Description section, added note advising custmers to contact Johnson Controls Technical
Services for information on alternate clearance hole sealing methods when installing below non-at
irregular surfaces.
12-20 Removed greater coverage area statements from Maximum Coverage Area and Maximum Spacing sec-
tions in Design Criteria; Removed references to other Tyco ESFR technical data sheets.
03-20 Table B Commodity Selection and Design Criteria, changed NFPA Response Type to Fast Response
(FR), formerly Quick Response (QR).
09-19 Removed contact information from page 1.
08-18
Updated Tyco® branding and document format; Added Johnson Controls copyright; Added disclaimer
stating specications and information subject to change without notice; Added reference to Regulatory
and Health Warning Technical Data Sheet TFP2300.
05-18 Organized technical information into tables as required by UL.
04-16 Updated Figure 5 to depict W-Type 26 wrench as applying jaw only on inlet wrench hex, not sprinkler
frame wrench ats.
09-15 Page 3, Sprinkler Grooved Connection section, corrected Figure reference to Figure 4, Typical Grooved
Connection Options, formerly shown as Figure 7.
03-15 Changed Temperature Rating to 212°F (100°C), formerly shown as 214°F (101°C).
10 -14 Added reference to FM Loss Prevention Data Sheet 7-29, Installation Criteria for Systems Protecting
Ignitable Liquid Storage in Portable Containers.
06-14 Claried function and application of Insulating Seal Assemblies.
12-13 Removed Mechanical Grooved Outlet Tee option from Figure 4, Typical Grooved Connection Options.
10 -13 Corrected part numbers in Ordering Procedure for 23 in. (584 mm) sprinklers.
08-13 Added 23 and 30 in. (584 and 762 mm) length options; Added FM Approved for 165°F (74°C) tempera-
ture rated sprinklers.
08-12 New Technical Data Sheet TFP320 describes Model ESFR-17 TY7229 16.8 K-factor Dry Pendent
Sprinkler.
Other manuals for ESFR-17
15
Table of contents
Other Tyco Irrigation System manuals

Tyco
Tyco TY-FRB Series User manual

Tyco
Tyco LFII Series Guide

Tyco
Tyco DS-2 Series User manual

Tyco
Tyco RAPID RESPONSE Series User manual

Tyco
Tyco Ultra K17 K-factor User manual

Tyco
Tyco TY-QRF User manual

Tyco
Tyco WP8360 User manual

Tyco
Tyco Rapidresponse LFII Series User manual

Tyco
Tyco Rapidresponse LFII Series Operating and maintenance instructions

Tyco
Tyco Rapidresponse LFII Series User manual