Vacon 10 User manual


safety vacon •1
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
1
This quick guide includes the essential steps for easy
installation and setup of your Vacon 10 frequency converter.
Before commissioning your drive, download and read the complete
Vacon 10 User Manual available at:
www.vacon.com -> Support & Downloads
1. SAFETY
ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO
CARRY OUT THE ELECTRICAL INSTALLATION!
This quick guide contains clearly marked warnings which are intended for your per-
sonal safety and to avoid any unintentional damage to the product or connected ap-
pliances.
Please read these warnings carefully:
The components of the power unit of the frequency converter
are live when Vacon 10 is connected to mains. Coming into
contact with this voltage is extremely dangerous and may
cause death or severe injury.
The motor terminals U, V, W (T1, T2, T3) and the possible brake
resistor terminals - / + are live when Vacon 10 is connected to
mains, even if the motor is not running.
The control I / O-terminals are isolated from the mains poten-
tial. However, the relay output terminals may have a danger-
ous control voltage present even when Vacon 10 is
disconnected from mains.
The earth leakage current of Vacon 10 frequency converters
exceeds 3.5 mA AC. According to standard EN61800-5-1, a
reinforced protective ground connection must be ensured.
See Chapter 7!
If the frequency converter is used as a part of a machine, the
machine manufacturer is responsible for providing the
machine with a main switch (EN 60204-1).
If Vacon 10 is disconnected from mains while running the
motor, it remains live if the motor is energized by the process.
In this case the motor functions as a generator feeding energy
to the frequency converter.
After disconnecting the frequency converter from the mains,
wait until the fan stops and the display segments or status
leds on the front panel go out. Wait 5 more minutes before
doing any work on Vacon 10 connections.
The motor can start automatically after a fault situation, if the
autoreset function has been activated.
!
Doc: DPD00714C, Released: 10.28.2011

2•vacon installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
2. INSTALLATION
2.1 Mechanical installation
There are two possible ways to mount Vacon 10 in the wall. either screw or DIN-rail
mounting.
Figure 1: Screw mounting, MI1 - MI3
Figure 2: DIN-rail mounting, MI1 - MI3
Note! See the mounting dimensions on the back of the drive.
Leave free space for cooling above (100 mm), below (50 mm), and on the sides
(20 mm) of Vacon 10! [ side-to-side installation allowed only if the ambient temper-
ature is below 40 °C.]
=
M5
MI3
MI1
=M4
MI2
=M5
LOC
REM
BACK
RESET
OK
LOC
REM
BACK
RESET
OK
LOC
REM
BACK
RESET
OK
12

installation vacon •3
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
.
Figure 3: Attaching the PE-plate and API cable support, MI1 - MI3
Attach this plate
BEFORE i nstalling
the p ow er ca bl es
Attach the support
AF TER installing
the power cables

4•vacon installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
2.2 Cabling and connections
2.2.1 Power cabling
Note! Tightening torque for power cables is 0.5 - 0.6 Nm
Figure 4: Vacon 10 power connections, MI1
Figure 5: Vacon 10 power connections, MI2 - MI3
1~ (230V)
3~ (230V, 400V)
Motor out
MAINS MOTOR
Strip the
plastic cable
coating for
360° earthing
L1 L2/N L3 U/ T1 V/ T2 W/T3R+ R-
1~ (230V)
3~(230V, 400V, 575V)
1~ (115V)
MAINS MOTOR
BRAKE
RESISTOR
External brake resistor
Motor out
Strip the
plastic
cable
coating
for 360°
earthing
3~(230V, 400V, 575V)

installation vacon •5
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
2
2.2.2 Control cabling
Figure 6: Open the lid MI1 - MI3
Figure 7: Install the control cables, MI1 - MI3
Strip the plastic
cable coating for
360°earthing
Control cable
tightening
torque: 0.4 Nm

