IC-664 INSTALLATION GUIDE
1
WARNINGS AND PRECAUTIONS
Although the manufacturer has made every effort to ensure the accuracy of the
information contained herein, this document is subject to change without notice due to
ongoing product development.
WARNINGS AND PRECAUTIONS
Defective equipment, probe failure, blown fuses and/or tripped breakers may prove
harmful to the contents of the building. Therefore it is strongly recommended to install
backup devices and alarm or warning devices. Spare equipment should also be
available at the user’s site. Equipment manufactured by the manufacturer is protected
against normal line surges. High surges caused by thunder storms or power supply
equipment may damage this equipment. For added security against line voltage surges
it is recommended that surge and noise suppression devices be installed at the
electrical distribution panel. Use of shielded cable for probes is recommended for
protection against lightning. These devices are available from most electrical supply
distributors.
RECOMMENDATIONS
The manufacturer recommends that all installation procedures described herein be
performed by a qualified electrician or installation technician. Further more the
manufacturer recommends to test all the functions and equipment connected to the IC,
including the alarm system and backup devices, after installation, after changes to the
installation and every month after that.
Fuse verification and replacement, as well as the proper setting of control values shall
be the responsibility of the owner of this equipment.
www.monitrol.com

IC-664 INSTALLATION GUIDE
2
TABLE OF CONTENTS
1. Unpacking................................................................................................................................ 3
2. Mounting Hardware Required................................................................................................ 3
3. General installation guidelines..............................................................................................4
3.1 IC-664 Control ..................................................................................................................... 4
3.2 Electrical Cables.................................................................................................................. 4
3.3 Electrical Power................................................................................................................... 4
4. Mounting.................................................................................................................................. 5
5. Control Description ................................................................................................................ 6
6. Connection Procedure ........................................................................................................... 8
6.1 General Wiring Diagram......................................................................................................8
6.2 Detailed Wiring Diagrams....................................................................................................8
6.2.1 Typical Sensor Wiring for Probes ................................................................................. 8
6.2.2 Typical Power Backup Wiring ....................................................................................... 9
6.2.3 Typical Thermostat Backup Wiring ............................................................................. 10
6.2.4 Typical Alarm Connection Wiring................................................................................ 12
6.2.5 Communication Port Connection ................................................................................ 12
7. Powering Up Procedure ....................................................................................................... 12
7.1 Adjust the Line Voltage Selection Switch .......................................................................... 12
7.2 Verify all Connections........................................................................................................ 12
7.3 Download the Configuration (if necessary) ....................................................................... 13
7.4 Hermetically Close the IC-664........................................................................................... 13
7.5 Troubleshooting................................................................................................................. 14
7.6 IC-664 Compatible Probes ................................................................................................ 15
7.7 IC-664 Compatible Modules.............................................................................................. 15
8. Specifications........................................................................................................................ 16
9. Limited Warranty................................................................................................................... 17
TABLE OF FIGURES
FIGURE NO. 1 Mounting Position and Devices....................................................................... 5
FIGURE NO. 2 The IC-664 Control ............................................................................................ 6
FIGURE NO. 3 IC-664 Electronic Main Board .......................................................................... 7
FIGURE NO. 4 Typical Temperature Probe Wiring.................................................................. 8
FIGURE NO. 5 Typical Power Backup Wiring.......................................................................... 9
FIGURE NO. 6 Typical Thermostat Backup Wiring ............................................................... 10
FIGURE NO. 7 Typical Alarm Connection Wiring.................................................................. 12
www.monitrol.com

