Vega VEGASWING 61 User manual

Operating Instructions
VEGASWING 61
-transistor (NPN/PNP)
Vibration

Contents
1About this document
1.1Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2Target group . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3Symbolism used . . . . . . . . . . . . . . . . . . . . . . . 5
2For your safety
2.1Authorised personnel . . . . . . . . . . . . . . . . . . . . 6
2.2Appropriate use. . . . . . . . . . . . . . . . . . . . . . . . 6
2.3Warning about misuse . . . . . . . . . . . . . . . . . . . 6
2.4General safety instructions . . . . . . . . . . . . . . . . 6
2.5CE conformity . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.6SIL conformity . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.7Safety instructions for Ex areas . . . . . . . . . . . . 7
2.8Manufacturer declaration . . . . . . . . . . . . . . . . . 7
2.9Environmental instructions . . . . . . . . . . . . . . . . 8
3Product description
3.1Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.2Principle of operation. . . . . . . . . . . . . . . . . . . . 9
3.3Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.4Storage and transport . . . . . . . . . . . . . . . . . . . 11
4Mounting
4.1General instructions. . . . . . . . . . . . . . . . . . . . . 12
4.2Mounting instructions. . . . . . . . . . . . . . . . . . . . 15
5Connecting to power supply
5.1Preparing the connection . . . . . . . . . . . . . . . . . 17
5.2Connection procedure . . . . . . . . . . . . . . . . . . . 17
5.3Wiring plan,single chamber housing. . . . . . . . . 18
5.4Wiring plan -version IP 66/IP 68,1bar. . . . . . . 20
6Set up
6.1In general . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.2Adjustment elements . . . . . . . . . . . . . . . . . . . . 21
6.3Function chart . . . . . . . . . . . . . . . . . . . . . . . . . 22
7Maintenance and fault rectification
7.1Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.2Fault rectification . . . . . . . . . . . . . . . . . . . . . . . 24
7.3Instrument repair . . . . . . . . . . . . . . . . . . . . . . . 25
2VEGASWING 61 - - transistor (NPN/PNP)
Contents
29225-EN-070614

8Dismounting
8.1Dismounting steps . . . . . . . . . . . . . . . . . . . . . . 26
8.2Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
9Supplement
9.1Technical data. . . . . . . . . . . . . . . . . . . . . . . . . 27
9.2Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
9.3Industrial property rights. . . . . . . . . . . . . . . . . . 38
9.4Trademark . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Supplementary documentation
Information:
Depending on the ordered version,supplementary documen-
tation belongs to the scope of delivery.You find this
documentation in chapter "Product description".
Instructions manuals for accessories and replacement
parts
Tip:
To ensure reliable setup and operation of your VEGASWING
61,we offer accessories and replacement parts.The
associated documents are:
lOperating instructions manual "Remote housing -VEGA-
SWING"
lOperating instructions manual "Oscillator VEGASWING
series 60"
VEGASWING 61 - - transistor (NPN/PNP)3
Contents
29225-EN-070614

1About this document
1.1Function
This operating instructions manual provides all the information
you need for mounting,connection and setup as well as
important instructions for maintenance and fault rectification.
Please read this information before putting the instrument into
operation and keep this manual accessible in the immediate
vicinity of the device.
1.2Target group
This operating instructions manual is directed to trained
personnel.The contents of this manual should be made
available to these personnel and put into practice by them.
1.3Symbolism used
Information,tip,note
This symbol indicates helpful additional information.
Caution:If this warning is ignored,faults or malfunc-
tions can result.
Warning:If this warning is ignored,injury to persons and/or
serious damage to the instrument can result.
Danger:If this warning is ignored,serious injury to persons
and/or destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
lList
The dot set in front indicates a list with no implied sequence.
àAction
This arrow indicates a single action.
1Sequence
Numbers set in front indicate successive steps in a procedure.
4VEGASWING 61 - - transistor (NPN/PNP)
About this document
29225-EN-070614