6•vacon vacon 10 api
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
3
3. CONTROL I / O AND TERMINALS
Figure 3.1: Vacon 10 I / O
Terminal Signal Factory preset Description
1 +10Vre Ref. voltage out Maximum load 10 mA
2 AI1 Analog signal in 1 Freq. reference P) 0 - 10 V Ri = 200 k
(min)
3 GND I/O signal ground
6 24Vout 24V output for DI's %, max. load 50 mA
7 GND I/O signal ground
8 DI1 Digital input 1 Start forward P) 0 - +30 V Ri = 12 k min
9 DI2 Digital input 2 Start reverse P)
10 DI3 Digital input 3 Fault reset P)
A A RS485 signal A FB Communication Negative
B B RS485 signal B FB Communication Positive
4 AI2 Analog signal in 2 PI actual value P) 0(4) - 20 mA, Ri = 200
5 GND I/O signal ground
13 GND I/O signal ground
14 DI4 Digital input 4 Preset speed B0 P) 0 - +30 V Ri = 12 k
(min)
15 DI5 Digital input 5 Preset speed B1 P)
16 DI6 Digital input 6 External fault P)
18 AO Analog Output Output frequency P) 0(4) - 20 mA, RL = 500
20 DO Digital signal out Active = READY P) Open collector, max.
load 48V/50mA
22 RO 13 Relay out 1 Active = RUN P) Max. switching load:
250Vac/2A or 250Vdc/
0,4A
23 RO 14
24 RO 22 Relay out 2 Active = FAULT P) Max. switching load:
250Vac/2A or 250Vdc/
0,4A
25 RO 21
26 RO 24
Table 3.1: Vacon 10 default I/O configuration and connections
P) = Programmable function, see parameter lists and descriptions,
chapters 8 and 9.
20
ON
OFF
mA

navigation & startup vacon •7
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
4
4. NAVIGATION & STARTUP
4. 1 The main menus of Vacon 10
Figure 1: The main menu of Vacon 10
FWD REV I/O KEYPAD BUS
REF
MON
PA R
SYS SYS
SYS SYS
SYS SYS
SYS SYS
FAULTALARMSTOPREADY RUN
FWD REV I/O KEYPAD BUS
REF
PA R
FAULTALARMSTOPREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAU L TALARMSTO PREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAULTALARMSTOPREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAULTALARMSTOPREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAULTALARMSTOPREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAU LTALARMSTO PREAD Y RUN
MON
PRESS
PRESS
PRESS
PRESS
PRESS
FWD REV I/O KEYPAD BUS
REF
MON
PA R
FAULTALARMSTOPREADY R UN
PRESS
PRESS
OK
OK
OK
OK
OK
In this menu
you can
browse the
monitoring
values.
In this menu
you can
browse and
edit the
parameters.
Dispalys the
keypad reference
value
regardless of
the selected
contron place.
Here you will be
able to browse
system parameter
and fault
submenu.
MONITORING
MENU
REFERENCE
MENU
PA R A M E T E R
MENU
SYSTEM
MENU
Hz
Hz

8•vacon navigation & startup
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
4
4.2 Commissioning and startup wizard
4.2.1 Commissioning steps:
4.2.2 Startup wizard
Vacon 10 runs the startup wizard in first power-up. The wizard can be run by setting
SYS Par.4.2 =1. The following figures show the procedure.
NOTE! Running the startup wizard will always return all parameter
settings to their factory defaults!
Figure 2: Vacon 10 startup wizard (standard application)
1. Read safety instructions on page 1 7. Perform test run without motor, see the
User Manual at www.vacon.com
2. Secure the grounding and check that cables
comply with requirements
8. Run no-load tests without motor being con-
nected to the process
3. Check quality and quantity of cooling air 9. Perform an identification run (Par. ID631)
4. Check that all start / stop switches are in
STOP position
10. Connect the motor to the process and per-
form test run once again
5. Connect the drive to mains 11. Vacon 10 is now ready for use
6. Run the Startup wizard and set all necessary
parameters
Table 1: Commissioning steps
FAU LTALARMSTOPREADY RUN
REF
MON
PAR
SYS
FAU LTALARMSTOPREADY RUN
REF
MON
PAR
SYS
FAU LTALARMSTOPREADY RUN
REF
MON
PAR
SYS
FWD REV I/O KEY PAD BUS
FWD REV I/O KEY PAD BUS
FWD REV I/O KEY PAD BUS
FWD REV I/O KEY PAD BUS
2
1
4
3Change P1.3 value
with Up/Down button
and press OK to
comfirm
Perform the same
procedure for P1.4,
motor nominal current
Press OK enter
edit mode
Enter Pa r. menu, select
P1.3 motor nominal speed
FAU LTALARMSTOPREADY RUN
REF
MON
PAR
SYS
OK
OK
rpm
A

