manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco
  6. •
  7. Irrigation System
  8. •
  9. Tyco TY7158 User manual

Tyco TY7158 User manual

Other Tyco Irrigation System manuals

Tyco CC1 User manual

Tyco

Tyco CC1 User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco ELOC User manual

Tyco

Tyco ELOC User manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco TY5332 User manual

Tyco

Tyco TY5332 User manual

Tyco DS-C Series User manual

Tyco

Tyco DS-C Series User manual

Tyco TY-FRL Series User manual

Tyco

Tyco TY-FRL Series User manual

Tyco TY-FRL Series User manual

Tyco

Tyco TY-FRL Series User manual

Tyco F08 FIP User manual

Tyco

Tyco F08 FIP User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco SW-20 User manual

Tyco

Tyco SW-20 User manual

Tyco DS-1 TY3255 Operating and maintenance instructions

Tyco

Tyco DS-1 TY3255 Operating and maintenance instructions

Tyco EC-8C User manual

Tyco

Tyco EC-8C User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco RFII Series User manual

Tyco

Tyco RFII Series User manual

Tyco ESFR-25 User manual

Tyco

Tyco ESFR-25 User manual

Tyco G1 User manual

Tyco

Tyco G1 User manual

Tyco Grinnell F692 DESIGNER User manual

Tyco

Tyco Grinnell F692 DESIGNER User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco ILLUSION TY5521 User manual

Tyco

Tyco ILLUSION TY5521 User manual

Tyco TY2235 Instruction Manual

Tyco

Tyco TY2235 Instruction Manual

Popular Irrigation System manuals by other brands

Toro ZSERIES 570Z brochure

Toro

Toro ZSERIES 570Z brochure

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Tyco Fire Product Star Galaxy SGQR instruction manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR instruction manual

Tyco Fire Product CENTRAL A instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL A instruction manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Reliable F1-300 quick start guide

Reliable

Reliable F1-300 quick start guide

Tyco Fire Product Gem F892 instruction manual

Tyco Fire Product

Tyco Fire Product Gem F892 instruction manual

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Reliable F4FR quick start guide

Reliable

Reliable F4FR quick start guide

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Reliable F1FR42 Series manual