2For your safety
2.1Authorised personnel
All operations described in this operating instructions manual
must be carried out only by trained specialist personnel
authorised by the operator.
During work on and with the device the required personal
protection equipment must always be worn.
2.2Appropriate use
VEGASWING 61 is a sensor for level detection.
You can find detailed information on the application range in
chapter "Product description".
2.3Warning about misuse
Inappropriate or incorrect use of the instrument can give rise to
application-specific hazards,e.g.vessel overfill or damage to
system components through incorrect mounting or adjustment.
2.4General safety instructions
This is a high-tech instrument requiring the strict observance of
standard regulations and guidelines.The user must take note
of the safety instructions in this operating instructions manual,
the country-specific installation standards as well as all
prevailing safety regulations and accident prevention rules.
The instrument must only be operated in a technically flawless
and reliable condition.The operator is responsible for trouble-
free operation of the instrument.
The user is also obliged to determine,during the entire
duration of use,the compliance of the necessary occupational
safety measures with the current valid regulations and take
note of new regulations.
2.5CE conformity
VEGASWING 61 is in CE conformity with EMC (89/336/EWG),
fulfils NAMUR recommendation NE 21 and is in CE conformity
with LVD (73/23/EWG).
Conformity has been judged according to the following
standards:
VEGASWING 61 - - transistor (NPN/PNP)5
For your safety
29225-EN-070614

lEMC:
-Emission EN 61326/A1:1998 (class B)
-Susceptibility EN 61326:1997/A1:1998
lLVD:EN 61010-1:1993
2.6SIL conformity
VEGASWING 61 fulfills the requirements to functional safety
according to IEC 61508 resp.IEC 61511.You find further
information in the Safety Manual "VEGASWING series 60".
2.7Safety instructions for Ex areas
Please note the Ex-specific safety information for installation
and operation in Ex areas.These safety instructions are part of
the operating instructions manual and come with the Ex-
approved instruments.
2.8Manufacturer declaration
In conformity with DIN EN 60079-14/2004,para.5.2.3,point
c1,VEGASWING 61 is suitable for use in zone 2.
The operator must use the instrument as it was intended to be
used and follow the specifications of the following documents:
lthis operating instructions manual
lthis manufacturer declaration (24612)
lthe valid installation regulations
Max.increase of the surface temperature during operation:
65 K(individual components in the instrument)
With an ambient temperature of 70 °C(158 °F)on the housing
and a process temperature of 70 °C(158 °F), the max.ambient
temperature during operation is 135 °C(275 °F).
Measures to maintain explosion protection during operation:
lOperate the instrument in the range of the specified
electrical limit values.Permissible supply voltage:see
"Technical data"
lMount and operate the instrument in such a way that no
danger of ignition by electrostatic charges is to be
expected.Process fitting,plastic-coated probe part or
housing (as the case may be depending on instrument
version)are made of electrically non-conductive plastic.
6VEGASWING 61 - - transistor (NPN/PNP)
For your safety
29225-EN-070614

lMake sure that the seal is mounted correctly between
lower part of the housing and cover.Screw the cover on
tightly.
lMake sure there is no explosive atmosphere present if you
intend to operate the instrument with opened cover
lMake sure that the cable gland is tight and strain-relieved.
The outer diameter of the connection cable must be
adapted to the cable gland.Tighten the pressure screw of
the cable gland carefully.
lCover unused openings for cable glands tightly
lMount the instrument in such a way that the sensor cannot
touch the vessel wall or vessel installations.Keep in mind
the influence of product movement in the vessel.
lThe surface temperature of the housing must not exceed
the ignition temperature of the surrounding explosive
atmosphere
This instrument was assessed by a person who fulfils the DIN
EN 60079-14 requirements.
2.9Environmental instructions
Protection of the environment is one of our most important
duties.That is why we have introduced an environment
management system with the goal of continuously improving
company environmental protection.The environment man-
agement system is certified according to DIN EN ISO 14001.
Please help us fulfil this obligation by observing the environ-
mental instructions in this manual:
lChapter "Packaging,transport and storage"
lChapter "Disposal"
VEGASWING 61 - - transistor (NPN/PNP)7
For your safety
29225-EN-070614

3Product description
3.1Configuration
The scope of delivery encompasses:
lVEGASWING 61 level sensor
lDocumentation
-this operating instructions manual
-Safety Manual "Functional safety according to
IEC 61508 or IEC 61511 (SIL)"
-Supplementary instructions manual "Plug connector for
level sensors"(optional)
-Ex-specific"Safety instructions"(with Ex-versions)
-if necessary,further certificates
VEGASWING 61 consists of the following components:
lHousing cover
lHousing with electronics
lprocess fitting with tuning fork
1
2
3
Fig.1:VEGASWING 61 with plastic housing
1Housing cover
2Housing with electronics
3Process fitting
3.2Principle of operation
VEGASWING 61 is a level sensor with tuning fork for level
detection.
It is designed for industrial use in all areas of process
technology and can be used in liquids.
Scope of delivery
Components
Area of application
8VEGASWING 61 - - transistor (NPN/PNP)
Product description
29225-EN-070614