navigation & startup vacon •9
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
4
Figure 3: Drive setup
123
4
1,1 x
I
NMOT
1,1 x
I
NM OT
1,5 x
I
NMOT
Selections:
Parameters
affected:
P1.1 Motor Un (V)
P1.2 Motor fn (Hz)
P1.7 Current limit (A)
P1.8 Motor control mode
P1.15 Torque boost
P2.1 Control place
P2.2 Start function
P2.3 Stop function
P3.1 Min frequency
P3.2 Max frequency
P3.3 I/O reference
P4.2 Acc. time (s)
P4.3 Dec time (s)
*Same as drive voltage,
except in 115V drives
this value is 230V
P1.1 P1.2 P1.7 P1.8 P1.15 P2.1 P2.2 P2.3 P3.1 P3.2 P3.3 P4.2 P4.3
Startup wizard
showns par 17.1
number.
Press OK to enter
edit mode.
Press OK to
confirm
drive setup
Select between
0-3, see below!
0 = Basic
1 = Pump drive
2 = Fan drive
3 = High Torque
drive
V*
V*
V*
V*
50/60
Hz
50/60
Hz
50/60
Hz
50/60
Hz
50/60
Hz
50/60
Hz
50/60
Hz
50/60
Hz
0=
Not
used
0=
Frequecny
control
0=
Frequecny
control
0=
Frequecny
control
1=Open
loop speed
ontrol
0=
Not
used
0=
Not
used
1=
used
I/O
I/O
I/O
I/O
0=
Ramp
0=
Ramp
1=
Ramp
1=
Flying
0=
Ramp
0=
Coast
0=
Coast
0=
Coast
0 Hz
0 Hz
20 Hz
20 Hz
4=AI1
0-10V 3s 3s
5s 5s
1s 1s
20s20s
OK
OK
READY RUN STOP ALARM FAULT
REF
MON
PAR
SYS
READY RUN STOP ALARM FAULT
FWD REV I/O KEYPAD BUS FWD REV I/O KEYPAD BUS FWD REV I/O KEYPAD BUS
READY RUN STOP ALARM FAULT
REF
MON
PAR
SYS
REF
MON
PAR
SYS
READY RUN STOP ALARM FAULT
REF
MON
PAR
SYS
FWD REV I/O KEYPAD BUS
1,5 x
I
NMOT
4=AI1
0-10V
4=AI1
0-10V
4=AI1
0-10V

10 •vacon monitoring & parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
5
5. MONITORING & PARAMETERS
NOTE! This guide is for Vacon 10 standard application, if you are using a special ap-
plication, please download the application manual on: www.vacon.com -> Support
& downloads.
5.1 Monitoring values
Code Monitoring signal Unit ID Description
V1.1 Output frequency Hz 1 Output frequency to motor
V1.2 Frequency reference Hz 25 Frequency reference to motor con-
trol
V1.3 Motor speed rpm 2 Calculated motor speed
V1.4 Motor current A 3 Measured motor current
V1.5 Motor torque % 4 Calculated actual / nominal torque
of the motor
V1.6 Output Power KW 79 Output power from drive to motor
V1.7 Motor voltage V 6 Motor voltage
V1.8 DC-link voltage V 7 Measured DC-link voltage
V1.9 Drive temperature °C 8 Heatsink temperature
V1.10 Motor temperature % 9 Calculated motor temperature
V2.1 Analog input 1 % 13 AI1 signal range in percent of used
range
V2.2 Analog input 2 % 14 AI2 signal range in percent of used
range
V2.3 Analog output % 26 AO signal range in percent of used
range
V2.4 Digital input status DI1,
DI2, DI3 15 Digital input status
V2.5 Digital input status DI4,
DI5, DI6 16 Digital input status
V2.6 RO1, RO2, DO 17 Relay / digital output status
V4.1 PI setpoint % 20 Regulator setpoint
V4.2 PI feedback value % 21 Regulator actual value
V4.3 PI error % 22 Regulator error
V4.4 PI output % 23 Regulator output
Table 5.1: Vacon 10 monitoring signals