IC-664 INSTALLATION GUIDE
3
The purpose of this guide is to fully inform the electrician on proper wiring and installation
procedures for the IC-664. Full conformity of the Installation and User’s Guide will lead to a
successful installation and proper functioning of the IC-664 control .
1. Unpacking
Unpack the IC-664 and inspect contents for damage. Should the contents appear to be
damaged, contact your local distributor to arrange for the return of damaged the material.
The package should contain the following standard item :
• 1 IC-664
• 1 Temperature probe
• 1 Spare power fuse
• 1 Spare alarm fuse
• 1 Spare FAN 1 and FAN 3 or FAN 2 and FAN 4 fuse
• 1 Installation Guide
• 1 User’s Guide package including list of equipment, wiring diagrams, parameter list, and
detailed description of the configuration.
2. Mounting Hardware Required
This is the list of the mounting hardware needed which is not included with the product :
• Shielded two-wire cable, AWG #18 (to extend temperature probes)
• Shielded two-wire low capacitance, AWG #18 to #22 (used for communication, or any other
module, except for temperature probes)
• 3 screws : 1 #8 X 1’’, 2 #6 X 1’’ (to hang the unit onto the wall)
• Screwdrivers
• Hammer (to punch out the knock outs)
• Soldering iron kit or approved sealed connectors
The manufacturer recommends that the following installation instructions be adhered as closely
as possible and all work be performed by a certified electrician. Failure to do so may void the
warranty.
www.monitrol.com

IC-664 INSTALLATION GUIDE
4
3. General installation guidelines
3.1 IC-664 Control
• It is recommended to install the unit in a hallway to limit the IC-664’s exposure to noxious gases.
• In order to avoid condensation problems inside the controller, it is recommended to install the
IC-664 on an inside wall. If it is not possible, use spacers to have an air gap between the wall
and the IC-664.
• It is required to install the IC-664 side up with the cable entry holes facing down (see figure 1).
• The enclosure is watertight, but not splash proof or immersion proof. DO NOT WATER the
control. Cover it carefully with plastic when cleaning the room.
• The IC-664 should be installed in easy access location but away from damaging elements
(heat, cold, water, direct sunlight, …).
• It is recommended to punch out knock outs by striking them at the bottom near the back of
the case (see figure 2).
• Do not drill the face, the side, the top or the underside of the control.
• Do not install the IC-664 control near high voltage equipment, power supply or transformer.
3.2 Electrical Cables
• All electrical cables must be installed according to local wiring codes.
• All cable shields must be connected to the IC-664 power ground only, except for the cable
connected to the optional PC interface (see SVPC-40 guide). The shield is needed to protect
the IC-664 and the modules against any electromagnetic interference generated by lightning
or nearby operating machinery.
• Never use the shield as a conductor.
• Connect only one end of the shield to the ground of the IC-664.
• Use separate conduit for the low voltage cables (communication and probes) and the high
voltage cables. There must be at least 1 foot (30 cm) between low voltage and high voltage
conduit.
• If a low voltage cable have to cross over a high voltage cable, make this crossing at 90°.
• All cable connections must be soldered or done with approved sealed connectors.
• Probe cables must be 500 ‘ (150m) or less.
• Communication cables must be 750 ‘ (250m) or less.
• It is prohibited to use overhead cable outside the building.
3.3 Electrical Power
• Protection from electrical surge should be included in the planning of each installation.
• Every module should have a separate breaker to avoid serious consequences.
• Certain control modules (VSM-2, VSM-2/2, VPM-2, VPM-1 and CIP-1) require the same
phase and same voltage as the IC-664 to operate.
• It is strongly recommended to put a backup power source to ensure life-sustaining conditions
in case of power failure (see figure 5).
• It is also strongly recommended to put a backup thermostat to sufficient fan and heating
system parallel to the IC-664 module output (see figure 6).
• Backup system and alarm must be thoroughly tested and verified as working properly before
using the ventilation system.
www.monitrol.com

IC-664 INSTALLATION GUIDE
5
4. Mounting
• Use a screwdriver to remove the 3 screws of the top faceplate and the 3 screws of the
access panel.
• Open both faceplates.
• Install mounting screw on wall and hang the unit in place by sliding the rear mounting hole of
the IC-664 over the screw (see figure 1).
• Install two more screws to secure the IC-664 in place using the bottom mounting holes.
FIGURE NO. 1 Mounting Position and Devices
REAR VIEW
TOP MOUNTING
HOLE
BOTTOM
MOUNTING HOLES
This side up
Screw Sizes:
Top mounting hole : #8 X 1”
Bottom mounting holes: #6 X 1”
www.monitrol.com