Typical applications are overfill and dry run protection.With a
tuning fork of only 40 mm length,VEGASWING 61 can be also
mounted,e.g.in pipelines from DN 25.The small tuning fork
allows use in vessels,tanks and pipes.Thanks to its simple
and robust measuring system,VEGASWING 61 is virtually
unaffected by the chemical and physical properties of the
liquid.
It functions even under difficult conditions such as turbulence,
air bubbles,foam generation,buildup,strong external vibration
or changing products.
Fault monitoring
The electronics module of VEGASWING 61 continuously
monitors via frequency evaluation the following criteria:
lStrong corrosion or damage on the tuning fork
lloss of vibration
lLine break to the piezo drive
If a malfunction is detected or in case of power failure,the
electronics takes on a defined switching condition,i.e.the
output transistor blocks (safe condition).
The tuning fork is piezoelectrically energised and vibrates at its
mechanical resonance frequency of approx.1200 Hz.The
piezos are fixed mechanically and are hence not subject to
temperature shock limitations.The frequency changes when
the tuning fork is covered by the medium.This change is
detected by the integrated oscillator and converted into a
switching command.
VEGASWING 61 is a compact instrument,i.e.it can be
operated without external evaluation system.The integrated
electronics evaluates the level signal and outputs a switching
signal.With this switching signal,a connected device can be
operated directly (e.g.a warning system,aPLC,a pump etc.).
The data for power supply are stated in chapter "Technical
data"in the "Supplement".
3.3Operation
The switching condition of VEGASWING 61 with plastic
housing can be checked when the housing is closed (signal
lamp). In the basic adjustment,products with a density >0.7g/
cm³(0.025 lbs/in³)can be detected.The instrument can be
adapted if products with lower density should be measured.
Functional principle
Supply
VEGASWING 61 - - transistor (NPN/PNP)9
Product description
29225-EN-070614

On the electronics module you will find the following indicating
and adjustment elements:
lsignal lamp for indication of the switching condition (green/
red)
lDIL switch for sensitivity adjustment
lMode switch for selection of the switching condition (A/B)
3.4Storage and transport
Your instrument was protected by packaging during transport.
Its capacity to handle normal loads during transport is assured
by a test according to DIN EN 24180.
The packaging of standard instruments consists of environ-
ment-friendly,recyclable cardboard.In addition,the sensor is
provided with a protective cover of ABS.For special versions
PE foam or PE foil is also used.Dispose of the packaging
material via specialised recycling companies.
lStorage and transport temperature see "Supplement -
Technical data -Ambient conditions"
lRelative humidity 20 …85 %
Packaging
Storage and transport tem-
perature
10 VEGASWING 61 - - transistor (NPN/PNP)
Product description
29225-EN-070614

4Mounting
4.1General instructions
In general,VEGASWING 61 can be mounted in any position.
The instrument must be mounted in such a way that the tuning
fork is at the height of the requested switching point.
The tuning fork has lateral markings (notches)that indicate the
switching point with vertical mounting.The switching point
refers to water with the basic setting of the sensitivity switch
>=0.7g/cm³(0.025 lbs/in³). When mounting VEGASWING 61,
make sure that this marking is at the height of the requested
switching point.Keep in mind that the switching point of the
instrument is shifted if the medium has a density other than
water -water =1g/cm³(0.036 lbs/in³). For products <0.7g/cm³
(0.025 lbs/in³)and >0.5g/cm³(0.018 lbs/in³)the density switch
must be set to >=0.5g/cm³.
Keep in mind that foams with a density >0.45 g/cm³(0.016 lbs/
in³)are detected by the sensor.This can cause faulty
switchings particulary when used as dry run protection system.
2
3
14
Fig.2:Vertical mounting
1Switching point approx.13 mm (0.51 in)
2Switching point with lower density
3Switching point with higher density
4Switching point approx.27 mm (1.06 in)
Switching point
VEGASWING 61 - - transistor (NPN/PNP)11
Mounting
29225-EN-070614

1
Fig.3:Horizontal mounting
1Switching point
1
2
Fig.4:Vertical installation (recommended installation position,especially for
adhesive products)
1Switching point
2Marking with screwed version on top,with flange versions directed to the
flange holes
With flange versions,the fork is directed as follows to the
flange holes.
Fig.5:Fork position with flange versions
Use the recommended cables (see chapter "Connecting to
power supply")and tighten the cable gland.
You can give your VEGASWING 61 additional protection
against moisture penetration by leading the connection cable
downward in front of the cable entry.Rain and condensation
Moisture
12 VEGASWING 61 - - transistor (NPN/PNP)
Mounting
29225-EN-070614