monitoring & parameters vacon •11
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.2 Quick setup parameters (Virtual menu, shows when par. 17.2 = 1)
Code Parameter Min Max Unit Default ID Note
Motor nominal
voltage 180 690 V Varies 110 Check rating plate on the
motor.
Motor nominal
frequency 30,00 320,00 Hz 50,00 /
60,00 111 Check rating plate on the
motor.
Motor nominal
speed 30 20000 rpm 1440 /
1720 112 Default applies for a 4-
pole motor.
Motor nominal
current
0,2 x
INunit
2,0 x
INunit AINunit 113 Check rating plate on the
motor.
Motor cos
(Power Factor)
0,30 1,00 0,85 120 Check rating plate on the
motor.
Current limit 0,2 x
INunit
2.0 x
INunit A1.5 x
INunit 107 Maximum motor current
Torque boost 0 1 0 109 0= Not used
1= Used
P2.1 Remote control
place 1 selection 01 0 172
0= I / O terminal
1= Fieldbus
Start function 010505
0= Ramp
1= Flying start
Stop function 010506
0= Coasting
1= Ramp
Min frequency 0,00 P3.2 Hz 0,00 101 Minimum freq reference
Max frequency P3.1 320,00 Hz 50,00 /
60,00 102 Maximum freq refer-
ence
P3.3
Remote Control
Place 1 frequency
reference selec-
tion
16 4 117
1= Preset Speeds 0-7
2= Keypad
3= Fieldbus
4= AI1
5= AI2
6= PI
P3.4 Preset speed 0 P3.1 P3.2 Hz 5,00 124 Activated by digital
inputs
P3.5 Preset speed 1 P3.1 P3.2 Hz 10,00 105 Activated by digital
inputs
P3.6 Preset speed 2 P3.1 P3.2 Hz 15,00 106 Activated by digital
inputs
P3.7 Preset speed 3 P3.1 P3.2 Hz 20,00 126 Activated by digital
inputs
Table 5.1: Quick setup parameters
P1.1
P1.2
P1.3
P1.4
P1.5
P1.7
P1.15
P2.2
P2.3
P3.1
P3.2

12 •vacon monitoring & parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
5
Acceleration time
1 0,1 3000,0 s 3,0 103
Acceleration time from
0 Hz to maximum fre-
quency.
Deceleration time
1 0,1 3000,0 s 3,0 104
Deceleration time from
maximum frequency to
0 Hz.
P6.1 AI1 Signal range 0 1 0 379
0= 0 - 100%
1= 20% - 100%
20% is the same as 2 V
minimum signal level.
P6.5 AI2 Signal range 0 1 0 390
0= 0 - 100%
1= 20% - 100%
20% is the same as 4
mA minimum signal
level.
Automatic reset 0 1 0 731 0= Disable
1= Enable
P17.2 Parameter
conceal 0 1 1 115
0= All parameters visi-
ble
1= Only quick setup
parameter group visible
Code Parameter Min Max Unit Default ID Note
Table 5.1: Quick setup parameters
P4.2
P4.3
P14.1

