Page 1 of 4 APRIL 2022 TFP338
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/model-
esfr-34-33_6-k-pen-sup-fast-res
Model ESFR-34
33.6 K-factor Pendent Sprinklers
Early Suppression, Fast Response
Technical
Data
Approvals
FM Approved
EAC Approved
Finish
Natural Brass
Physical Characteristics
Frame � � � � � � � � � � � � � � � � � � � � � � � � � � � � �Brass
Deflector � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze
Compression Screw � � � � � � � � � � Stainless Steel
Hook � � � � � � � � � � � � � � � � � � � � � � � � � � � � MONEL
Strut� � � � � � � � � � � � � � � � � � � � � � � � � � � � � MONEL
Link Assembly� � � � � � � � � � � � � � � � Solder, Nickel
Button ��������������������� Stainless Steel
Sealing Assembly ��Beryllium Nickel w/TEFLON
Additional Technical Data
See Table A
Operation
The fusible link assembly is com-
prised of two link halves that are joined
together by a thin layer of solder� When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
flowing water�
The Model ESFR-34 Sprinklers are pri-
marily used for ceiling-only sprinkler
protection of (but not limited to) the
following storage applications:
• Most encapsulated or non-encap-
sulated common materials including
cartoned, unexpanded plastics
For more specific criteria, refer to Table
B as well as the applicable design
standard�
The Model ESFR-34 can protect a
storage arrangement of 50 ft (15,2 m)
with a ceiling height of 55 ft (16,8 m)
without requiring in-rack sprinklers�
In addition, it can be installed with a
maximum centerline of thermal sensing
element-to-ceiling distance of 17 in�
(432 mm)�
NOTICE
The Model ESFR-34 Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of FM Global, in addi-
tion to the standards of any authorities
having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
In all cases, the appropriate FM instal-
lation standard, or other applicable
standard, must be referenced to ensure
applicability and to obtain complete
installation guidelines. The general
guidelines in this technical data sheet
are not intended to provide complete
installation criteria.
Sprinkler
Identification
Number
See Table A
General
Description
TYCO Model ESFR-34 Pendent Sprin-
klers are Early Suppression, Fast
Response Sprinklers having a nominal
K-factor of 33�6 (See Figure 1)� They are
suppression-mode sprinklers that are
especially advantageous as a means of
eliminating the use of in-rack sprinklers
when protecting high-piled storage�
TFP338
Page 2 of 4
Design
Criteria
The following general guidelines pro-
vided for the TYCO Model ESFR-34
Pendent Sprinklers can be used for a
quick reference�
FM Global Property Loss Prevention
Data Sheet 2-0, “Installation Guide-
lines for Automatic Sprinklers”, pro-
vides the installation guidelines for
the TYCO K33�6 sprinkler under the
heading of Storage Sprinkler, whereas
FM Global Property Loss Prevention
Data Sheet 8-9, “Storage of Class 1,
2, 3, 4 and Plastic Commodities”, pro-
vides its design guidelines� In all cases,
the appropriate FM Global installation
standard must be referenced to ensure
applicability and cannot be substituted
by other codes or standards� Table B
provides a summary of the design
and installation guidelines provided in
Data Sheets 2-0 and 8-9; they are not
intended to provide complete installa-
tion criteria�
Roof Construction
Refer to FM 2-0, Section 2�2
Ceiling Slope
Up to 10°
Maximum Coverage Area
100 ft² (9,3 m²)
Minimum Coverage Area
64 ft² (5,8 m²)
Maximum Spacing
• 12 ft (3,7 m) for building heights up
to 30 ft (9,1 m)
• 10 ft (3,0 m) for building heights
greater than 30 ft (9,1 m)
Minimum Spacing
8 ft (2,4 m)
Minimum Deflector to Top of
Storage
36 in� (914 mm)
Minimum Aisle Width
6 ft (1,8 m)
Centerline of Thermal Sensing
Element-to-Ceiling Distance
• Max� Distance: 17 in� (432 mm)
• Min� Distance: Refer to FM 2-0,
Section 2�2
Item Description
Sprinkler Identication Number (SIN) TY9286
K-factor, gpm/psi½(lpm/bar½)33�6 gpm/psi½(480 lpm/bar½)
Thread Size 1 1/4 in� NPT or ISO 7-R 1 1/4
Sprinkler Orientation Pendent
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
2
6
4
3
1
5
7
8
-
-
-
-
-
-
-
-
Deector
Hook
Compression
Assembly
Components:
Link
Frame
Screw
Strut
Assembly
Button
Assembly
Sealing
WRENCH
FLATS
CENTERLINE
OF THERMAL
ELEMENT
TEMPERATURE
RATING
5/8"
(15,9 mm)
NOMINAL
MAKE-IN
4-3/16"
(106,4 mm)
1-1/4" NPT
1
8
7
5
4