water can thus drain off.This applies mainly to mounting
outdoors,in areas where moisture is expected (e.g.by
cleaning processes)or on cooled or heated vessels.
Fig.6:Measures against moisture penetration
Do not hold VEGASWING 61 on the tuning fork.Particularly
with flange or tube versions,the tuning fork can be damaged
just by the weight of the instrument.Transport coated
instruments very carefully and avoid touching the tuning fork.
Remove the protective cover just before mounting.
The process fitting must be sealed if there is gauge or low
pressure in the vessel.Before use,check if the seal material is
resistant against the measured product and the process
temperature.
The max.permissible pressure is stated in chapter "Technical
data"in the "Supplement"or on the type label of the sensor.
The vibrating level switch is a measuring instrument and must
be treated accordingly.Bending the vibrating element will
destroy the instrument.
Warning:
The housing must not be used to screw the instrument in!
Applying tightening force on the housing can damage its
rotational mechanical parts.
To screw in,use the hexagon above the thread.
Transport
Pressure/Vacuum
Handling
VEGASWING 61 - - transistor (NPN/PNP)13
Mounting
29225-EN-070614

4.2Mounting instructions
VEGASWING 61 has a defined thread starting point.This
means that every VEGASWING 61 is in the same fork position
after being screwed in.Remove therefore the supplied seal
from the thread of VEGASWING 61.This seal is not required
when using a welded socket with O-ring in front.
Keep in mind that this welded socket is not suitable for coated
instrument versions.
Screw VEGASWING 61 completely into the welded socket.
The later position can be determined already before welding.
Mark the appropriate position of the welded socket.Before
welding,unscrew VEGASWING 61 and remove the rubber ring
from the welded socket.The welded socket has a marking
(notch). Weld the socket with the notch facing upward,or in
case of pipelines,aligned with the direction of flow.
1
Fig.7:Marking on the welded socket
1Marking
In case of horizontal mounting in adhesive and viscous
products,the surfaces of the tuning fork should be vertical in
order to reduce buildup on the tuning fork.On the screwed
version you will find a marking on the hexagon.With this,you
can check the position of the tuning fork when screwing it in.
When the hexagon touches the seal,the thread can still be
turned by approx.half a turn.This is sufficient to reach the
recommended installation position.
With flange versions,the fork is directed to the flange holes.
When used in adhesive and viscous products,the tuning fork
should protrude into the vessel to avoid buildup.For that
reason,sockets for flanges and mounting bosses should be
avoided when mounting horizontally.
Welded socket
Adhesive products
14 VEGASWING 61 - - transistor (NPN/PNP)
Mounting
29225-EN-070614

IfVEGASWING 61 is mounted in the filling stream,unwanted
mismeasurements may result.Mount VEGASWING 61 at a
location in the vessel where no disturbing influence from e.g.
filling openings,agitators,etc.can occur.
To minimise flow resistance caused by the tuning fork,
VEGASWING 61 should be mounted in such a way that the
surfaces of the blades are parallel to the product movement.
Inflowing medium
Flows
VEGASWING 61 - - transistor (NPN/PNP)15
Mounting
29225-EN-070614

5Connecting to power supply
5.1Preparing the connection
Always keep in mind the following safety instructions:
lConnect only in the complete absence of line voltage
In hazardous areas you should take note of the appropriate
regulations,conformity and type approval certificates of the
sensors and power supply units.
Connect the power supply according to the following diagrams.
Take note of the general installation regulations.As a rule,
connect VEGASWING 61 to vessel ground (PA), or in case of
plastic vessels,to the next ground potential.On the side of the
instrument housing there is a ground terminal between the
cable entries.This connection serves to drain offelectrostatic
charges.InEx applications,the installation regulations for
hazardous areas must be given priority.
You can find data on voltage supply in chapter "Technical
data"in the "Supplement".
VEGASWING 61 is connected with standard cable with round
cross section.An outer cable diameter of 5…9mm
(0.2…0.35 in)ensures the seal effect of the cable gland.
If cable with a different diameter or wire cross section is used,
exchange the seal or use an appropriate cable connection.
In hazardous areas,only use approved cable connections for
VEGASWING 61.
Take note of the corresponding installation regulations for Ex
applications.
5.2Connection procedure
With Ex instruments,the housing cover may only be opened if
there is no explosive atmosphere present.
Proceed as follows:
1Unscrew the housing cover
2Loosen compression nut of the cable entry
Note safety instructions
Take note of safety
instructions for Ex
applications
Select power supply
Selecting connection cable
Select connection
cable for Ex applica-
tions
16 VEGASWING 61 - - transistor (NPN/PNP)
Connecting to power supply
29225-EN-070614