monitoring & parameters vacon •13
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.3 Motor settings (Control panel: Menu PAR -> P1)
Code Parameter Min Max Unit Default ID Note
Motor nominal
voltage 180 690 V Varies 110 Check rating plate on the
motor
Motor nominal fre-
quency 30,00 320,00 Hz 50,00 /
60,00 111 Check rating plate on the
motor
Motor nominal
speed 30 20000 rpm 1440 /
1720 112 Default applies for a 4-pole
motor.
Motor nominal
current
0,2 x
INunit
2,0 x
INunit AINunit 113 Check rating plate on the
motor
Motor cos
(Power Factor)
0,30 1,00 0,85 120 Check rating plate on the
motor
Motor type 0 1 0 650 0= Induction
1= Permanent magnet
Current limit 0,2 x
INunit
2.0 x
INunit A1.5 x
INunit 107 Maximum motor current
Motor control
mode 01 0600
0= Frequency control
1= Open loop speed control
U / f ratio 0 2 0 108
0= Linear
1= Quadratic
2= Programmable
Field weakening
point 8,00 320,00 Hz 50,00 /
60,00 602 Field weakening point fre-
quency
Field weakening
point voltage 10,00 200,00 % 100,00 603 Voltage at field weakening
point as % of Unmot
U / f mid point
frequency 0,00 P1.10 Hz 50,00 /
60,00 604 Mid point frequency for
programmable U / f
U / f mid point
voltage 0,00 P1.11 % 100,00 605
Mid point voltage for pro-
grammable U / f as % of
Unmot
Zero freq voltage 0,00 40,00 % Varies 606 Voltage at 0 Hz as % of
Unmot
Torque Boost 0 1 0 109 0= Disabled
1= Enabled
Switching fre-
quency 1,5 16,0 kHz 4,0 / 2,0 601
PWM frequency. If values
are higher than default,
reduce the current capacity
Brake Chopper 0 2 0 504
0 = Disabled
1 = Enabled: Always
2 = Run state
Table 5.2: Motor settings
P1.1
P1.2
P1.3
P1.4
P1.5
P1.6
P1.7
P1.8
P1.9
P1.10
P1.11
P1.12
P1.13
P1.14
P1.15
P1.16
P1.17

14 •vacon monitoring & parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
5
NOTE! These parameters are shown, when P17.2 = 0.
5.4 Start / stop setup (Control panel: Menu PAR -> P2)
Motor identifica-
tion 01 0631
0= Not active
1= Standstill identification
(need run command within
20 s to activate)
Rs voltage drop 0,00 100,00 % 0,00 675
Voltage drop over motor
windings as % of Unmot at
nominal current.
Overvoltage con-
troller 02 1607
0 = Disabled
1 = Enabled, Standard
mode
2 = Enabled, Shock load
mode
Undervoltage
controller 01 1608
0= Disable
1= Enable
Code Parameter Min Max Unit Default ID Note
P2.1 Remote Control
Place 1 Selection 01 0 172 0= I / O terminals
1= Fieldbus
Start function 01 0 505 0= Ramp
1= Flying start
Stop function 01 0 506 0= Coasting
1= Ramp
P2.4 I / O Start / Stop
logic 0 3 2 300
I / O control I / O control
signal 1 signal 2
0Forward Backward
1Fwd(edge) Inverted Stop
2Fwd(edge) Bwd(edge)
3Start Reverse
P2.5 Local / Remote 0 1 0 211 0= Remote control
1= Local control
P2.6 Keypad control
direction 0 1 0 123 0= Forward
1= Backward
Table 5.3: Start / stop setup
Code Parameter Min Max Unit Default ID Note
Table 5.2: Motor settings
P1.18
P1.19
P1.20
P1.21
P2.2
P2.3

monitoring & parameters vacon •15
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.5 Frequency references (Control panel: Menu PAR -> P3)
NOTE! These parameters are shown, when P17.2 = 0.
Code Parameter Min Max Unit Default ID Note
Min frequency 0,00 P3.2 Hz 0,00 101
Max frequency P3.1 320,00 Hz 50,00 /
60,00 102
P3.3
Remote Control
Place 1 fre-
quency refer-
ence selection
1 6 4 117
1= Preset Speeds 0
2= Keypad
3= Fieldbus
4= AI1
5= AI2
6= PI
P3.4 Preset speed 0 P3.1 P3.2 Hz 5,00 124 Activated by digital inputs
P3.5 Preset speed 1 P3.1 P3.2 Hz 10,00 105 Activated by digital inputs
P3.6 Preset speed 2 P3.1 P3.2 Hz 15,00 106 Activated by digital inputs
P3.7 Preset speed 3 P3.1 P3.2 Hz 20,00 126 Activated by digital inputs
P3.8 Preset speed 4 P3.1 P3.2 Hz 25,00 127 Activated by digital inputs
P3.9 Preset speed 5 P3.1 P3.2 Hz 30,00 128 Activated by digital inputs
P3.10 Preset speed 6 P3.1 P3.2 Hz 40,00 129 Activated by digital inputs
P3.11 Preset speed 7 P3.1 P3.2 Hz 50,00 130 Activated by digital inputs
Table 5.4: Frequency references
P3.1
P3.2