3
2
6
2-1/4"
(57,2 mm)
2-1/16"
(52,4 mm)
FIGURE 1
MODEL ESFR-34 (TY9286) EARLY SUPPRESSION, FAST RESPONSE
PENDENT SPRINKLER 33.6 K-FACTOR
TABLE A
MODEL ESFR-34 PENDENT SPRINKLER
TECHNICAL DATA
TFP338
Page 3 of 4
Installation
TYCO Model ESFR-34 Pendent Sprin-
klers must be installed in accordance
with this section�
General Instructions
Damage to the fusible Link Assem-
bly during installation can be avoided
by handling the sprinkler by the frame
arms only (that is, do not apply pres-
sure to the fusible Link Assembly),
and by using the appropriate sprinkler
wrench� Failure to do so can lead to an
unstable link assembly and premature
activation of the sprinkler� Damaged
sprinklers must be replaced�
A leak-tight 1 1/4 in� NPT sprinkler
joint should be obtained by applying a
minimum-to-maximum torque of 30 to
40 lb-ft (40,7 to 54,2 N∙m)� Higher levels
of torque can distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler�
Note: Install the Model ESFR-34
Pendent Sprinkler in the pendent posi-
tion (See Figure 2).
Step 1. With pipe-thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting� Do not apply pres-
sure to the Link Assembly, and handle
the Model ESFR-34 Pendent Sprinkler
only by the Frame arms�
Step 2. Use only the W-Type 26 Sprin-
kler Wrench (See Figure 2) to install
the Model ESFR-34 Pendent Sprinkler�
Fully engage (seat) the wrench recess
on the sprinkler wrench flats (See
Figure 1) and wrench-tighten�
Step 3. After installation, inspect the
Link Assembly of each Model ESFR-34
Pendent Sprinkler for damage� In par-
ticular, verify that the Link Assembly
and Hook are positioned as illustrated
in Figures 1 and 2, and that the Link
Assembly is not bent, creased, or
forced out of normal position in any
way� Replace damaged sprinklers�
Description Specification
Sprinkler Type QR Storage (ESFR)
Response Type QR
System Type Wet
Temperature Rating ºF (ºC) 165°F (74°C) and 212°F (100°C)
Open Frame (i.e., no solid shelves) Single, Double, Multiple Row,
or Portable Rack Storage of Class I-IV and Group A or B Plastics Refer to FM 2-0 and 8-9
Solid Pile or Palletized Storage of Class I-IV and Group A or B
Plastics Refer to FM 2-0 and 8-9
"SPRINKLER
SIDE"
TOWARDS
SPRINKLER
WRENCH
RECESS
FIGURE 2
W-T YPE 26
SPRINKLER WRENCH
TABLE B
MODEL ESFR-34 PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA
TFP338
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
MONEL is a registered trademarks of Special Metals Corporation; TEFLON is a trademark of The Chemours Company FC, LLC
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Care and
Maintenance
TYCO Model ESFR-34 Pendent Sprin-
klers must be maintained and serviced
in accordance with this section�
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action�
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced�
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory�
Modified sprinklers must be replaced�
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush�
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation� Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced�
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa-
tion (NFPA), such as NFPA 25, in addi-
tion to the standards of any authorities
having jurisdiction� Contact the install-
ing contractor or product manufacturer
with any questions�
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes�
Limited
Warranty
For warranty terms and conditions, visit
www�tyco-fire�com�
Ordering
Procedure
Contact your local distributor for avail-
ability� When placing an order, indicate
the full product name and Part Number
(P/N)�
Sprinkler Assemblies with
1 1/4 Inch NPT Thread Connection
Specify: Model ESFR-34 (TY9286),
K=33�6, Early Suppression, Fast
Response Pendent Sprinkler with
1 1/4 in� NPT thread connection,
(specify) temperature rating, Natural
Brass, P/N (specify):
16 5° F ( 74° C ) ������������������ 51-681-1-165
212°F (100°C) ����������������� 51-681-1-212
Special Order
Sprinkler Assemblies with
ISO 7-1 Thread Connections
Specify: Model ESFR-34 (TY9286),
K=33�6, Early Suppression, Fast
Response Pendent Sprinkler with
ISO 7-R 1 1/4 thread connection,
(specify) temperature rating, Natural
Brass, P/N (specify):
16 5° F ( 74° C ) ������������������51- 682-1-165
212°F (100°C) �����������������51-682-1-212
Sprinkler Wrench
Specify: W-Type 26 Sprinkler Wrench,
P/N 56-341-1-001