Reliable

Reliable F1FR42 Series manual

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Tyco Fire Product CENTRAL ELO-231 instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Model TY7158 — 16.8 K-factor
Standard Coverage Upright
Storage Sprinkler — Specific Use
Page 1 of 2 MARCH 2018 TFP336
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO 16.8 K-factor Model TY7158
Standard Coverage Upright Storage
Sprinkler is an automatic, standard
response, standard coverage sprin-
kler intended for a specific end use
application.
The TYCO Model TY7158 Sprinkler
has been subjected to full-scale fire
testing at UL LLC using test parame-
ters specified by TYCO that are con-
sidered representative of the specific
end use. The fire test performance
results of the large scale testing have
been verified by UL. Details of the tests
performed and results obtained may be
found in UL Test Report ‘Report of a
Special Services Investigation Involving
K16.8 gpm/(psi)½Upright and Pendent
Sprinkler Protection of a Shelf Display
and Rack Storage Arrangement of Car-
toned Group A Plastic’ (Report Number
NC27954).
For further details, contact the Techni-
cal Services Department.
NOTICE
The Model TY7158 Standard Coverage
Upright Storage Sprinkler described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the stan-
dards of any other authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating
condition. Contact the installing con-
tractor or product manufacturer with
any questions.
Sprinkler
Identification
Number (SIN)
TY7158
Technical
Data
Approvals
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT
Minimum Spacing
6 ft (1,83 m)
Discharge Coefficient
K=16.8 GPM/psi½(241,9 LPM/bar½)
Temperature Ratings
155°F (68°C)
200°F (93°C)*
286°F (141°C)*
* Fire testing of the TYCO Model TY7158 Sprinkler was
completed only in the 155°F (68°C) temperature rating.
The results of such re testing is outlined in UL test re-
port number NC27954.
Finish
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Deflector ............... Commercial Bronze
Compression Screw . . . . . . . . . . . . . . . . . .Brass
Bulb (5 mm). . . . . . . . . . . . . . . . . . . . . . . . . Glass
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Sealing Assembly ..Beryllium Nickel w/TEFLON
Operation
When the glass bulb reaches its rated
temperature of 155°F (68°C), 200°F
(93°C), or 286°F (141°C) the glass bulb
bursts allowing the sprinkler to activate
and flow water.
Installation
Install the TYCO Model TY7158 Stan-
dard Coverage Upright Sprinkler in
accordance with this section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontal, a small air bubble
should be present. For the Model
TY7158 Sprinkler, the diameter of the
air bubble is approximately 1/16 inch
(1,6 mm).
A leak tight 3/4 inch NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque or 10 to 20
ft.-lbs. (13,4 to 26,8 Nm). Higher levels
of torque may distort the sprinkler inlet
with consequent leakage or impair-
ment of the sprinkler. Only the W-type
8 Sprinkler Wrench (Ref. Figure 2) shall
be used during installation.
Sprinkler Installation
Install the Model TY7158 Upright Sprin-
kler only in the upright position as
follows:
Step 1. Apply pipe-thread sealant to
sprinkler threads.
TFP336
Page 2 of 2
NATIONAL FIRE PROTECTION ASSOCIATION is a registered trademark of National Fire Protection Association;
TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Step 2. Hand-tighten sprinkler into
sprinkler fitting. Do not apply force to
glass bulb, grasp only by wrench flats
while hand-tightening.
Step 3. Wrench tighten the Model
TY7158 sprinkler 1-1/4 to 1-1/2 turns
beyond hand-tightening or by applying
a minimum-to-maximum torque of 10
to 20 ft.-lbs. (13,4 to 26,8 Nm) by fully
engaging (seating) the wrench on the
sprinkler flats (Ref. Figure 1) using only
the W-Type 8 Sprinkler Wrench (Ref.
Figure 2).
NOTICE
Higher levels of torque may distort
sprinkler inlet with consequent leakage
or impairment of sprinkler.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
When placing an order, indicate the full
product description and Part Number
(P/N).
Sprinkler Assembly
Specify: Model TY7158 Standard Cov-
erage Upright Sprinkler, SIN TY7158,
temperature rating (specify), P/N
(specify):
155°F (68°C) ................ 51-901-1-155
200°F (93°C)* . . . . . . . . . . . . . . . 51-901-1-200
286°F (141°C)* . . . . . . . . . . . . . . . 51-901-1-286
* Fire testing of the TYCO Model TY7158 Sprinkler was
completed only in the 155°F (68°C) temperature rating.
The results of such re testing is outlined in UL Test Re-
port Number NC27954.
Sprinkler Wrench
Specify: W-Type 8 Sprinkler Wrench,
P/N 56-892-1-001
Care and
Maintenance
The TYCO Model TY7158 Standard
Coverage Upright Sprinkler must be
maintained and serviced in accordance
with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this decision.
Inspection, testing, and maintenance
must be performed as indicated below
and in accordance with the local
requirements and/or national codes.
Any impairment must be immediately
corrected.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of any authorities having jurisdiction.
Contact the installing contractor or
product manufacturer regarding any
questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
2-3/8"
(60,3 mm)
WRENCH
FLAT
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
3/4"
NPT
Compression
1
3
2
6
5
4
Button
Frame
2-
-
1 3
Deector
Bulb
Assembly
-Sealing
-
5
-
4
Screw
-
6
WRENCH
RECESS
FIGURE 1
MODEL TY7158 STANDARD COVERAGE,
UPRIGHT STORAGE SPRINKLER, 16.8 K-FACTOR
FIGURE 2
W-T YPE 8
SPRINKLER WRENCH