16 •vacon monitoring & parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
5
5.6 Ramps and brakes setup (Control panel: Menu PAR -> P4)
Code Parameter Min Max Unit Default ID Note
Ramp S-shape 0,0 10,0 s 0,0 500 0= Linear
>0 = S-curve ramp time
Acceleration time 1 0,1 3000,0 s 3,0 103
Deceleration time 1 0,1 3000,0 s 3,0 104
Ramp S-shape 2 0,0 10,0 s 0,0 501
Acceleration time 2 0,1 3000,0 s 10,0 502
Deceleration time 2 0,1 3000,0 s 10,0 503
Flux Braking 0 3 0 520
0= Off
1= Deceleration
2= Chopper
3= Full Mode
Flux Braking Cur-
rent
0,5 x
INunit
2,0 x
INunit AINunit 519
DC Braking Current 0,3 x
INunit
2,0 x
INunit AINunit 507
Defines the current
injected into the motor
during DC brakeing.
Stop DC current
time 0,00 600,00 s 0,00 508
Determines if braking is
ON or OFF and the brak-
ing time of the DC-brake
when the motor is stop-
ping.
0= Not active
Stop DC current
frequency 0,10 10,00 Hz 1,50 515
The output frequency at
which the DC-braking is
applied.
Start DC current
time 0,00 600,00 s 0,00 516 0= Not active
Table 5.5: Ramps and brakes setup
P4.1
P4.2
P4.3
P4.4
P4.5
P4.6
P4.7
P4.8
P4.9
P4.10
P4.11
P4.12

monitoring & parameters vacon •17
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.7 Digital inputs (Control panel: Menu PAR -> P5)
5.8 Analogue inputs (Control panel: Menu PAR -> P6)
Code Parameter Min Max Unit Default ID Note
P5.1 I / O control signal 1 0 6 1 403
0= Not used
1= DI1
2= DI2
3= DI3
4= DI4
5= DI5
6= DI6
P5.2 I / O control signal 2 0 6 2 404 As parameter 5.1
P5.3 Reverse 0 6 0 412 As parameter 5.1
P5.4 Ext. fault Close 0 6 6 405 As parameter 5.1
P5.5 Ext. fault Open 0 6 0 406 As parameter 5.1
P5.6 Fault reset 0 6 3 414 As parameter 5.1
P5.7 Run enable 0 6 0 407 As parameter 5.1
P5.8 Preset speed B0 0 6 4 419 As parameter 5.1
P5.9 Preset speed B1 0 6 5 420 As parameter 5.1
P5.10 Preset speed B2 0 6 0 421 As parameter 5.1
P5.11 Ramp time 2 selec-
tion 0 6 0 408 As parameter 5.1
P5.12 Disable PI 0 6 0 1020 As parameter 5.1
P5.13 Force to I/O 0 6 0 409 As parameter 5.1
Table 5.6: Digital inputs
Co
de Parameter Min Max Unit Default ID Note
P6.1 AI1 Signal range 0 1 0 379 0= 0 - 100% ( 0 - 10 V)
1= 20% - 100% ( 2 - 10 V)
P6.2 AI1 Custom min -100,00 100,00 % 0,00 380 0,00 = no min scaling
P6.3 AI1 Custom max -100,00 300,00 % 100,00 381 100,00 = no max scaling
P6.4 AI1 filter time 0,0 10,0 s 0,1 378 0 = no filtering
P6.5 AI2 signal range 0 1 0 390
0 = 0 - 100% ( 0 - 20 mA)
1 = 20% - 100% (4 -20
mA)
P6.6 AI2 Custom min -100,00 100,00 % 0,00 391 0,00 = no min scaling
P6.7 AI2 Custom max -100,00 300,00 % 100,00 392 100,00 = no max scaling
P6.8 AI2 filter time 0,0 10,0 s 0,1 389 0= no filtering
Table 5.7: Analogue inputs