This manual suits for next models

1

Other Tyco Irrigation System manuals

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco ILLUSION User manual

Tyco

Tyco ILLUSION User manual

Tyco rapid response LFII Series Operating and maintenance instructions

Tyco

Tyco rapid response LFII Series Operating and maintenance instructions

Tyco TY-FRB Series Operator's manual

Tyco

Tyco TY-FRB Series Operator's manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco TY5332 User manual

Tyco

Tyco TY5332 User manual

Tyco EC-11 Series User manual

Tyco

Tyco EC-11 Series User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco DS-1 Series User manual

Tyco

Tyco DS-1 Series User manual

Tyco RFIII User manual

Tyco

Tyco RFIII User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco TY-FRL Series User manual

Tyco

Tyco TY-FRL Series User manual

Tyco TY2235 Instruction Manual

Tyco

Tyco TY2235 Instruction Manual

Tyco TY-FRL Series User manual

Tyco

Tyco TY-FRL Series User manual

Tyco LD User manual

Tyco

Tyco LD User manual

Tyco ELO-231 Series User manual

Tyco

Tyco ELO-231 Series User manual

Tyco rapid response LFII Series User manual

Tyco

Tyco rapid response LFII Series User manual

Tyco ESFR-1 Operating and maintenance instructions

Tyco

Tyco ESFR-1 Operating and maintenance instructions

Tyco FASTFLEX YN25 User manual

Tyco

Tyco FASTFLEX YN25 User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco TY-L Series User manual

Tyco

Tyco TY-L Series User manual

Tyco TY-L Series User manual

Tyco

Tyco TY-L Series User manual

Popular Irrigation System manuals by other brands

SNOWJOE Aquajoe AJ-OMS18-TRB manual

SNOWJOE

SNOWJOE Aquajoe AJ-OMS18-TRB manual

Viking VK2001 Technical data

Viking

Viking VK2001 Technical data

Reliable GL 112 quick start guide

Reliable

Reliable GL 112 quick start guide

Orbit WaterMaster Voyager Installation instruction

Orbit

Orbit WaterMaster Voyager Installation instruction

Eden 94135EDAMZ manual

Eden

Eden 94135EDAMZ manual

Toro 340 Series brochure

Toro

Toro 340 Series brochure

Tyco Fire Product CENTRAL LF instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL LF instruction manual

Toro Infinity Stealth-T installation guide

Toro

Toro Infinity Stealth-T installation guide

Eden WTX-500 Service manual

Eden

Eden WTX-500 Service manual

Johnson Controls tyco TY-B Series manual

Johnson Controls

Johnson Controls tyco TY-B Series manual

Tyco Fire Product CENTRAL A instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL A instruction manual

Reliable G5 Series manual

Reliable

Reliable G5 Series manual

Duramaxx Sprizzz manual

Duramaxx

Duramaxx Sprizzz manual

Reliable DD56-6 Bulletin

Reliable

Reliable DD56-6 Bulletin

Underhill Tracker Assembly instructions and operation manual

Underhill

Underhill Tracker Assembly instructions and operation manual

Cellfast MULTI sz IDEAL 52-060 user manual

Cellfast

Cellfast MULTI sz IDEAL 52-060 user manual

Viking FREEDOM VK4840 Technical data

Viking

Viking FREEDOM VK4840 Technical data

Reliable F156 Series manual

Reliable

Reliable F156 Series manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.