3Remove approx.10 cm (4in)of the cable mantle,strip
approx.1cm (0.4in)insulation from the ends of the
individual wires
4Insert the cable into the sensor through the cable entry
5Open the terminals with a screwdriver
6Insert the wire ends into the open terminals according to
the wiring plan
7Tighten the terminals with a screwdriver
8Check the hold of the wires in the terminals by lightly
pulling on them
9Tighten the compression nut of the cable entry.The seal
ring must completely encircle the cable
10 Screw the housing cover back on
The electrical connection is finished.
5.3Wiring plan,single chamber housing
The following illustrations apply to the non-Ex as well as to the
EEx d version.
1
4
44
2 3
Fig.8:Material versions,single chamber housing
1Plastic (not with EEx d)
2Aluminium
3Stainless steel (not with EEx d)
4Filter element for pressure compensation or blind stopper with version IP 66/
IP 68,1bar (not with EEx d)
Housing overview
VEGASWING 61 - - transistor (NPN/PNP)17
Connecting to power supply
29225-EN-070614

SW E60T
1 0 -55V DC
1PNP2 3 4 1 NPN2 3 4
A
B
0,5g/cm3
0,7g/cm3
max 4 00m A
out
1 2 3 4
+
++
3
5
1
2
4
Fig.9:Electronics and connection compartment,single chamber housing
1Control lamp
2DIL switch for mode adjustment
3DIL switch for switching point adaptation
4Ground terminal
5Screwed terminals
We recommend connecting VEGASWING 61 in such a way
that the switching circuit is open when there is a level signal,
line break or failure (safe condition).
The instrument is used to control relays,contactors,magnet
valves,warning lights,horns as well as PLC inputs.
+ -
1 2 3 4
+-
Fig.10:NPN action
Electronics and connection
compartment
Wiring plan
18 VEGASWING 61 - - transistor (NPN/PNP)
Connecting to power supply
29225-EN-070614

+ -
1 2 3 4
+-
Fig.11:PNP action
5.4Wiring plan -version IP 66/IP 68,1bar
1
2
3
4
5
Fig.12:Wire assignment connection cable.The numbers of the wires
correspond to the terminals of the instrument.
1brown (+)voltage supply
2White
3Yellow
4blue (-) voltage supply
5Screen
Wire assignment,connection
cable
VEGASWING 61 - - transistor (NPN/PNP)19
Connecting to power supply
29225-EN-070614

6Set up
6.1In general
The numbers in brackets refer to the following illustrations.
The switching condition of the electronics can be checked on
the plastic housing with closed housing cover (control lamp). In
the basic setting,products with a density >0.7g/cm³(0.025 lbs/
in³)can be detected.For products with lower density,the
switch must be set to >0.5g/cm³(0.018 lbs/in³).
On the electronics module you will find the following indicating
and adjustment elements:
lSignal lamp (1)
lDIL switch for mode adjustment -A/B(2)
lDIL switch for sensitivity adjustment (3)
Note:
For test purposes,immerse the tuning fork of VEGASWING 61
always in liquids.Do not test the function of VEGASWING 61
with the hand.This can damage the sensor.
6.2Adjustment elements
1234
1
2
3
Fig.13:Oscillator SWE60T-Transistor output
1Signal lamp (LED)
2DIL switch for mode adjustment
3DIL switch for sensitivity adjustment
Function/Configuration
20 VEGASWING 61 - - transistor (NPN/PNP)
Set up
29225-EN-070614
Other manuals for VEGASWING 61
6
Table of contents
Other Vega Accessories manuals

Vega
Vega VEGAPULS 6X User manual

Vega
Vega VEGAFLEX 82 User manual

Vega
Vega VEGASON 62 User manual

Vega
Vega POINTRAC 31 User manual

Vega
Vega VEGAFLEX 86 User manual

Vega
Vega VEGAFLEX 82 User manual

Vega
Vega VEGAPULS 69 User manual

Vega
Vega VEGASON 61 User manual

Vega
Vega VEGAPULS 63 User manual

Vega
Vega VEGAFLEX 65 User manual

Vega
Vega VEGAFLEX 65 User manual

Vega
Vega B-LIFT 8120 200 Evo Series User manual

Vega
Vega vegacap 62 User manual

Vega
Vega VEGAPULS 61 User manual

Vega
Vega VEGACAL 66 User manual

Vega
Vega VEGAPULS WL 61 User manual

Vega
Vega POINTRAC 31 User manual

Vega
Vega VEGAPULS 61 User manual

Vega
Vega VEGAPULS 66 Profibus PA User manual

Vega
Vega VEGACAL 62 User manual