IC-664 INSTALLATION GUIDE
6
5. Control Description
FIGURE NO. 2 The IC-664 Control
KNOCK OUTS
provided for ease
of installation
FRONT VIEW
BOTTOM VUE
IC-
75.7
1 s onde temp. EST
DEG FAHRENHEIT
1 Output 1
2 2Output
3 3Output
4 4Output
5 5Output
6 6Output
7 7Output
8 8Output
9 9Output
10 10Output
CONFIGURATION
1 Parameter 1
2 Parameter 2
3 Parameter 3
4 Parameter 4
5 Parameter 5
6 Parameter 6
7 Parameter 7
8 Parameter 8
9 Parameter 9
10 Parameter 10
11 Parameter 11
12 Parameter 12
13 Parameter 13
14 Parameter 14
15 Parameter 15
16 Parameter 16
17 Parameter 17
18 Parameter 18
19 Parameter 19
20 Parameter 20
www.monitrol.com

IC-664 INSTALLATION GUIDE
7
FIGURE NO. 3 IC-664 Electronic Main Board
10A SLO-BLO
250V
F1
0.125A
250V
Slo-Blo
10A SLO-BLO
250V
F5
30V/1A MAX
F4
F1
0.125A
250V
Slo-Blo
F1
0.125A
250V
Slo-Blo
F3
FAST-
ACT-
ING
TO POWER
SOURCE
www.monitrol.com

IC-664 INSTALLATION GUIDE
8
6. Connection Procedure
6.1 General Wiring Diagram
Since the IC-664 is a configurable control, the general wiring diagram comes with the User’s
Guide particular to this installation.
6.2 Detailed Wiring Diagrams
6.2.1 Typical Sensor Wiring for Probes
The inside temperature sensor should be located in the area which gives the most accurate
temperature reading to achieve optimum ventilation. It must be located in an area protected
from operating machinery, animal bites, personnel or anything that could damage the sensor.
See also “3. General information guidelines”.
If it is an outside temperature sensor, it must be installed in a location which is not influenced by
heat generated by the building or direct sunlight.
FIGURE NO. 4 Typical Temperature Probe Wiring
SHIELD
GND
PROBE
8VAC
100mA
PRB 1
PRB 2
PRB 3
PRB 4
www.monitrol.com

IC-664 INSTALLATION GUIDE
9
6.2.2 Typical Power Backup Wiring
A backup relay (DPDT) connects to the power source 1 in normal operation but will switch to the
power source 2 if source 1 is disabled. The backup relay must be selected to ensure it is able to
support the required power load.
FIGURE NO. 5 Typical Power Backup Wiring
8 PIN RELAY DPDT
(OMRON model MK2EP-UA-AC120)
3
4
5
6
2
1
8
7
NO 2
NO 1
NC 1
NC 2
COM 2
COM 1
L2/N GND
L1
3
4
5
6
2
1
8
7
L2 L1 GND
source 1
DISTRIBUTION
PANEL
L2 L1 GND
N
LINE
115/230 VAC
source 2
DISTRIBUTION
PANEL
LINE
115/230 VAC
www.monitrol.com
Table of contents
Other Varifan Control System manuals

Varifan
Varifan ECS 5M User manual

Varifan
Varifan ECS-1M User manual

Varifan
Varifan IC-610 User manual

Varifan
Varifan DIP-1/115 Operation manual

Varifan
Varifan SVIM-1LE User manual

Varifan
Varifan VPM-1 User manual

Varifan
Varifan CM10-2 User manual

Varifan
Varifan MST-5C User manual

Varifan
Varifan DIP-1C Operation manual

Varifan
Varifan CPS-3M User manual