18 •vacon monitoring & parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
5
5.9 Digital outputs (Control panel: Menu PAR -> P8)
5.10 Analogue outputs (Control panel: Menu PAR -> P9)
Code Parameter Min Max Unit Default ID Selections
P8.1 RO1 signal
selection 011 2313
0= Not used
1= Ready
2= Run
3= Fault
4= Fault Inverted
5= Warning
6= Reversed
7= At Speed
8= Motor regulator active
9= FB Control Word.B13
10 = FB Control Word.B14
11 = FB Control Word.B15
P8.2 RO2 signal sel-
cetion 0 11 3 314 As parameter 8.1
P8.3 DO1 signal sel-
cetion 0 11 1 312 As parameter 8.1
P8.4 RO2 inversion 0 1 0 489 0= No inversion
1= Inverted
Table 5.8: Digital outputs
Code Parameter Min Max Unit Default ID Selections
P9.1 Analog output
signal selection 0 4 1 307
0= Not used
1= Output freq. (0-fmax)
2= Output current (0-InMotor)
3= Motor torque (0-TnMotor)
4= PI output (0 - 100%)
P9.2 Analog output
minimum 0 1 0 310 0 = 0 mA
1 = 4 mA
Table 5.9: Analogue outputs

monitoring & parameters vacon •19
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.11 Protections (Control panel: Menu PAR -> P13)
NOTE! These parameters are shown, when P17.2 = 0.
5.12 Fault autoreset parameters (Control panel: Menu PAR -> P14)
NOTE! These parameters are shown, when P17.2 = 0.
Code Parameter Min Max Unit Default ID Note
P13.1 Analog Input low
fault 0 2 1 700
0 = No action
1= Alarm
2= Fault: Coast
Under voltage
fault 1 2 2 727
1 = No response (no fault
generated but drive still
stops modulation)
2 = Fault:Coast
Earth fault 02 2 703 As parameter 13.1
Output Phase
Fault 02 2 702 As parameter 13.1
Stall protection 02 0 709 As parameter 13.1
Under load pro-
tection 02 0 713 As parameter 13.1
Motor thermal
protection 02 2 704 As parameter 13.1
Mtp:Ambient
temperature -20 100 °C 40 705 Environment tempera-
tion
Mtp:Zero speed
cooling 0,0 150,0 % 40,0 706 Cooling as % at 0 speed
Mtp:Thermal time
constant 1200 min 45 707 Motor thermal time con-
stant
Table 5.10: Protections
Code Parameter Min Max Unit Default ID Note
Automatic Reset 0 1 0 731 0= Disabled
1 = Enable
Wait time 0,10 10,00 s 0,50 717 Waiting time after fault
Trial time 0,00 60,00 s 30,00 718 Maximum time for trials
Restart Function 0 2 2 719
0= Ramping
1 = Flying
2= From Start Function
Table 5.11: Fault autoreset parameters
P13.2
P13.3
P13.4
P13.5
P13.6
P13.7
P13.8
P13.9
P13.10
P14.1
P14.2
P14.3
P14.5
Other manuals for 10
8
Table of contents
Other Vacon Controllers manuals

Vacon
Vacon 100 HVAC User manual

Vacon
Vacon 100 INDUSTRIAL User manual

Vacon
Vacon 100 HVAC Instructions for use

Vacon
Vacon NX series User manual

Vacon
Vacon NX User manual

Vacon
Vacon 20 User manual

Vacon
Vacon 100 INDUSTRIAL User manual

Vacon
Vacon 500X User manual

Vacon
Vacon NX User manual

Vacon
Vacon 10 User manual

Vacon
Vacon 10 User manual

Vacon
Vacon 20 SERIES Instructions for use

Vacon
Vacon 20 x User manual

Vacon
Vacon 10 User manual

Vacon
Vacon 100 INDUSTRIAL User guide

Vacon
Vacon 10 User manual

Vacon
Vacon 10 Installation instructions

Vacon
Vacon 20 x Maintenance and service guide

Vacon
Vacon NX ACTIVE FRONT END II Instructions for use

Vacon
Vacon 20 x User manual